VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Nr. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 22 23 24 25 26 27 28 29 30 31 32 33 34 36 37 38 40 41 42 46 47 48 49 50 51 52 53 54 55 56 57 58 59



Description



Display Message



Software 5.5x



Warning



Possible cause(s)



10V low Live zero error No motor Mains phase loss DC voltage high DC voltage low DC overvoltage DC undervoltage Inverter overload Motor ETR overload Motor thermistor overload Torque limit Over current Earth fault Incompatible hardware Short circuit Controlword-Timeout Hoist Mech. Brake Internal fans External fans Brake resistor Brake overload Brake IGBT fault Brake check Heatsink temp Motorphase U missing Motorphase V missing Motorphase W missing Inrush fault Fieldbus fault Mains failure Phase imbalance Internal fault Overload on digital output terminal 27 Overload on digital output terminal 29 Overload on digital output terminal 30/6-7 Power card supply 24 V supply low 1,8 V supply low Speed limit AMA-Calibration AMA-Unom, Inom AMA-Low Inom AMA-Big motor AMA-Small motor AMA-Parameter range AMA-Interrupt AMA-Timeout AMA-Internal fault Current limit



X (X) (X) (X) X X X X X (X) (X) X X X (X) (X) (X) X (X) X (X) X (X) (X) (X) X X (X) X X X X X X X



X



Alarm



Trip-lock



(X) (X) X X X (X) (X) (X) X X X X (X) (X) (X) (X)



(X)



X X X X



(X) (X) X (X) (X) (X) X X X (X) X



X X X X X X X X X X X X



Parameter



Possible solution(s)



X (X) (X) (X) X



X



X X X



Page



3 3 4 4 5 5 6 6 7 1-90 7 1-90 8 14-25 8 9 9 10 10 8-04 10 1-72 11 14-53 11 14-53 11 12 2-13 12 12 2-15 13 13 4-58 14 4-58 14 4-58 14 14 15 15 14-12 16 16 5-00 / 5-01 16 5-00 / 5-02 16 5-32 event. 5-33 17 17 17 17 18 18 18 19 19 19 19 20 20 20 21 6-01 1-80 14-12



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 1 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



61 62 63 64 65 66 67 68 69 70 71 72 79 80 90 91 -



Display Message Tracking error



Possible cause(s) (X) X



Output frequency limit Mechanical brake low Voltage limit Controlcard temperature Low temperature Option change Safe stop FC Overtemp Illegal FC-config PTC1 Safe Stop Dangerous Failure Illegal PS config Drive initialized Feedback monitoring Analog input set wrong Display dark



(X)



Possible solution(s) 4-30 4-19 2-20



X



X X X



X X (X) X (X)



(X) (X)



X



X (X) X



(X)



5-19



X (X) X X



5-19



17-61 Switch A-54



21 22 22 23 23 23 24 24 24 25 25 25 26 26 26 27 27



(X) Parameter dependent



General advice Overview LCP 102 Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Live zero error [W2] Auto Remote Running



Warning



²@ 2.121



Status 0RPM



0.00A



³@ 2.121



¡µ ¡Hz ¢¡¡% ³Live zero error [A2] Auto Remote Trip



Alarm



Status 0RPM



0.00A



³@ 2.121



¡µ ¡Hz ¢¡¡% ³Mains ph. loss [A4] Auto Remote Trip lock



Trip lock



The operation values shown on the display give detailed information about the status of the drive and the connected peripherals. With the LCP 102 you can choose these values freel in the Parameter group 0-2*. These values are accessible also when warning and alarm messages are shown. Alarm Reset The reset of an Alarm is possible in either way - The [Reset] Key on the LCP (The [Off] Key is activated simultaneously) - Terminal control (Parameter setting in Group 5-1*) - The automatic reset function (Parameter setting in Group 14-2*) - Reset signal via serial communication (e.g. RS-485 or Profibus) Alarm with Trip lock An Alarm with Trip lock can be reset only after a complete mains off (Display dark). If the drive is equipped with an external 24V supply (D-option), it is enough to switch off mains and then reset the Alarm. The control card remains active, e.g. for serial communication via Fieldbus. After a mains Off/On it is possible to reset an Alarm on the VLT® FC 300 as mentioned above.



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 2 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message



Possible cause(s)



Possible solution(s)



Note: ²@ The internal 10V Voltage supply A change of the signal type 1.52A 2.121 is overloaded. (Voltage/Current) via the DIP switch S201/S202 A-53/A-54 ¢¥µ¹% is effective only after a mains off. ¡¡¡¡¢¢¢¡¡¡bin



Status 150RPM



²10V low [W1] Auto Remote Running The type of the signal (Current or Voltage) and the scale of the terminals 53 & 54 can be shown on the Display.



1



1. Terminal 50 is short-circuited 1. Check the connection of the part connected between termibecause of: nal 50 and 53/54, eventually - a faulty connection the part itself onto a short- a defect on an external part (e.g. an potentiometer) circuit (min. 590 Ω) 2. Too many external devices are 2. The power consumption of the powered by the 10V supply 10 Volt supply (Terminal 50) must not exceed 15 mA



10 Volt low



3. The chosen signal type on the 3. Make sure that he DIP switch position on S201(A-53) or input does not match the connected signal (U or I) S202(A-54) matches the connected signal type (U or I) 4. The internal 10 Voltage supply 4. Please contact your local Danis defective foss supplier!



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Live zero error [W2] Auto Remote Running Status 0RPM



0.00A



The Live Zero Timeout Function ²@ (Par.6-01) of terminals 53 & 54 is 2.121 activated. The active Signal value is below 50% of the min. U/I – Scale of the terminal for a time period defined in Par. 6-00.



Please check Par. 6-00 und 6-01 ² Par. 6-01 ≠ Off setting. ³ Par. 6-01 = Stop und Trip ³@ Stops the Motor (Coasting) and triggers the Alarm 2.121



¡µ¡Hz ¡% ³ Live zero error [A2] Auto Remote Trip The type of the signal (Current or Voltage) and the scale of the terminals 53 & 54 can be shown on the Display.



2



Live zero error



Note: A change of the signal type (Voltage/Current) via the DIP switch S201/S202 A-53/A-54 is effective only after a mains off.



1. The signal lead is interrupted



1. Check the signal cables for breaks



2. The limits that are set for the 2. Check the limits: Terminal 53: Par. 6-10 & 6-12 terminals are not optimised Terminal 54: Par. 6-20 & 6-22 3. The signal is disturbed (e.g. EMC- influence)



3. Make sure that the installation is EMC-correct



4. The chosen signal type of the analog input does not match the connected signal type (Current or Voltage)



4. Make sure that he DIP switch position on S201(A-53)/ S202(A-54) matches the connected signal type (U or I) Reset via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 3 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



Possible cause(s)



²@ In Par. 1-80 Motor check was Make sure that the motor is activated as a stop function. connected properly to the output 2.121 of the FC 300 The FC 300 cannot detect a motor on the converter output. Note: A missing motor phase is NOT detected by the Motor check function.



