Characteristics... .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . Stipulation.. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. Technical Data.. .. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. ... Structure and installation.. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. ... 4.1 outside drawing.. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 4.2 inside construction drawing.. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. 4.3 installation dimension drawing.. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. ... 4.4 external wiring requirement.. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 4.5 external terminal layout drawing. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. From installation to operation. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. Basic functions... .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. ... 6.1 start up.. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. ... 6.2 register external device. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 6.3 fire alarm.. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. 6.4 monitoring information.. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 6.5 associate operation information. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. ... 6.6 fault alarm..... .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. 6.6.1 main power supply fault. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 6.6.2 back-up power supply fault. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. ... Menu operation function.. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 7.1 device information.. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 7.2 register information. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. ... 7.3 event record.. .. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . ... 7.4 adjust time.. .. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. 7.5 associated setup. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. 7.5.1“or”1 logic setup. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. 7.5.2“or”2 logic setup. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. 7.5.3“and” logic setup.. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. ... 7.5.4 pulse mode module . .. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . 7.6 system setup.. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. ... 7.7 exit.. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. ... System self-check. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. ... Lock key/Unlock.. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. Automatic/Manual switch.. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. ... Associated control. .. .. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. Repair and Maintenance. .. .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . ... Notice. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . Our service. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. . ..



1 1 2 3 3 4 6 6 6 7 7 7 7 8 9 9 9 9 9 9 10 11 12 12 12 13 13 13 14 14 14 15 15 15 16 16 17 17



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



Hello! Welcome to Brightsky World!Connecting newest technology 5iserise fire alarm system that will Exceed your imagination:directly and plenty figure interface you will be the first time to feel our products’ reliability,The speed of fire alarm system is quicker than before, Brightsky Electronic Co., Ltd quests system reliability and accurately that will be embodied completely. This customer manual will let you know the super function of this kind of machine step by step.



Characteristics — — — — — — —



Graphic menu operation, new design Black box record function Detector condition display 250 intelligent bus device points capacity Alarm address information second-conversion accurate locating fire address(can input in the form of pre-programming at desk computer or laptop) All fire protection linkage operation relationship on-site programming Standard 485 interface, LAN network and remote communication function



Our Stipulations In below descriptions: —



—



—



all



display letter or icon is button,For example:



this is Down button , 复位 this



is Reset button. Bus equipments which are including heat detectors, smoke detectors, manual call points, signal input module etc fire alarm touching equipments and Long-range control module etc Linkage control equipments. According to habit or description’s requirements,It will be possible to use“Detector”letter can take place smoke detector, heat detector, manual call point, signal input module etc fire alarm touching equipments。



—



In the system, from No.001 to No.250, it is standard device address (detector, remote control module, etc), from No.251 to No.256, it is six multi-line control modules.



Wuxi Brightsky Electronic Co., Ltd 1



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



Technical Data Main Power: :



AC 220V (+10%~-15%) ,50HZ



Back-up power supply:



DC 24V,2.3AH(built in)



Work consumption:



Monitor state:≤2.4W;Alarm state:≤10W



Basic monitoring capacity:



5i series addressable device 250 pieces



Direct external control contact:



6 pairs



Polling cycle:



≤10 second(when Condition abnormity, single point continues to poll)



Signal transportation distance:



≤1500 meters.



Wiring method:



1、 5i series detectors——2-wire bus, non-polarity; 2、 5i series modules——2-wire bus, polarity(T+——anode, T-——cathode);



Wire application:



RVS-2×1.5mm2 two color plastic soft wire.



Outside control touch points:



KA1,KA2 first time alarm, then closed immediately. YA1,YA2 first time alarm under nobody controlled machine delay 2 minutes closed.



Outside control touch points capacity:



DC 30V,2A.



Operation Environment Temperature:



0℃~55℃



Relatively humidity:



≤95%



External dimension:



440×340×82(H×W×T)mm3



Installation form:



Wall mounted type



Weight:



About12Kg



Black box record data:



Be able to save 500 records(including open, close, alarm, fault and linkage information)



Linkage programming amount:



150 items(or one, or two, with logic 50 items)



Room number conversion capacity:



250 pieces



Room number conversion maximum allowable characters numbers:



30 pieces English characters



2



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



Wuxi Brightsky Electronic Co., Ltd 5



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



Fire alarm controller should be installed in a room or place where can be controlled by man,at the same time please install fire alarm controller on the wall. Normally fire alarm controller’s bottom is far away from the ground 1.5 meters,It will leave more than 0.5 meter distance in two sides. So that it will be easy operate and maintenance.



