DEEP SEA ELECTRONICS PLC DSE9470 Configuration Suite PC Software Manual Document Number 057-159 Author: Fady Atallah



DSE9470 Configuration Suite PC Software Manual ISSUE



DSE9470 Configuration Suite PC Software Manual



DEEP SEA ELECTRONICS PLC Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail : [email protected] Website : www.deepseaplc.com



DSE9470 Configuration Suite PC Software Manual © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice. Amendments List Issue



Comments



1



Initial release



Minimum Module version required 1



Minimum Configuration Suite Version required



Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.



NOTE:



Highlights an essential element of a procedure to ensure correctness.



CAUTION!:



Indicates a procedure or practice which, if not strictly observed, could result in damage or destruction of equipment.



WARNING!:



Indicates a procedure or practice which could result in injury to personnel or loss of life if not followed correctly.







Deep Sea Electronics Plc owns the copyright to this manual, which cannot be copied, reproduced or disclosed to a third party without prior written permission.



SAE



Society of Automotive Engineers (USA)



2



DSE9470 Configuration Suite PC Software Manual



TABLE OF CONTENTS 1 BIBLIOGRAPHY .......................................................................................... 3 2 DESCRIPTION ............................................................................................. 3 3 INSTALLATION AND USING THE DSE CONFIGURATION SUITE SOFTWARE ....................................................................................................... 4 4 EDIT CONFIG............................................................................................... 4 4.1 SCREEN LAYOUT.............................................................................................................................. 4 4.2 CHARGER .......................................................................................................................................... 5 4.2.1 CHARGER SETTINGS................................................................................................................ 5 4.2.2 TIMERS ....................................................................................................................................... 5 4.3 BATTERY............................................................................................................................................ 6 4.3.1 BATTERY TEMPERATURE SENSOR........................................................................................ 6 4.3.2 OVER CURRENT ALARM .......................................................................................................... 7 4.3.3 OVER VOLTAGE ALARM ........................................................................................................... 7 4.4 MAINS ................................................................................................................................................. 8 4.4.1 MAINS VOLTAGE ALARMS ....................................................................................................... 8 4.5 COMMUNICATIONS ........................................................................................................................... 9 4.5.1 RS485 PORT............................................................................................................................... 9



1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com: DSE PART 053-049 057-085



DESCRIPTION DSE9000 Series Battery Charger Installation Instructions DSE9000 Series Battery Charger Operator Manual



2 DESCRIPTION This manual covers the operation of the DSE Configuration Suite for DSE9470 battery charger. Separate manuals cover the remaining DSE modules supported by the software. The DSE Configuration Suite allows the DSE9470 to be connected to a PC via USB ‘A –USB B’ cable. Once connected the various operating parameters within the charger can be viewed or edited as required by the engineer. This software allows easy controlled access to these values and also has diagnostic monitoring facilities. The DSE Configuration Suite should only be used by competent, qualified personnel, as changes to the operation of the module may have safety implications on the panel to which it is fitted. The information contained in this manual should be read in conjunction with the information contained in the appropriate module documentation. This manual only details which settings are available and how they may be used. A separate manual deals with the operation of the charger (See section entitled Bibliography elsewhere in this document).



3



Edit Configuration



3 INSTALLATION AND USING THE DSE CONFIGURATION SUITE SOFTWARE For information in regards to installing and using the DSE Configuration Suite Software please refer to DSE publication: 057-151 DSE Configuration Suite PC Software Installation & Operation Manual which can be found on our website: www.deepseaplc.com



4 EDIT CONFIG This menu allows module configuration, to change the function of Inputs, Outputs and LED’s, system timers and level settings to suit a particular application.



4.1



SCREEN LAYOUT Move to the Previous or Next configuration page



The type of configuration file being edited



The coloured shading shows the currently selected page.



Close this configuration file Click + or – to show or hide the sub settings within each sections.



Click to select the subsection to view / edit



4



Edit Configuration - Charger



4.2 4.2.1



CHARGER CHARGER SETTINGS Free entry boxes to allow the user to give the configuration file a description. Typically this is used to enter the job number, customer name, engineers name etc.