²No Motor [W3] Auto Remote Motor check 3



No motor



Status 150RPM



1.52A



A phase is missing on the supply Perform an mains On/Off. ²@ side or the mains voltage 2.121 imbalance is too high.



¶¡µ£Hz ¢¡¡%



²



²Mains ph. loss [W4] Auto Remote Run on ref. Status 0RPM



0.00A



Possible solution(s)



³@ 2.121



Par. 14-12 = Warning shows just a warning. The motor is still driven.



³ Par. 14-12 = Alarm stops the motor after a short warning (Coasting) and then triggers an alarm.



¡µ¡Hz ¢¡¡% ³ Mains ph. loss [A4] Auto Remote Trip lock 4



Mains phase loss



1. One or more power supplies 1. Check the power supply for the VLT® AutomationDrive FC 300 are interrupted 2. A mains phase is missing or 2. Check the mains for imbalance (the voltage difference of the the imbalance is too high three phases must not exceed ± 3% of the nominal supply 3. There are cyclic loads or voltage) load imbalances in the system 4. The rectifier of the VLT® is defective



3. Check the system/application on the motor side for cyclic loads or load imbalances



Note: Alarm 4 protects the VLT® against 4. Please contact your local Danfoss supplier! damage caused by mains imbalance. It is triggered only after an according load on the VLT® output. Attention: The deactivation of the Mains phase loss detection (Par. 14-12≠ Alarm) can lead to warranty loss.



Reset (with ext. 24V supply during Mains-Off) via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 4 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¡µ¡Hz ¢¡¡%



²@ The intermediate circuit voltage is higher then the DC-high limit. 2.121 The over voltage limit is not yet reached.



²DC voltage high [W5] Auto Remote Running The DC link voltage can be shown on the Display (UDC).



5



DC voltage high



Possible cause(s)



1. Generating operation: a) The down ramps are too short b) The inertia of the load is too big c) The brake electronics of the VLT® is defective or overloaded



4. Interaction between the VLT® and the idle current compensation device



1.52A ¶¡µ£Hz ¢¡¡%



²DC voltage low [W6] Auto Remote Running 6



DC voltage low



Limits (w/wo. Brake) 3x200-240V -> 390/405V DC 3x380-500V -> 810/840V DC 3x525-600V -> 943/965V DC 3x525-690V -> 1084/1109V DC 1. Reduce the generative energy: a) Set longer down ramps b) Reduce the load, activate Over Voltage Control (Par. 2-17), resp. activate ACBrake (Par. 2-10, please see Note) or use a VLT® with a brake resistor c) Please contact your local Danfoss supplier



2. Mains transients in the supply voltage 3. Over voltage in the power supply



Status 150RPM



Possible solution(s)



2. Check the mains for possible transients 3. Check the mains for possible over voltage



Note: Over voltage control can lead to prolonged ramp times and ACBrake can lead to additional warming of the motor.



4. Check mains conditions eventually use idle current compensation devices with chokes



²@ The intermediate circuit voltage is lower then the DC-low limit. 2.121 The under voltage limit is not yet reached.



Switch the mains supply Off and On.



1. The mains supply was disconnected (see Note) 2. The supply voltage does not match the VLT®



1. Check the connections of the VLT® AutomationDrive FC 300 2. Check the mains for imbalance (the voltage difference of the three phases must not exceed ± 3% of the nominal supply voltage)



3. The mains supply is not stable or overloaded. Eventually 3. Check the system/application loads with high starting curon the motor side for cyclic rents are connected in parallel loads or load imbalances with the VLT®. Note: When the mains are disconnected, warning 6 is shortly shown on the display of the VLT®.



Reset (with ext. 24V supply during Mains-Off) via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 5 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²DC over volt [W7] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



Limits 3x200-240V 3x380-500V 3x525-600V 3x525-690V



1. Generating operation: a) The down ramps are too short ³@ b) The inertia of the load is too big 2.121 c) The brake electronics of the VLT® is defective or overloaded



1. Reduce the generative energy: a) Set longer down ramps b) Reduce the load, activate Over Voltage Control (Par. 2-17) resp. AC Brake (Par. 2-10) (see Note) or use a VLT® with a brake resistor c) Please contact your local Danfoss supplier



2. Mains transients in the supply voltage



The DC link voltage can be shown on the Display (UDC).



3. Over voltage in the power supply 4. Interaction between the VLT® and the idle current compensation device



DC over voltage



Note: Over voltage control can lead to prolonged ramp times and ACBrake can lead to additional warming of the motor. Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²DC under volt [W8] Auto Remote Running Status 0RPM



0.00A



does not ³@ 1. The supply voltage ® match the VLT 2.121



³DC under volt [A8] Auto Remote Trip The DC link voltage can be shown on the Display (UDC).



DC under voltage NOT on drives with ext. 24 V DC supply



2. The mains supply was interrupted



-> -> -> ->



410V DC 855V DC 975V DC 1130V DC



2. Check the mains for possible transients 3. Check the mains for possible over voltage 4. Check mains conditions eventually use idle current compensation devices with chokes Reset via [Reset], Terminal or Bus



²@ The intermediate circuit voltage is Limits 2.121 lower then the under voltage limit 3x200-240V of the drive. 3x380-500V 3x525-600V The VLT® will trip with an alarm 3x525-690V after a short warning message.



¡µ¡Hz ¢¡¡%



8



Possible solution(s)



²@ The intermediate circuit voltage is higher then the over voltage 2.121 limit of the drive. The VLT® will trip with an alarm after a short warning message.



³DC over volt [A7] Auto Remote Trip



7



Possible cause(s)



-> -> -> ->



185V 373V 532V 553V



DC DC DC DC



1. Check the supply to the VLT® (see name plate) 2. Check the connections of the VLT® AutomationDrive FC 300



3. The mains supply is not stable 3. Check the dimensioning of the mains supply or overloaded. Eventually loads with high starting currents are connected in parallel with the VLT®. Reset via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 6 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Inverter overld. [W9] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Inverter overld. [A9] Auto Remote Trip The thermal load of the (in %) can be shown on play.



9



Inverter overload



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Motor ETR over [W10] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Motor ETR over [A10] Auto Remote Trip The thermal load of the (in %) can be shown display.