This is installation dimension drawing:



6



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



Meanwhile,According to position array figures, in order to check whether wiring is right or not,Each of hardware whether is solid or not. 4、 Start up. 5、 According to fire code and project linkage operation relationship requirement, edit linkage operation relationship list based on “linkage operation programming”section. 6、 Re open the panel, according to “register external device” section, register external devices.



Basic functions Start First time start please press control panel 复位 button,Meanwhile please press main/ reserved power switch,After controller initialized, indicator and sounder check itself,Then all devices of bus are loading(at the moment let loose 复位 ),It takes about 2 minutes. Then system comes to normally monitor and control state,Power of indicate in controller flashes. Attention:Each time restart system linkage is manually state,at the moment automatic/manually indicator always flashes.。



类型设定 Fire Alarm Panel 设备号: 010号至011号 2004/10/23 10:28 类 型:



称重模块



Register outside devices Register outside devices include to register detectors, modules etc connect with bus devices in the return circuit. Register operating, after start the controller,Press controller power switch,when controller panel indicator flashes. Press 复位 register,after finish to register, then indicate to have registered bus devices number and address code. Press or You can check the details’ listing,Press 复位 return to monitor and control state.



004号 参数测试 register :device… 参考值 026 008: 026 当前值 类 型: 烟感



Fire alarm Under normally monitor and control state, the controller patrols registered each of detectors,monitor each of detectors current smoke consistency or temperature value,then using the data to calculate and recognize by formula. Using the data according to formula calculate and recognize. If it is be fit for fire alarm condition,it can be put into fire alarm state. At the moment,the controller sounds 8



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



the alarm,the controller panel’s fire alarm indicator flashes,the displayer indicates alarm address, number etc information,printer(when you install this printer)can print alarm address, alarm time,Meanwhile the outside controller position KA1、KA2 closed,YA1,YA2 begin to delay,If nobody controls controller (reduce sounder or reduce)this position closed. If linkage position is in the automatic state,the controller is according to be the first time addressable linkage logic relation which can set out command in order to start corresponding long-range control module,so that start or close outside devices.(For example fire pump)。 System uses different pages approach among fire alarm, linkage and default information ,If there are two or many kinds of alarm information exist at the same time , Please press or switch to another fire alarm type page, Press or you can check the up or down information.。 Therein: fire alarm page displays fire detector, manual call point, etc alarm information monitoring page displays feedback signal from signal input module and remote control module. Linkage operation page displays activation signal of remote control module. All fault information is displayed in fault page besides power supply and back-up power supply fault information.



Fire:03



Associate:01 Monitor:02 004号 * * * * * * 参考值 Fire 01/03 002 : 026 smoke detector 当前值: 026 2004/10/23 10:26 类 型: 烟感 Memo:room1



Fault:01 参数测试



In above figure: “Fire:03”express there are three fire alarm signals for the time being. “Fault:01”express there is one fault signal for the time being. “Associate:01”express there is one linkage operation for the time being. “Monitor:02”express there are two monitoring feedback for the time being. “Fire 01/03 002”shows that it is first page of fire alarm page. Alarm number is No.002 device. “smoke detector”express No.002 is one smoke detector “2004/10/23 10:26”express it is the alarm time. “memo:room1”express this detector is installed in “room1”. Fire alarm display will not disappear by itself. We should use manually reset to disarm detector alarm condition, then the page will come back to front page.



Monitoring information All information from signal input module alarm information and remote control module’s feedback information will be displayed in this page. This page displayed information format is almost same as in “fire alarm”section. So it is not shown Wuxi Brightsky Electronic Co., Ltd 9



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



once again here. After the monitoring signal disappears, the relevant display will also disappear, which is one important different point from fire alarm display.



Associate operation information Remote control module activated information is shown here. This page displayed information format is almost same as the one in “fire alarm” section. So we do not repeat it here. After the module is closed, the display will disappear.



Fault Alarm In order to ensure fire alarm control system can be longer normally running,The controller must monitor circuit, detector, long-range control module etc bus equipment and power, accumulator etc devices,that means there are alarm and default function. When there has default and alarm,It will set out default alarm sound, the indicator will flash in the controller ,the monitor displays default type。 If detectors or long-range control module default,The printer(when you set up this printer)print default address, alarm time,the monitor will display alarm address, number etc information. At the moment,the operator should obviate the default, After obviated default ,the controller can reduce automatically,change to normally Alarm state. This page displayed information format is almost same s the one in “fire alarm” section. So we do not repeat it here.



