Status: In progress



Done



Signed



Punched Item



Date: 01.02.2013



Engine control and supervision sensors test 1.



Equipment information



GENSET NUMBER



#7



Engine type



W18V46



Engine serial number



91414



Generator manufacturer



ABB



Generator type



AMG 1600SS12 DSE



Generator serial number



4573681



2.



Check of engine primary control functions



Designation



Description



Engine start command (Local)



Engine is started from Local panel. Engine can only start when the start block function is not active.



Engine stop command (Local)



Engine is stopped from Local panel. Only if local/remote switch is in local



Engine start command (CFC061)



Engine is started from CFC061 panel. Engine can only start when the start block function is not active.



Engine stop command (CFC061)



Engine is stopped from CFC061 panel. Only if local/remote switch is in remote



Engine start command (WOIS)



Engine is started from WOIS system. Engine can only start when the start block function is not active.



Engine stop command (WOIS)



Engine is started to its nominal speed and given stop command from WOIS system.



Engine speed increase / decrease commands



Engine speed can be controlled when genset control is selected manual and operation mode is speed droop. (engine not synchronized).



Excitation increase / decrease commands



Generator excitation can be varied when genset control mode is selected manual and generator control in voltage droop control.



Breaker close command against dead bus



Voltage sensing circuit is tested by simulating the conditions when breaker should not close. Closing only possible against dead busbar.



Checked (ok?)



3.



Testing of hardwired shut down functions with running engine



Designation



Description



Emergency stop, CFA901



Emergency push button (plant shut down) activated in common control panel CFA901



Emergency stop, CFC0_1



Emergency push button activated in engine wise control panel CFC0_1.



Emergency stop, CFE0_1



Emergency push button activated in engine wise control panel CFE0_1.



Lube oil pressure line towards to pressure Lubeoil pressure low shut down switch PSZ201 is closed and vented to function simulate low pressure. Also PT201 PLC HT Water temperature high shut down function



HT water temperature sensor TE402 or TE403 heated over 105°C to activate the shut down function. PLC



PLC initiated shut down function



One shut down function executed in PLC is simulated in order to check the functionality of the shut down circuit with running engine.



Auto shutdown



Engine shutdowns automatically if breaker has tripped and after 2 min running in idle



Oil mist shutdown



Test to blow smoke in to the test opening on oil mist detector



HT water pressure shutdown



Increase the HT water pressure, PLC



LT water pressure shutdown



Increase the LT water pressure, PLC



Exhaust gas temperature



PLC initiated shut down function



Main bearing temperature



PLC initiated shut down function



Cylinder liner temperature



PLC initiated shut down function



Generator winding temperature



PLC initiated shut down function



Generator bearing temperature



PLC initiated shut down function



Checked (ok?)



4.



Engine overspeed protection



Designation



Description



Overspeed protection, engine speed control system



Engine speed is raised to reach engine over speed limit, or trip limit is reduced to simulate overspeed trip. Limit is set in the software.



Mechanical overspeed protection



Engine’s speed is raised until the mechanical over speed limit is reached. (if applicable)



5.



Over speed setting



Measured maximum speed



575rpm



Test of engine’s synchronization functions



Designation



Description



Manual synchronization



Engine frequency and voltage level can be controlled on the engine to be synchronized on the busbar. Breaker closed manually on the sync unit.



Automated synchronization



Engine frequency and voltage controlled by auto synchronizer. Breaker closed automatically.



6.



Test equipment used



Signal simulator: Pressure pump:



Checked (ok?)