10



Motor ETR overload



Possible cause(s)



Possible solution(s)



²@ The inverter of the VLT® is ther2.121 mally overloaded, because the output current was too long over The Reset of the alarm is posthe rated limit. sible only when the load is below 90%. ² Warning on 98% load ³ Alarm on 100% load ³@ 1. The current input is too high 1. Make sure that the input current of the motor matches because of: 2.121 the output current of the VLT®: a) Set correct motor data a) Wrong motor data Group 1-2* (1-5* / 1-6*) (Over compensation) b) Check the motor b) Defect motor c) Use a bigger VLT® c) The VLT® is too small d) Check load conditions d) The motor is overloaded inverter e) Reduce the length of motor e) The motor cable is too long the discables or use a LC-Filter 2. The switching frequency is too 2. Reduce the switching frequency (Par.14-10) and check high the switching pattern (Par. 14-00); eventually use a bigger VLT® Reset via [Reset], Terminal or Bus The Motor Thermal Protection ²@ (ETR) was activated in Par. 1-90 2.121 and the timer for the calculated thermal motor load has reached 100%.



Note: The ETR function is designed for self-ventilated motors. For motors with external ventilation please check Par. 1-91.



² Par. 1-90 = ETR Warning ³ Par. 1-90 = ETR Alarm stops the motor (Coasting) and ³@ triggers the alarm 2.121 thermally 1. The motor is overloaded: a) The permanent load is too high b) Low RPM with relatively high load (reduced selfventilation of the motor) inverter on the c) Motor blocked



A Reset of the alarm is possible only with 0% of thermal load. 1. Check the load: a) Check the load conditions b) Adjust the load for low RPM conditions, use a motor with external ventilation c) remove the blockage of the motor 2. Check motor data (Group 1-2*) Reset via [Reset], Terminal or Bus



2. Wrong motor data (Over compensation)



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 7 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



² Motor th over [W11] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Motor th over [A11] Auto Remote Trip 11



1.52A ¶¡µ£Hz ¢¡¡%



0.00A



the Sensor type 2. The settings for the KTY Sensor 2. Check (Par. 1-95) and the Threshold do not match the used part level (Par. 1-97) of the KTY Sensor 3. The motor is overheated or the Thermistor/KTY Sensor is defect resp. the connection is 3. Check the motor, the Sensor and their connection interrupted Reset via [Reset], Terminal or Bus The torque is higher then the va²@ lue set in Par. 4-16 (motor mode) 2.121 resp. in Par.4-17 (generator mode). ³ The torque limit is reached and the time set in Par. 14-25 did run out ³@ 1. The motor is blocked resp. 1. Check the load conditions 2.121 overloaded



¡µ¡Hz ¢¡¡% ³Torque limit [A12] Auto Remote Trip If in Par. 14-25 the time is set to 0s, the VLT® will immediately trigger an alarm when reaching the Torque limit.



12



Torque limit



Note: The choice of the appropriate terminal depends on the specification of the used motor protection element.



² Par.1-90=Thermistor Warning ³ Par.1-90=Thermistor Trip stops the motor (Coasting) and ³@ triggers the alarm 2.121 1. The Sensor is not connected 1. Check the allocation of the terminals: between the terminal and - Thermistor: Par. 1-93 earth according to Par. 1-93 - KTY Sensor: Par. 1-96 resp. 1-96



²Torque limit [W12] Auto Remote Running Status 0RPM



Possible solution(s)



²@ The evaluation of the thermal motor protection in Par. 1-90 was 2.121 activated. The used motor protection (Thermistor/KTY Sensor) has triggered.



Motor thermistor overload



Status 150RPM



Possible cause(s)



2. Too short Up/Down ramps



2. Adjust the ramp times (Group 3-4* to 3-8*)



3. Wrong motor data resp. 3. Check motor data (Group 1-2*) and motor connection wrong motor connection (Y/Δ) 4. Over compensation motor



of



the 4. Check the compensation parameters (Group 1-5* & 1-6*)



5. The value set in Par. 4-16 / 4- 5. Adjust Par. 4-16 and Par. 4-17 17 is too low Reset via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 8 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A



³ After ca. 8-12s the motor is Switch mains supply off and on set loose and the alarm is trig- again. gered



²Over Current [W13] Auto Remote Running



0.00A



³@ 2.121



1. The motor is blocked resp. 1. Check the load conditions overloaded 2. Too short Up/Down ramps



¡µ¡Hz ¢¡¡%



When the mechanical brake control is active, the alarm can be reset without mains off.



Over current



2. Adjust the ramp times (Group 3-4* to 3-8*)



3. Wrong motor data resp. 3. Check motor data (Group 12*) and motor connection wrong motor connection (Y/Δ)



³Over Current [A13] Auto Remote Trip lock



13



Possible solution(s)



²@ The peak current limit of the inverter is exceeded (ca. 180% of 2.121 the rated VLT® current).



¶¡µ£Hz ¢¡¡%



Status 0RPM



Possible cause(s)



4. Overcompensation of the mo- 4. Check compensation parameters (Group 1-5* & 1-6*) tor 5. Torque limits (Par.4-16 and/or 5. Adjust setting of Par. 4-16 and Par. 4-17 Par. 4-17) are too low Reset via [Reset], Terminal or Bus



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Earth fault [W14] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Earth fault [A14] Auto Remote Trip lock 14



Earth fault



²@ The VLT® has detected an earth Disconnect mains. 2.121 fault, i.e. a leakage current flows from the output phases to earth. 1. Check VLT® output, Motor und Motor cable 1. Earth fault in the cable between the VLT® and the motor 2. Remove the earth fault on the Motor, or change the Motor 2. Earth fault in the motor 3. Check the repair switch / con³@ 3. The repair switch / contactors tactors 2.121 between the drive and the motor are ohmically not 4. Initialize the internal current symmetrical (e.g. contacts are measuring of the VLT® with an swollen) Manual Reset. 4. The calibration of the internal current sensor of the VLT® is To do this, please hold the folnot symmetrical anymore lowing keys pressed, until the internal fan of the VLT® starts: Note on manual reset Save your parameterisation beLCP 101:[Main Menu] fore resetting the VLT® to factory LCP 102: Status]+[OK]+[Main Menu] settings (e.g. via Par. 0-50 LCPConnect mains again. Copy)! Reset Attention: A deactivated EMC Filter (Par. 14-50) is activated (with ext. 24V during Mains-off) again after a Manual Reset! via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 9 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM 0.00A 15 Inkompatible Hardware ¡µ¡Hz ¢¡¡%



Possible cause(s)



Possible solution(s)



³@ An installed Option is not sup- Use a drive with a newer software ported from the control card version or a option with an older 2.121 (Hardware or Software). software version. Please contact your local Danfoss supplier!



³Incomp.HW [A15] Auto Remote Trip lock 16Status Short circuit 0RPM 0.00A ¶¡µ£Hz ¢¡¡%



® ²@ The VLT detected a short circuit, Disconnect mains, regarding all that means a short circuit current Safety precautions (e.g. secure 2.121 flows between two output phases. mech. brake), disconnect the Motor and connect mains again.



Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



³Short Circuit [A16] Auto Remote Trip lock.