Main power fault Main Power fault is AC 220V Power voltage is not lower than 187V(Including no electric),the controller indicates main power abort,Main power abort indicator flashes. At the moment,the controller must have reserved power,otherwise, the controller is due to no electric so that the controller stops working.



Back-up power supply fault Reserved power abort tat means reserved power in the controller is lower than 19.2V,reserved power opened wire, reserved power is no charge,the controller indicates reserved power abort,reserved power abort indicator flashes.



Menu operation function Under monitor state,according to menu button display input password:



Menu password 进入菜单操作:







10



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



After inputted password is correct, enter main menu, otherwise, be back to monitor state. There are seven menu options in main menu,these include “Device information”、 “Register information” 、 “Event record” 、 “Adjust time” 、 “Associated setup”、 “System setup” 、“Exit”。 Main Menu 功能菜单



参数测试 Device information



According to or function listing.



press to your need information,According to



enter



Device information “Device information” function is look at each device’s detailed information, which include registered analogue value, current analogue value (smoke value and temperature value), device type, status (whether isolated or not) and remark information.



Device No. : 001 Base Value : 028 参数测试 Current Value: 028/003 : 026 参考值 Type: smoke detector Status: normal 当前值: 026 Memo: room1



004号



类 型: 烟感



“Device No. :001”express current querying No.001 device; “Base Value: 028”express this device registered value is 028; “Current Value: 028/003”express this device current smoke value 028,heat value is 003; “Type: smoke detector”express this device type is smoke detector; “Status: normal”express this device currently works normally. If in “isolated”,it expresses this device has been isolated and it cannot alarm。 “Memo:room1” express this device’s annotation, that is to say, this device’s installation location is in “room1” 。 Push Push Push Push Push This



down or plus one or minus one to change current device number; down or plus ten or minus ten to change current device number; down 自检 (self-test) to change device condition; down 消音 (silence) to return; down menu key (middle key in below small box) and one sub-menu will appear. sub-menu has three items:“edit memo”、 “copy memo”、“return” 。



Wuxi Brightsky Electronic Co., Ltd 11



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



参数测试 1:edit memo



004号



2:copy memo 参考值: 0:return



026 当前值: 026 类 型: 烟感



push down corresponding digital key to enter relevant function。 “Edit Memo”is one text edition interface. It’s function mainly is input device installation location, that is remark, in order to show its accurate alarm lication.



Memo edit



联动控制 No.001



Hello world



模块号:000



ABC 001 012



按消音打开,自检关闭



push down 自检 (self-test) switch input method; push down 消音 (silence) delete current cursor location character; push down menu key( middle key in below small box) to store modification and return。



“Copy Memo” is copy current device remark to other device。 Copy No.001 to



或1逻辑控制



00条



From: 002 to 006 控制源: 001号至020号



控制对象:



push down push down



自检 消音



120号至123号



(self-test)to start copy; (silence) to return。



Register information “Register information” function is check registered external device numbers。 Device Total:120 登录查阅 001 006 001 011 006 016 011 021



Press



or



002 007 002 012 007 017 012 022



003 008 003 013 008 018 013 023



总数:100



004 009 004 014 009 019 014 024



005



010 005 015 010 020 015 025



check details’ listing,Press



复位



return main menu。



Event Record 12



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



“Event Record” is query historic alarm records, which include: Fire、Fault、 Monitor、Associate、Power-On、Power-Off、Reset、AC Fault、DC Fault、 Manual Status、 Auto Status, etc. Event Record Total:500 406 001 故障 017号 001 manual status 2002/02/24 10:32:20 Time:2004/10/23 10:28 002 fire 005 002 开机 Type:smoke detector 2002/02/24 10:20:10 Time:2004/10/22 10:28



The latest record will be first shown. Push down or to query above or next record. Push down 消音 (silence) to return main menu. Push down 1 to print(when ancillary device is installed) events record.



Adjust Time “Adjust Time” is set up date and time in the system。 时间设置Time Adjust 2002/04/22 10:53:21 2004/10/22



Push down or to move cursor; Push down digital key to change time value; Push down 自检 (self-test) to store date and time modification and start to use new date and time. Push down 消音 (silence) to give up modification and directly return main menu.



