Microcomputer Temperature Controller MTC-5060C User Manual
Parameter indicator
“Current”display window Se ng range
Default se ng
“On Temp” LED lights.
On Temp
Off Temp~+50.0℃
10.0℃
Compressor starts on reaching the set-point.
“Off Temp” LED lights.
Off Temp
-50.0℃~ On Temp
-10.0℃
Compressor stops on reaching the set-point.
“Comp. Delay” LED lights. Compressor delay me
1~120 min
3 min
“Def. Cycle”
Defrost cycle
0~120 hours
6 hours
“Def. Time” LED lights.
Defrost me
0~120 min
30 min
“Def. Stop Temp”LED
Defrost stop
lights.
temperature
-50.0℃~+50.0℃
10.0℃
The minimum me between switch-off of the compressor and the successive switch-on.
Overview used as control terminal device to match with Elitech relay module and connect to network. It features temperature measurement,
Specifications
LED lights.
Notes
The interval me between The start of two Successive defros ng opera ons. Dura on of defros ng Defrost is disabled when Defrost sensor temperaturegoes above this set-point.
Front panel size: 100 (length) * 51 (width) (mm)
System menu
Product size: 100 (length) * 51 (width) * 82.5 (depth) (mm) Length of current transformer wire: 670mm (not including coil length) Length of temperature sensor: 2m (including probe length)
“Temp” display window
Technical requirements Temperature measuring range: -50℃~50℃ Temperature measuring accuracy: ±1℃ ℃ Current measuring accuracy: ±1A (0-20A), ±5 % (20A-40A) Sensor: NTC (10KΩ/25℃, B value 3435K), current transformer Ambient temperature: -15 °C~60 °C Ambient humidity: 20%~85% (non-condensing)
-10.0℃~+10.0℃
0℃
F02
Over temperature limit alarm
0~50.0℃
5.0℃
Refrigera on LED
Defrost LED
Meaning
Off
Compressor stops.
Flash
Compressor delays.
On
Compressor runs.
Off
Defrost stops.
Flash
Dripping.
On
Defrost is on.
Defrost types
F04
Defrost cycle calcula on
F05 F06
Dripping me a er defrost Backup mode Over temperature limit alarm delay Over-temperature alarm delay
0: Electric defrost 1: Hot gas defrost
0: Cumula ve working me of the controller a er power on 1 1: Cumula ve working me of the compressor a er power on 0~120 min 3 min -1~5 1 30 min 2 hours
F09
a er power on for the first me Enable phase sequence protec on
0~120 hours 0: Disable 1: Enable
1
F10 F11
Three-phase voltage selec on Enable current protec on
0:220V 1:380V 0: Disable 1: Enable
1 1
F12
Set the Max value of Protec on current
Protec on current value (F13) at present~40A
Notes Calibrate the temperature by increasing/decreasing“temperature calibra on” set-point when error occurs to displayed cold storage temperature. It alarms if cold storage temperature﹥“On Temp set-point” +“Over temperature limit alarm set-point” or ﹤ “Off Temp set-point – Over-temperature limit alarm set-point”.
0
0~120 min
F08
Status
Default se ng
Temperature calibra on
F07
Table of indicator status
Se ng range
F01
F03
Panel
Indicator
“Current”display window
Delay me a er defros ng ends.
A er power on, there is no overtemperature alarm within this me set-point.
40A
Set the maximum value of protec on Current in user and administrator interface.
20A
When current exceeds protec on current set-point and lasts for certain me, the protector will enable protec on func on.
F13
Set protec on current
0~the Max value of protec on current
F14 F15
Enable me reverse lag Set protec on me
0: Disable 1: Enable 0~60s
1 5s
F16
0~5 mes
2
Reset in half an hour
F17
Times of overload auto reset Set percentage of three-phase imbalance
5~80%
25%
The percentage of three-phase imbalance
F18
RS485 communica on address
1~247
1
Benchmark me of overcurrent protec on
View user menu
User menu
value. (“Temp” display window shows single-phase current symbol. “Current” display window displays the corresponding current.) press
3. Overcurrent protection
cold storage temperature or single-phase current symbol.
Set user menu ▲/
modify the set-point value displayed in “Current” display window.
or ▼ to
4. Inverse time lag protection
Set system menu
n-1
▼ “Current” display window. All the parameter indicators are off.
5. Current imbalance protection ▲/
or ▼ to modify the set-point value displayed in
parameter view status.
Max three-phase current – Min three-phase current
“Left Def. Time” button:
Three-phase mean current
×100%
6. Phase-loss protection
“Forced Def.” button: LED lights. In running status, press and hold “Forced Def.” for more than 5 seconds to exit from defrost status, and defrost LED is off.
7. Auto reset
“Forced Ref.”:
Alarm information “▲/
” button: ▲/
“▼ ” button
” to cancel the buzzer alarm beep.
▼
Function control rules 1. Compressor control
a) Cold storage temperature ≤ Off Temp set-point. b) When electric defrost starts. c) When hot gas defrost stops.
Alarm info
Notes Coldstoragesensor is notinstalled well,causing shortcircuit oropencircuit.Refrigera onruns inpropor on(stops 30minutes andstarts 15 E1 minutes)and buzzerbeeps. Defrostsensor is notinstalled well,causing shortcircuit oropencircuit.Defrostruns based onthesetdefrostcycleanddefrost me,andbuzzer E2 beeps. Cold storagetemperatureexceedsthe upperlimitof measuring range.Refrigera onruns inpropor on(stops 30minutes and starts 15minutes) E3 and buzzerbeeps. E4 Defrosttemperatureexceedstheupperlimitof measuring range.Defrost runsbasedonthe setdefrost cycleand defrost me,andbuzzerbeeps. E6 Phasesequenceprotec on,refrigera onanddefrost stop.Poweronthe controller againand resetprotec on. E7 Thecurrentexceedsthe protec oncurrentset-point.Refrigera on and defroststop.Autoreset inspecified mes. E8 Currentunbalanceprotec on,refrigera onand defroststop.Poweronthe controlleragainand resetprotec on. E9 Currentphase-loss protec on,refrigera onanddefroststop.Poweronthe controlleragainand resetprotec on. Coldstorage Overlimitalarm,coldstoragetemperature ≥“OnTempset-point”+“Over-temperaturealarmdifferen alset-point” anddura on≥“Temperature temperature alarmdelay” orcold storagetemperature≤ “OffTempset-point” - “Over-temperaturealarm differen alset-point”dura on≥ “Temperature alarm delay”. flashes.
Wiring diagram 2. Defrost control b) Defrost sensor temperature < the set-point of defrost stop temperature. c) The “Def. Cycle” set-point elapses or forced defrost starts. output load
b) Defrost cycle is set to 0. c) Defrost sensor temperature > the set-point of defrost stop temperature.
phase sequence detection
The controller has one channel of buzzer alarm output. In running status, the buzzer beeps in case of sensor fault, outrange of sensor ▲
1. Phase sequence detection module controller is power on.
2. Enable time filter function
Safety rules
defrost sensor
power supply 220VAC
cold storage sensor
3. Alarm output
Protection rules
current transformer
compressor
defrost
Notice
or strong corrosion environment. 4. The power voltage must be in accordance with the voltage labeled on the controller. Please ensure the stability of power voltage. V1.0