Start the VLT® for a test. 1. Short circuit in the power 1. If the Alarm 16 is shown section, resp. on the output of again, then there is probably a the VLT® fault in the VLT® power section. Please contact your local Danfoss supplier! 2. Short circuit in the Motor or 2. Is the VLT® running without an Motor cable Alarm message, there is an short circuit in the Motor or Motor cable. Remove the short circuit and connect the VLT® again. Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Ctrl. word TO [W17] Auto Remote Running Status 0RPM



0.00A



²@ The Control Word Timeout Function (Par. 8-04) was activated. A 2.121 control word, that was already active via Bus, is not valid. The Time-out time (Par.8-03) has run out. ² Par. 8-04 ≠ Off ³ Par. 8-04 = Stop and Trip Ramps down the Motor and ³@ triggers the Alarm 2.121



¡µ¡Hz ¢¡¡% ³Ctrl. word TO [A17] Auto Remote Trip An Ctrl. Word TO Alarm can be automatically using 17 reseted Controlword-Timeout Par. 8-06.



1. The bus line was interrupted



Check the settings of Par. 8-03 and 8-04 1. Check the interruptions



bus



lines



for



2. Check, if a Control word is active via bus



2. No control word is being sent 3. Secure the function of the interface Master and/or Convia bus anymore verter 3. The bus interface Master and/or Converter are defect or Reset via [Reset], Terminal or Bus not active



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 10 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Hoist Mech. brake [A22] Auto Remote Trip



23Status Internal fans 150RPM 1.52A ¶¡µ£Hz ¢¡¡% ²Internal Fans [W23] Auto Remote Running Status 0RPM



0.00A



Possible cause(s)



Possible solution(s)



1-01 is ³@ The setting of Par. Flux w/motor feedback. As a start 2.121 function (Par. 1-72) Hoist, mechanical brake was set.



1. The motor is not reaching the 1. Please check the motor data predefined Torque ref. (Par. 2(Group 1-2* / 1-5* & 1-6*) 26) and the settings of parameters 2-24 to 2-28. 2. A digital input was set to Mech. Brake Feedb. or Mech. 2. Check the electrical wiring of Brake Feedb. Inv. But the inthe feedback sensor and the put was not activated within a setting of Par. 2-25. time set in Par. 2-25 with a brake feedback signal from the Reset mech. Brake. (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



²@ The monitoring of the internal 2.121 fans was activated in Par 14-53. ² Par. 14-53 = Warning ³ Par. 14-53 = Alarm The Fan ³@ removed. 2.121



is



defect



or



was Check the fan and contact your local Danfoss supplier.



¡µ¡Hz ¢¡¡%



Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



³Internal Fans [A23] Auto Remote Trip Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²External Fans[W24] Auto Remote Running Status 0RPM 0.00A 24 External fans ¡µ¡Hz ¢¡¡%



Attention: Wrong settings can lead to the opening of the brake or to loosing the load!



²@ The monitoring of the internal Note: and external fans was activated In case that the VLT® is driven 2.121 without the fan, a power derating in Par. 14-53 is necessary to prevent possible overheating of the drive. ² Par. 14-53 = Warning ³ Par. 14-53 = Alarm 1. Check the fan and contact your local Danfoss supplier.



1. The Fan is defect



³@ the 2.121 2. The fan was removed on pur- 2. Check Par. 14-53 pose, e.g. for reducing acoustic noise



setting



in



Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



³External Fans [A24] Auto Remote Trip



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 11 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



Possible cause(s)



Possible solution(s)



® ® ²@ During operation, the VLT has Switch off the VLT and check detected a short circuit in the the Brake resistor. 2.121 Brake resistor.



The operation is further on possi- Exchange resistor. ble, but without brake function.



the



faulty



Brake



²Brake resistor [W25] Auto Remote Running 25



Brake resistor



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Brake overload [W26] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Brake overload [A26] Auto Remote Trip 26



The Brake Power Monitoring If necessary, use a 40% work ²@ (Par. 2-13) was activated. The cycle brake resistor. 2.121 Power (average) applied to the Brake resistor in the last 120s was too high: Switch mains off and on again. ² Warning on 90% load ³ Alarm on 100% load Par. 2-13 = Warning/Alarm or ³@ Alarm stops the Motor and trig2.121 gers the alarm 1. Faulty Brake resistor data



1. Check brake resistor data in Par. 2-11 and Par. 2-12



2. Too short down ramps



2. Adjust ramp times (Group 3-**)



3. Faulty Motor data (Overcompensation)



3. Check Motor data (Group 1-2*)



Brake overload



4. Faulty dimensioning Brake resistor.



of



the 4. Check brake resistor data (Par.2-11 / 2-12) and load cycle (10% resp. 40%) Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Brake IGBT [W27] Auto Remote Running 27 Brake IGBT fault



The VLT® has detected a short Switch off the VLT® and interrupt ²@ circuit in the Brake-IGBT and the line to the brake resistor. 2.121 turned off the brake function. The VLT® can still be driven, but because of the short circuit, a big load is applied to the brake resistor, although no brake process is realized.



Warning When a short circuit of the Brake-IGBT occurs, there is a risk of overheating the brake resistor and other equipment near by.



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 12 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Brake check [W28] Auto Remote Running Status 0RPM



0.00A



Switch Mains Off and On again ² Par. 2-15 = Warning ³ Par. 2-15 = Alarm stops the Check setting in Par. 2-15 Motor and triggers the Alarm ³ Par. 2-15 = Stop and trip ³@ stops the Motor and the trip lock 2.121 Alarm 1. Check the brake resistor



1. Brake resistor defect



³Brakecheck [A28] Auto Remote Trip The Brake check Warning is reseted only after a mains-off.



2. No brake resistor connected, 2. Check the electrical connection of the brake resistor resp. a fault in the connections. Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



Brake check



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Heatsink temp [W29] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³ Heatsink temp [A29] Auto Remote Trip lock



The temperature on the heat sink Switch the mains Off and On ²@ of the VLT® has reached the max. again 2.121 Beware: limit. The alarm can be reset only ³ The switch-off limit of 95°C for when the temperature of the IP20/IP21 was reached (Toler- heat sink has dropped to ca. 70°C. ance ± 5°C)



³@ 2.121



1. The ambient temperature is 1. Try to reduce the ambient temperature (check the design too high and ventilation of the cabinet) 2. Ensure the correct function of the cooling vents



2. Internal fans failure



3. Ventilation vents or the filter 3. Clean the ventilation vents and the change the filter pads pads are dirty 4. The motor cable is too long



29



Possible solution(s)



in ²@ The Brake resistor check Par. 2-15 was activated. A fault in 2.121 the brake circuit was detected.



¡µ¡Hz ¢¡¡%



28



Possible cause(s)



Power card thermal overload 5. Switching frequency Par 14-01 is too high



set



4. Check the length of the Motor cable. Consider the use of an LC filter. the switching in 5. Reduce frequency (Par. 14-10) and pattern (Par. 14-00); eventually use a bigger VLT® Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 13 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³U phase loss [A30] Auto Remote trip lock. Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³V phase loss [A31] Auto Remote trip lock. Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³W phase loss[A32] Auto Remote trip lock.