Associated Setup “Associated Setup” is automatic associated/linkage operation after the fire alarm happens. The control panel will make a judge from alarm information and start or close relevant devices based on linkage operation programmed logic relationship ( in manual operation condition, all linkage operation dependency relationship is not valid). It has five menu items, which include :“OR1 Logic Setup” 、“OR2 Logic Setup” 、 “AND Logic Setup”、“Pulse Mode Setup”and “Exit” Associated operation 1:OR1 Logic setup 2:OR2 Logic setup 3:AND Logic setup 4:pluse mode setup 0:exit



Push down corresponding digital key to enter relevant function. OR1 Logic Setup Wuxi Brightsky Electronic Co., Ltd 13



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



“OR1 Logic Setup”: if any one detector in one detectors group alarms, it will initiate or close corresponding device. OR1 logic setup



或1逻辑控制



000



00条



Activate source:



001 to 003 控制源:From: 001号至020号 Activate object: From: 120号至123号 011 to 012 控制对象:



now we use above chart example to explain all data meaning in “OR1 Logic Setup” programming. That is: set up any one detector (from No.001 to No.003) to alarm within “Activate source”range,it will activate remote control modules(from No.011 to No.012) within “Activate object”date range. Top right corner “000”express current one is No.00 item (one item per page). Push down digital key to edit various data items. Push down or to move cursor,push down or to edit or query above or next item(page) data. After the setup is completed, input end item, that is, set up this page’s first data item as “ 0 ”。 Push down 消音 (silence) to return associated/linkage operation programming menu.



OR2 Logic Setup “OR2 Logic Setup”: if any two detectors alarm in one detectors group, it will start or close relevant devices. Chart example and setup method is referred to “OR1 Logic Setup” AND Logic Setup “AND Logic Setup”: if any one detector in one group and any one detector in another group alarm simultaneously, it will start or close relevant devices.



AND logic setup



或1逻辑控制 Activate source:



000



00条



From: 001 to 003 006 to 009 控制源:From: 001号至020号 Activate object: From: 120号至123号 015 to 015 控制对象:



Now we use above chart example to explain various data meaning in AND logic programming, that is: any one detector (from No.001 to No.003) set up within “Activate source1”data item range and any one detector (from No.006 to No.009) set up within “Activate source2” data item range alarm simultaneously, it will activate the remote control module(from No.015 to No.016) set up in “Activate object” data item range. Top right corner “000” express current item is No.00 item(each item per page). This page’s other operation is referred to “OR1 Logic Setup” section. Pulse Mode Module 14



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



“Pulse Mode module” expresses remote control module activation is point activated method, that is, after the module is closed and two seconds delay, it will be broken up once again.



pluse mode module



或1逻辑控制



000



00条



From: 021 to 023 控制源: 001号至020号



控制对象:



120号至123号



For example, in above figure, the control modules from No.021 to No.023 has been set up into point activation mode. This page’s other operation is referred to “OR1 Logic Setup” section.



System Setup In this sub-menu, you can set up and decide whether the printer need to print the information on real-time base and the control panel need to monitor main power supply and back-up power supply, etc.



System setup print AC monitor 打印机 DC monitor real time polling 主电监视 address code capacity 备电监视 fire repeater



系统管理 real time 1 2 3



> yes : yes



:禁止 : yes : no



:允许 : 000 : 000



:允许 : 000



Push down or to move cursor to next or above item. Push down 自检 (self-check) to change item status. Push down digital key to edit item content. Push down 消音 (silence) to store setup and return main menu. If we set up the printer into non-workable status, the printer will not print out real-time information when there is fire alarm, fault, associated operation and monitoring signal input. But this setup will not influent printing operation in “Event Record”.



Exit It expresses to return monitoring condition. In any interface in main menu, you can directly push down 0 to return monitoring condition.



System self-check System self-check: check system’s display LCD, condition indication LEDs and alarm sounders. In polling condition, push down 自检 (self-check) to enter this function。 Wuxi Brightsky Electronic Co., Ltd 15



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



Test Sound 测试音响



during self-check process, all status LEDs in the front face of the panel will flash, the sounder will send out ambulance car sounder, printer ( if the ancillary device has been installed) will print out “Fire Alarm Panel”。After self-check is completed, it will return to monitoring condition.