4.2.2



TIMERS Click and drag to change the setting. Timers increment in steps of 1 second up to one minute, then in steps of 30 seconds up to 30 minutes, then in steps of 30 minutes thereafter (where allowed by the limits of the timer).



Timer Bulk Charge Run-On



Description This is the duration after the bulk charge is over (determined by the battery charger) for which the charger will continue in bulk charge mode before automatically switching to float mode.



5



Edit Configuration - Battery



4.3 4.3.1



BATTERY BATTERY TEMPERATURE SENSOR Enable or disable the external Battery Temperature Sensor (PT1000). The relevant values below will appear greyed out if the option is disabled.



Type the value or click the up and down arrows to change the settings



Click and drag to change the settings



Over Temperature Alarms If the battery temperature exceeds the Trip value setting Trip AND Remains higher for the “Trip Delay” time duration : Trip Delay The onboard status LED 2 will light continuously and the NC relay output will change to open position. If the battery temperature falls below the return value setting Return AND Remains lower for the “Return Delay” time duration : Return Delay The onboard status LED 2 will turn back off and the NC relay output will return to close position. Temperature The amount by which the voltage is decreased for each degree Celsius of temperature rise. This is normally specified by the battery manufacturer. Compensation Voltage Reduction /°C



6



Edit Configuration - Battery



4.3.2



OVER CURRENT ALARM Enable or disable the alarms. The relevant values below will appear greyed out if the option is disabled.



Click and drag to change the settings Over Current Alarm Trip



Type the value or click the up and down arrows to change the settings



If the current drawn by the battery exceeds the trip value setting, AND Remains higher for the “Trip Delay” time duration :



Trip Delay



Return Return Delay



The onboard status LED 1 will start flashing and the NC relay output will change to open position. If the current drawn by the battery falls below the return value setting AND Remains lower for the “Return Delay” time duration : The onboard status LED 1 will switch off and the NC relay output will return to close position.



4.3.3



OVER VOLTAGE ALARM Enable or disable the alarms. The relevant values below will appear greyed out if the option is disabled. Type the value or click the up and down arrows to change the settings Click and drag to change the settings



Over Voltage Alarm Trip



If the battery voltage exceeds the trip value setting AND Remains higher for the “Trip Delay” time duration :



Trip Delay



Return Return Delay



The onboard status LED 1 will light continuously and the NC relay output will change to open position. If the battery voltage falls below the return value setting AND Remains lower for the “Return Delay” time duration : The onboard status LED 1 will switch off and the NC relay output will return to close position.



7



Edit Configuration - Mains



4.4 4.4.1



MAINS MAINS VOLTAGE ALARMS Enable or disable the alarms. The relevant values below will appear greyed out if the option is disabled.



Type the value or click the up and down arrows to change the settings



Click and drag to change the settings



Mains Over Voltage Alarms If the Mains voltage exceeds the trip value setting Trip AND Remains higher for the “Trip Delay” time duration : Trip Delay Return Return Delay



The onboard status LED 1 will start flashing If the Mains voltage falls below the return value setting AND Remains inactive for the “Return Delay” time duration : The onboard status LED 1 will switch off



Mains Under Voltage Alarms If the Mains voltage falls below the trip value setting Trip AND Remains active for the “Trip Delay” time duration : Trip Delay Return Return Delay



The onboard status LED 1 will start flashing If the Mains voltage exceeds the return value setting AND Remains inactive for the “Return Delay” time duration : The onboard status LED 1 will switch off



8



Edit Configuration - Communications



4.5



COMMUNICATIONS



Click to edit the RS485 settings



4.5.1



RS485 PORT



RS485 Port Basic Slave ID Baud Rate Advanced Master Inactivity Timeout



The Modbus Slave address and RS485 baud rate. This is used when connecting the RS485 port to a Modbus Master device. Modbus timer to enable the charger to detect when the Modbus Master is no longer communicating.



9