30 31 32 Status 0RPM



Motorphase U missing Motorphase V missing Motorphase W missing



0.00A ¶¡µ£Hz ¢¡¡%



³Inrush Fault [A33] Auto Remote trip lock.



33



Inrush Fault



Possible cause(s)



Possible solution(s)



²@ The Motor phase monitoring (Par. 4-58) is activated. The VLT® Switch the mains Off and On 2.121 has detected a missing motor again phase on the output. 1. The motor cable or not connected



is



defect 1. Check the motor cables and the connection for possible faults ³@ 2. Imbalance; eventually the motor is defect or internally 2. Check the motor and assure a 2.121 wrongly wired symmetrical load on the VLT® output 3. The motor is too small related to the VLT® AutomationDrive FC 300 ³@ 4. The external wiring of the 2.121 motor (neutral point ) is not complete



3. Use a FC 300 of adequate power 4. Ensure the right wiring of the motor (Star/Delta connection)



Note If the AMA is started without a Reset connected motor, the drive stops (with ext. 24V during Mains-off) showing Alarm 30. via [Reset], Terminal or Bus The sensitivity of the Motor phase monitoring can be adjusted in Par. 4-58. The inrush current was to high ²@ when the VLT® was switched on. Switch mains off and on again. 2.121 1. The VLT® was switched Off/On 1. Reduce the power ups accordtoo often in a short time ing to the power of the drive 2. The external 24 V (D-Option) is defect



supply 2. Check the external 24 V power supply (D-Option)



3. The connected brake resistor is 3. Check the resistor defect



connected



brake



Reset Note The max. power ups in 1minute (with ext. 24V during Mains-off) for the AutomationDrive FC 300 via [Reset], Terminal or Bus depends on the power of the drive: ≤ 7,5 kW max. 2x per Minute 11-75 kW max. 1x per Minute ≥ 90 kW max. 1x in 2 Minutes



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 14 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message 34 Fieldbus fault 36Status Mains failure 150RPM 1.52A ¶¡µ£Hz ¢¡¡% ²Fieldbus fault [W34] Auto Remote Running Status 0RPM



0.00A



Possible cause(s)



²@ A communication fault occured in an application using Fieldbus 2.121 communication.



• the master configuration



³Fieldbus fault [A34] Auto Remote Trip



1.52A ¶¡µ£Hz ¢¡¡%



²Mains failure [W36] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Mains failure [A36] Auto Remote trip



Check:



Note You will find more detailed fault • if the bus lines are installed properly and EMC correctly descriptions in the hand book of the respective Fieldbus option. • the bus address, baud rate and ³@ eventually the protocol type (depends on the Fieldbus type) 2.121



¡µ¡Hz ¢¡¡%



Status 150RPM



Possible solution(s)



Reset via [Reset], Terminal or Bus



The mains failure function Check the power supply and the ²@ (Par. 14-10 ≠ Deactivated) was fuses ahead of the VLT®. 2.121 activated. The supply voltage has reached the threshold value defined in Check the setting of Par. 14-10 Par. 14-11. and Par. 14-11 The selected Mains failure function (Par. 14-10) will be/is per³@ formed. Reset 2.121 via [Reset], Terminal or Bus ² In Par. 14-10, one of the following functions was selected: -



Controlled ramp-down Coasting Kinetic back-up



³ In Par. 14-10, one of the following functions was selected: -



Controlled ramp-down, trip Kinetic back-up, trip Alarm



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 15 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message 37 Phase imbalance Status 0RPM 0.00A 38 Internal fault ¶¡µ£Hz ¢¡¡%



Possible cause(s)



Possible solution(s)



²@ An unsymmetrical current was detected on the output of the 2.121 VLT®, that suggests a damage of the IGBT’s. 1. The power section is defective



²Phase imbalance [W37] 40 Overload on digital output terminal 27 Auto Remote Running



1. Please contact Danfoss supplier!



your



local



2. The calibration of the internal 2. Initialise the internal current sensors of the VLT® with a current sensors of the VLT® is Status ³@ Manual Reset. To do this, not symmetrical anymore. 150RPM 1.52A 2.121 please hold the following keys pressed, when reconnecting ¶¡µ£Hz the mains, until the internal ¢¡¡% fan starts: Note on Manual Reset Save your parameterisation of ³Phase imbalance [A37] the VLT® before initializing the LCP 101:[Main Menu] Auto Remote trip drive to factory settings (e.g. via LCP 102: Status]+[OK]+[Main Menu] Par. 0-50 LCP-Copy)! Attention: A deactivated EMC Reset Filter (Par. 14-50) is activated via [Reset], Terminal or Bus again after a Manual Reset!



An internal fault occured in the Typical fault codes: ²@ VLT® (e.g. failures in the internal 1299 SW Option A is too old 0.00A 2.121 bus). 1300 SW Option B is too old 1301 SW Option C0 is too old ¶¡µ£Hz 1302 SW Option C1 is too old ¢¡¡% 41 Overload on digital output terminal 29 1315 SW Option A is not supported ³Internal fault:1315 [A38] 1316 SW Option B is not supported 1317 SW Option C0 is not supported Auto Remote Trip lock 1318 SW Option C1 is not supported Status 0RPM



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Overload T27 [W40] Auto Remote Running



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Overload T29 [W41] Auto Remote Running



²@ The terminal 27 in configured as an output (Par. 5-01) with a posi2.121 tive switching logic (Par. 5-00). The terminal is overloaded or short circuited to ground because of the following: - faulty wiring - defective ext. component



Check the condition of the component connected between terminal 27 and 20/39 the part itself for short circuit.



²@ The terminal 29 in configured as an output (Par. 5-02) with a posi2.121 tive switching logic (Par. 5-00). The terminal is overloaded or Check the condition of the comshort circuited to ground because ponent connected between termiof the following: nal 29 and 20/39 the part itself for short circuit. - faulty wiring - defective ext. component



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 16 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Ovrld X30/6-7 [W42] Auto Remote Running



Possible cause(s)



Possible solution(s)



²@ The terminal X30/6 (DOUT 3) or X30/7 (DOUT 4) of the MCB 101 2.121 Option is overloaded or short circuited: Check the condition of the component connected between termi- faulty wiring nal X30/6 or X30/7 and X30/5 (or - defective ext. component 20/39) and the part itself for short circuit.



Only with I/O Option MCB 101



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



One of the internal power sup- Please contact your local Danfoss ²@ plies (+/-18V, 24V, and 5V) supplier! 2.121 of the power card was longer then 5 seconds outside the specified tolerance.