Lock key/Unlock To avoid non-operator’s non-proper operation, this control panel has lock key function. In monitoring condition, push down lock key( fourth key start from left to right in small box in the panel)button to enter this function.



输入上锁密码: Keyboard lock







Input lock password. If it is correct, lock key LED will flash. If the key is locked, it cannot do other operation besides silence and unlock operation. If you want to unlock the key, please push down lock key button, it will show “Keyboard Unlock” in the LCD display interface.



Automatic/Manual switch If the system is not monitored by the operator, we can set up the fire alarm control panel into automatic status, that is: when there is fire alarm, the control panel can open or close relevant external devices based on pre-set associated operation logic relationship and it does not need manual interference. When we open the fire alarm control panel, it is in manual condition. In this condition, all associated logic relationships are not valid. That is, associated device cannot be automatically closed based on fire alarm. In monitoring condition, push down “manual/automatic” switch button (the fourth key from left to right in the small box of the panel) to enter this function.



手动自动切换: Switch to auto status







16



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



The same as lock key operation procedure, input switch password. If it is correct, the system will be switched from automatic condition to manual condition. Or vice versa, corresponding “manual/automatic” LED in the panel will be illuminated in manual condition.



Associated control Except that we can use associated logic relationship to active the devices in automatic condition, we also can use system provided “ Associate Operate” function to open or close the devices. For example, for some kind of requirement, you want to some one ventilation fan in third floor, and the remote control module number is No.008 which controls this ventilation fan, you can do following operation: In polling condition, push down 1 key to enter associated function; Push down digital key to input remote control module number 008; Other push-key operation will have indication in the LCD. Associate operate



联动控制



module No : 008



模块号:000



Key’silence’ open Key’selfcheck’ close Key’reset’ return 按消音打开,自检关闭



Repair and Maintenance —



—



—



—



—



Open the machine and it does not implement self-check function, the panel does not have any response: please check main power supply and back-up power supply to see whether they are in normal condition. After check and repair, please open the machine once again. After the machine is open, LCD display mixed codes(cannot be read): character library piece or program slice is broken or it is not plugged tightly. Please change or plug the microprocessor once again and the issue will be solved. After the machine is open, control panel LEDs and sounder self-check are normal, but the LCD does not have back light and display: The reason is that LCD contrast degree is too small. Therefore, we cannot see any display content. Please adjust main board’s contrast degree potentiometer and the issue will be solved. After the machine is open, LCD always displays “system initialization, please wait”: This expresses that the serial EEPROM microprocessor is broken, the control panel always fetch the data. Please change the microprocessor and the issue will be solved. The devices cannot be registered: Possible reason is that we set up non-proper “device type” in the system



Wuxi Brightsky Electronic Co., Ltd 17



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



—



management. 5i series bus device should be set up into “intelligent” condition. Device registration is not complete Possible reason is that device address exceeds the system capacity. For example, if the system capacity is 32 points, then the device address which exceeds 32 points cannot be registered.



Notice —



—



—



Fire alarm control panel should have good ground connecting protection. In the control panel, there should be have earth-connecting sign. The earth connection requirement should follow the stipulation in GBJ116-88 “automatic fire alarm th system design code” 4 section. Fire alarm control panel is specific fire protection device. The system owner need to appoint one full-time person to manage and maintain and check its function on regular time and make written record. If the system is in fault condition, please ask professional person or contact original manufacturer to repair it. When the main power source is cut off and the system uses back-up battery power source, if the control panel sends out back-up battery power fault alarm signal, it expresses the back-up battery voltage is too low. In this time, we need to take other offset measures to avoid battery damage caused by back-up battery unrestrained discharge.



Our Service The control panel operator must be trained by our company. For some basic maintenance work, the persons who have been trained can deal with. But during the operation, if you meet some abnormal situation which you are not familiar with, please call us and our technical engineers will make relevant answers for you. Or, we can dispatch our persons to your site system to make service(based on China market). Also you can visit our company website (www.bsky.cn) to understand our company development and read any document you are interested in.



Special notes Wuxi Brightsky Electronic Co., Ltd follows continuous development strategy. So we keep the rights to modify our current product ranges and technical specification which does not need to inform our customers in advance.



18



无锡蓝天电子有限公司



JB-QB-5Si fire alarm control panel (associate operation type) operation manual



This operation manual copy right belongs to Wuxi Brightsky Electronic Co., Ltd



Wuxi Brightsky Electronic Co., Ltd 19