²Powr. card supply [W46] Auto Remote Triplock 42



Overload on digital output terminal 30/6-7



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



lowsupply [W47] 46²24V supply Power card Auto Remote Running Status 0RPM



0.00A



²@ The internal 24V power supply is Switch the mains Off and On again. overloaded. 2.121 1. Too many external devices are 1. The load of the 24V power supply (Terminal 12 & 13) is powered by the 24V supply. not allowed to exceed the max. load current: FC 301: 130mA FC 302: 200mA ³@ 2.121 2. The internal 24V power supply 2. Please contact your local Danis defective. foss supplier!



¡µ¡Hz ¢¡¡%



Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



³24V supply low [A47] Auto Remote triplock.



Status 0RPM 47



0.00A 24V supply low ¡µ¡Hz ¢¡¡%



²@ A fault occured in the internal Please contact your local Danfoss 1,8 V Switch Mode Power Supply supplier! 2.121 (SMPS).



²1,8V supply low [A48] Auto Remote triplock.



48 1,8V supply low



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 17 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



Possible cause(s)



²@ The motor with the given reference would be driven outside the 2.121 chosen limits: [RPM] : Par. 4-11 / 4-13 [Hz] : Par. 4-12 / 4-14



²Speed limit [W49] Auto Remote Running The actual reference shown on the Display.



can



be



The FC 300 limits the output frequency to the set min. resp. max. limit. 1. The limits are not well pro- 1. Check Par. 4-11 / 4-13 [RPM] grammed resp. Par. 4-12 / 4-14 [Hz] 2. The references are set wrongly resp. wrongly scaled.



49



Status 0RPM



Speed limit



0.00A ¡µ¡Hz ¢¡¡%



50³AMA calibration AMA-Calibration [A50] Auto Remote Trip



51 AMA-Unom, Inom Status 0RPM 0.00A ¡µ¡Hz ¢¡¡% ³AMA Unom, Inom [A51] Auto Remote Trip



Possible solution(s)



3. There are no reference signals



2. Check the setting and scaling of the internal preset references and the ext. reference sources 3. Check the ext. reference source



³@ When performing the Automatic Check the programmed Motor Adaptation AMA a fault data (Group 1-2*). 2.121 occured.



motor



During the AMA an internal cali- Please contact your local Danfoss bration of the current transducers supplier! and their deviation is tested. The measured values have ex- Reset ceeded the permitted tolerances. (with ext. 24V during Mains-off) via [Reset], Terminal or Bus One or more current transducers are faulty.



³@ When performing the Automatic 1. Check the programmed motor Motor Adaptation AMA a fault data (Group 1-2*) 2.121 occured. 2. Determine the motor data via The combination of the proexternal measurements or use grammed motor data is probably the data from the motor wrong. manufacturer.



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 18 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³AMA low Inom [A52] Auto Remote Trip



52Status AMA-low Inom 0RPM 0.00A ¡µ¡Hz ¢¡¡% ³AMA big motor [A53] Auto Remote Trip



Status 0RPM 53



0.00A AMA-Big motor ¡µ¡Hz ¢¡¡%



³AMA small mot [A54] Auto Remote trip



Possible cause(s)



Possible solution(s)



³@ When performing the Automatic 1. Check the motor current set in Par. 1-24 Motor Adaptation AMA a fault 2.121 occured. 2. Ensure the correct wiring of the motor (Star or Delta). There is a conflict between the current demand of the motor and Reset the chosen motor data via [Reset], Terminal or Bus



³@ When performing the Automatic 1. Check the motor power set in Motor Adaptation AMA a fault Par. 1-20 2.121 occured. There is a conflict between the 2. Check if the VLT® is suitable calculated power size and the for the motor. programmed motor data The motor is probably too big for the VLT®.



3. Try and change the wiring of the motor from Star to Delta (Program the motor data again!).



³@ When performing the Automatic 1. Check the motor power set in Motor Adaptation AMA a fault Par. 1-20 2.121 occured. 2. Check if the VLT® is suitable There is a conflict between the for the motor. calculated power size and the chosen motor data 3. Try and change the wiring of the motor from Star to Delta (Program the motor data again!).



If the motor is several power sizes smaller then the drive, the AMA can NOT be performed.



Reset via [Reset], Terminal or Bus 54 Status 0RPM



AMA-Small motor



0.00A ¡µ¡Hz ¢¡¡%



³AMA par. range [A55] Auto Remote Trip



55



³@ When performing the Automatic 1. Check the motor data in Motor Adaptation AMA a fault (Group 1-2*) 2.121 occured. 2. Determine the motor data via There is a conflict between the external measurements or use measured and the programmed the data from the motor motor data manufacturer. Reset via [Reset], Terminal or Bus



AMA-Parameter range



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 19 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



Possible cause(s)



³@ The AMA was interrupted by the To run a complete AMA, it must user. be programmed again in Par. 2.121 1-29 and started with the [Hand on] Key. Reset via [Reset], Terminal or Bus



³AMA interrupt[A56] Auto Remote Trip



Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³AMA timeout [A57] Auto Remote Trip



Possible solution(s)



³@ The AMA function was activated 2.121 via Par. 1-29, but cannot determine any stable and reliable values.



To run a complete AMA, it must be programmed again in Par. 1-29 and started with the [Hand on] Key.



1. The AMA function was not star- 1. Start via the [Hand On] key is possible only when no stop sited with the [Hand On] key. gnals (e.g. Coasting inverse) The internal timeout was reaare active ched. 2. The motor cables are too long 2. Check the length of the motor cables and their screening. or the screening of the cables Eventually Ggfs. An AMA is not is done badly possible 3. The motor was too warm when 3. Wait until the cooled down the AMA started



56



57 Status 0RPM



AMA-Interrupt



4. The slip of the motor is too big



4. An AMA is not possible



5. The determined resistance of the motor is too high in relation to other motors, that leads to strong heating of the motor during the AMA.



5. An AMA is not possible Reset via [Reset], Terminal or Bus



AMA-Timeout



0.00A ¡µ¡Hz ¢¡¡%



motor



has



Note: If running an AMA is not possible, you can determine the values (Rs, Xs, etc.) through external measurements or you can use the data from your motor supplier



When performing the Automatic Check the motor data in ³@ Motor Adaptation AMA an internal (Group 1-2*). 2.121 fault occured. Please contact your local Danfoss supplier! Reset via [Reset], Terminal or Bus



³AMA internal[A58] Auto Remote Trip 58 AMA-Internal fault



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 20 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Currentlimit [W59] Auto Remote Running 59



Current limit



Possible cause(s)



Possible solution(s)



²@ The motor current has reached the value set in Par. 4-18. The 2.121 VLT® limits the output current to this value. ³ The current is reached and the time set in Par. 14-24 was exceeded 1. The drive control reaches (e.g. 1. Check the load conditions because of load pulses) the set current limit. 2. Ramp up times too short



2. Adjust the ramp times (Group 3-**)



3. False motor data



3. Check the motor data (Group 1-2*)



4



Overcompensation of the mo- 4. Check the compensation parameters (Group 1-5* & 1-6*) tor



5. The value set in Par. 4-18 is 5. Assure the right setting of Par. 4-18 too low Reset via [Reset], Terminal or Bus Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Tracking error [W61] Auto Remote Running Status 0RPM



0.00A



¡µ¡Hz ¢¡¡% 61 Tracking error ³ Tracking error [A61] Auto Remote Trip



²@ In Par.1-00/1-01 a control mode with feedback was chosen. The 2.121 feedback monitoring (Par.4-30) is activated. The calculated motor- and the measured encoder revolutions differ from each other for a longer time then the timeout (Par.4-32) and the value in Par.4-31 .



Notes When Par. 4-30 = Warning the motor is running even in case of a failure Connection of the 24V encoder: T32: Track A (Par.5-14: no.fct) T33: Track B (Par.5-15: no.fct)



Check the settings in Par. 1-00 ³@ and 1-01. 2.121 ² Par. 4-30= Warning ³ Par. 4-30= Alarm stops the motor (Coasting) and triggers 1. Check the feedback connection the alarm over failure and EMC influences 1. The active feedback signal is interrupted or disturbed 2. Check the mechanical and dynamical conditions of the drive system 2. The inertia of the load is too big (the mechanical system is 3. Test the functionality of the too idle) encoder 3. The encoder is defective Reset via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 21 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



The actual reference, feedback and the corresponding signal levels can be shown on the display.



Status 0RPM



¡µ ¡Hz ¢¡¡% ²Mech. brake low [A63] Auto Remote Trip



Mechanical brake low



is



superior



to



1. Par. 4-19 is set too small



1. Check Par. 4-19



2. The reference is too high



2. Check the reference sources and their scaling



A Relay (Par.5-40) was pro²@ grammed to Mechanical brake 2.121 control. A Start function is set in Par.1-72, that does not reach the motor current set in Par. 2-20. The mech. brake does not open.



The motor current can be shown on the display.



63



62 49.



3. In Par. 1-00, PID-Process is 3. Check the sensor and the settings of the controller activated: a) check the scaling of the a) the feedback signal is not feedback range and the inprocessed correctly put b) check the sensor b) the sensor is defective c) optimize the controller setc) process regulation of the tings. Consider the regulaoutput frequency is not tion principle (Par. 7-30)! stable



Output frequency limit



0.00A



Possible solution(s)



²@ The motor frequency has reached the value set in Par. 4-19. The 2.121 VLT® limits the output frequency Note strictly to this value (without slip Warning Warning compensation).



²Output freq. lim. [W62] Auto Remote Running



62



Possible cause(s)



Attention: False settings can lead to the opening of the brake or to a drop of the load ! The VLT® has to be programmed in a way, that the mechanical brake opens only after the motor is sufficiently magnetized.



1. The start function is 1. Select a Start function (Par.1not magnetizing the motor 72) that energizes the motor sufficiently. sufficiently 2. The start delay (Par.1-71) is 2. Assure the proper settings of too short and/or the starting Par. 1-71, 1-74 [RPM] resp. 1current (Par.1-76) is too small 75[Hz] and Par. 1-76. 3. The power line between the 3. Check the power connection motor and the FC 300 is interbetween the FC30 and motor rupted 4. False motor data



4. Check motor data (Group 1-2*)



5. The Release brake current 5. Adjust the brake settings in (Par. 2-20) is too high Par. 2-20 Note The monitoring is active only Reset when in Par. 1-71 the time is set via [Reset], Terminal or Bus to > 0s.



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 22 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



If the connected PM motor is Run the motor with a lower driven with a frequency, where frequency the drive is not able to supply the motor with enough voltage, W64 apears. Notes: • The VLT® is able to supply the motor, depending on the mains condition, up to +10% mains voltage. Note: In the moment the warning is • If the drive is fitted apropriately displayed, the drive is not able to to the motor, the warning control the motor with the proper apears, when the motor goes in U/f characteristic. to the field weakening area.



Voltage limit



Status 150RPM



1.52A



The temperature on the Control Switch mains off and on again. ²@ card of the VLT® has reached the 2.121 max. allowed limit.



¶¡µ£Hz ¢¡¡%



³ The switch off limit of 80°C of the control card was reached.



²Ctrl. card temp [W65] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



Possible solution(s)



²@ Flux mode (w/wo feedback) was chosen as Control Principle (in 2.121 Par. 1-10) and PM, non salient SPM as motor type (Par. 1-10)



²Voltage limit [W64] Auto Remote Running 64



Possible cause(s)



³@ 2.121



1. The ambient temperature is 1. Reduce the ambient temperature (check the cabinet structoo high ture and ventilation) 2. The ventilation holes or the 2. Clean the ventilation holes and change the filter pads filter pad of the VLT® are dirty



³Ctrl. card temp [A65] Auto Remote Triplock



65



Control card temperature



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²Low temp. [W66] Auto Remote Running 66



Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus The temperature in the frequency Check the ambient conditions. ²@ converter is below 0°C. 2.121 Note Because a fault of the temperature sensors can not be excluded, the internal fans are running with full speed.



Please contact your local Danfoss supplier!



Low temperature



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 23 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Option change [A67] Auto Remote Trip 67Status Option change 0RPM 0.00A ¶¡µ£Hz ¢¡¡% ²Safe Stop [W68] Auto Remote Coasting



Possible cause(s)



³@ One or more options were mounted/demounted during the last 2.121 mains off/on of the VLT® . Note You can check detailed information about the installed Options in Par. Group 15-6*. ²@ Only on FC 301 in A1 enclosure and on FC 302: 2.121 The function on Terminal 37 Par. 5-19) is Safe Stop and and the terminal 37 is not wired up (Signal = 0V).



Possible solution(s) Note: After mounting an option, a reset to factory settings should be done. Save your parameterisation before (e.g. via Par. 0-50 LCP-Copy)! 1. Par. 14-22 = Initialise 2. Switch mains off and on again



Check the wiring of terminal 37.



Reset via [Reset], Terminal or Bus ² Par. 5-19= Safe Stop Warning ³ Par. 5-19= Safe Stop Alarm Status ³@ 0RPM 0.00A 2.121 Note 68 Safe Stop If Par.5-19 is programmed on ¡µ¡Hz Safe Stop Warning, then the war¢¡¡% ning activates the function Coast (the motor runs out uncon³Safe Stop [A68] 69Auto Remote FC Overtemp trolled). Is the terminal wired Trip again, the coasting is deactiThe setting of the terminal 37 vated. The motor could then start CANNOT be changed. again! Status 0RPM



0.00A ¶¡µ£Hz ¢¡¡%



³Pwr. Card Temp [A69] Auto Remote Triplock



on the power- Switch the mains Off and On ³@ The temperature card of the VLT® has reached the again 2.121 allowed max. limit. 1. Try to reduce the ambient 1. The ambient temperature is temperature (check the design too high and ventilation of the cabinet) 2. Internal fans failure



2. Ensure the correct function of the cooling vents



3. Ventilation vents or the filter pads are dirty 3. Clean the ventilation vents and the change the filter pads 4. The motor cable is too long 4. Check the length of the Motor cable. Consider the use of an 5. Switching frequency set in LC filter. Par 14-01 is too high 5. Reduce the switching frequency (Par. 14-10) Beware: and pattern (Par. 14-00); The alarm can be reset only eventually use a bigger VLT® when the temperature of the Reset power card has dropped. (with ext. 24V during Mains-off) . via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 24 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A



Possible cause(s)



Possible solution(s)



³@ The used power card and the installed control card are not com2.121 patible. Please contact your local Danfoss supplier!



¡µ¡Hz 70 Illegal FC configuration ¢¡¡% ³Illegal FC config. [A70] Auto Remote Triplock



Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



²PTC1 Safe Stop [W71] Auto Remote Coasting 71 PTC1 Safe Stop Status 0RPM 0.00A ¡µ¡Hz ¢¡¡%



²@ Terminal 37 (Par. 5-19) is set to PTC monitoring of the option 2.121 (MCB 112) and a digital input is programmed to PTC Card 1. The PTC option triggered properly.



Note If Par. 5-19 is set to Warning, the coasting function is activated together with the warning (the motor is coasting). If the temperature of the ther² Par. 5-19 = setting with PTC 1 mistor reaches an acceptable value, the coasting function is and Warning ³ Par. 5-19 = setting with PTC 1 deactivated and the motor can eventually start again!!! and Alarm ³@ 2.121 1. Check the motor, load and 1. The motor is overheated temperature conditions



³PTC1 Safe Stop [A71] Auto Remote Trip



2. The thermistor is faulty or the connection is interrupted



2. Please check the thermistor (min. 20 Ω) and the wiring Reset (with ext. 24V during Mains-off) via [Reset], Terminal or Bus



Only with an PTC MCB 112 option



³@ Terminal 37 (Par. 5-19) set to Switch mains off and on again PTC monitoring of the option 0.00A 2.121 (MCB 112) and a digital input is programmed to PTC Card 1. • Check the switching of the in¡µ¡Hz 72 Dangerous¢¡¡% Failure puts or eventually the wiring A difference between the PTC option signal and the programming • If an additional safety relay is ³Dangerous Failure [A72] occured. connected between terminal 12 Auto Remote Triplock of the MCB 112 option and terminal 37 of the drive, change Only with an PTC MCB 112 option Note the setting of terminal 37 If the digital input is set to PTC 1, ® (Par. 5-19) to PTC 1 & Relay AutomationDrive the VLT expects, that the digital input is activated simultaneously with the safe stop. Status 0RPM



Until this switching of the inputs Reset does not happen simultaneously, (with ext. 24V during Mains-off) the drive evaluates this as a fault via [Reset], Terminal or Bu in the system.



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 25 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message Status 0RPM



0.00A



Possible cause(s)



Possible solution(s)



³@ The internal hardware configura- Please contact your local tion between the power cars and Danfoss supplier! 2.121 the options is not valid anymore.



¡µ¡Hz ¢¡¡%



During operation, the internal configuration is being checked. An inconsistency was detected during this procedure.



³Illegal PS config [A79] Auto Remote Triplock



79 Illegal PS-config Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



The frequency converter was ³@ initialised via Par. 14-22 or 2.121 manually directly on the Local Operation Panel Reset LCP 101: „1-Finger reset“ via [Reset], Terminal or Bus LCP 102: „3-Finger reset“



³Drive initialised [A80] Auto Remote Trip 80



The drive was set to factory setup.



Drive initialized



Status 150RPM



1.52A ¶¡µ£Hz ¢¡¡%



²@ The feedback monitoring of the MCB 102 (Par.17-61) is activated. 2.121 The signals of the encoder are defect. ² Par. 17-61= Warning ³ Par. 17-61= Alarm stops the motor (Coasting) and triggers the Alarm.



²Feedback Mon.[W90] Auto Remote Running Status 0RPM



0.00A ¡µ¡Hz ¢¡¡%



³Feedback Mon. [A90] Auto Remote Trip



³@ 2.121



The monitoring of the tracking error is stil active (Warning/Alarm 61). Check settings in Par. 17-60 and 17-61.



1. The active encoder signal is interrupted or disturbed



1. Check the encoder connection on braking and EMC influences



2. The encoder is defect or a wrong one is connected



2. Test the function and type of the encoder in Par. 17-10 / 1720



3. The inertia of the load is too high (the mechanical system is too idle)



3. Check the mechanical and dynamical conditions of the drive system



Only with MCB 102



90



Notes When Par. 17-61 = Warning the motor continues to run even when a failure occurs.



Feedback monitoring



Reset via [Reset], Terminal or Bus



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 26 / 27



VLT® AutomationDrive FC 300



– Alarm & Warning - Messages – Software 5.5x



Display Message



Possible cause(s)



Possible solution(s)



Terminal 54 was selected as KTY Note ²@ Sensor Resource (Par. 1-96). A change of the signal type (volt0.00A 2.121 age/current) using the A-54 DIP The monitoring of the Motor Ther- switch is recognised only after ¡µ ¡Hz mal Protection in Par. 1-90 a Mains Off/On. ¢¡¡% (Thermistor Warning or Thermistor Trip.) was activated. ²AI54 set wrong [A91] Switch the drive off (Display Auto Remote Trip Terminal 54 was configured as a dark). Signal type (current or voltage) and signal level of the terminal 54 current input using the A-54 DIP switch. Switch the A-54 switch to „U“. can be shown on the display. Status 0RPM



Switch On the mains again. 91



Analog input set wrong



Reset via [Reset], Terminal or Bus



The connected operating panel stays dark.



Display dark



-



Display dark



1. VLT® power supply is defective.



1. Check the mains supply of the VLT®



2. LCP power supply is defective.



2. Check the connection cable between the VLT® and LCP



3. Short circuit of the control vol- 3. Check the control voltage supplies tage (T. 12 or T. 50) or of the control terminals 24V: T. 12/13 to 20/39 10V: T. 50 to 55 4. Use a 4. Wrong LCP LCP 101 (Order no. 130B1124) (LCP from a VLT® 2800 / 5000 or / 6000 / 8000 / FCD or FCM) LCP 102 (Order no. 130B1107) 5. Local control panel (LCP) de- 5. Exchange the operating panel fective 6. Power supply unit defective; 6. Please contact your local internal supply fault Danfoss supplier!



Safety note:



To avoid electrical shock hazard- even after the power is disconnected- wait at least as follows before doing service on the frequency converter: (380-500V: 0.25-7.5 kW: 4 Min. / 11-75 kW: 15 Min./ 90-200 kW: 20 Min./ 250-400 kW: 40 Min.) ..\FC300\Alarm-Warn\English\Alarms & Warnings FC 300 SW 5.5x



18.08.2008 MC



Page 27 / 27