Method of Statement For Testing & Commissioning of Fire Alarm System [PDF]

  • 0 0 0
  • Suka dengan makalah ini dan mengunduhnya? Anda bisa menerbitkan file PDF Anda sendiri secara online secara gratis dalam beberapa menit saja! Sign Up
File loading please wait...
Citation preview

Menu



HOME »» ELECTRICAL METHOD STATEMENTS »» METHOD OF STATEMENT FOR TESTING & COMMISSIONING OF FIRE ALARM SYSTEM



Method Of Statement For Testing & Commissioning of Fire Alarm System The Advertisement



purpose



mentioned statement steps



is



for



of



below



method to



explain



the



Commissioning



of the



testing



of



fire



&



alarm



system. This procedure is to define the step by step method to



implement



the



correct practices for the pre commissioning



&



commissioning of “Fire Alarm System”through the guidelines contained



herein



so



as



to



ensure that the job execution complies with the project requirements and serves the intended function to satisfactory level. Tools Required: Portable Hand tools Step Ladder Insulation Resistance Tester Continuity tester



Pre Commissioning Procedure for Fire Alarm System Ensure that the Fire alarm field devices installation is complete and completion is approved. Ensure a written acceptance test procedure (ATP) for testing the fire alarm system components & installation will be in accordance with NFPA 72 and specifications & approved by civil defense authority. Ensure that no damage has occured between mechanical completion & precommissioning. Repair / replace damaged components, if any. 1. Cable Testing Upon completion of installation & inspection of cables they will be



tested as follows: Upon completion of glanding of the cables, the cables will be tested with a standard industrial insulation tester. The tests shall be carried out to check for short circuits between conductors & between conductors and the outer sheath. If each core cannot be identified, they will be phased to determine each core at both ends& will be suitably marked. 2. Ensure that the smoke detectors, speakers,bells, strobes & fire man’s telephone jack are identified location wise and service wise. 3. Ensure



that



the



wiring



termination



to



the



Fire



Alarm



Panels



are complete & correct polarity is maintained for all field devices. 4. Ensure



that



wiring



termination



to



the



voice



evacuation



panels



for speakers and fire man’s telephones are complete & correct polarity are maintained at all field devices. 5. Ensure that the Fire alarm cables are pretested for continuity before termination. 6. Ensure



that



the



earthing



of



the



Fire



Alarm



panels



&



voice



evacuation panels has been completed. 7. Ensure the availability of power supply to the fire alarm panels & voice evacuation panels. 8. Check the presence of batteries in all Fire alarm panels. 9. Check for the proper location & mounting height of all the manual call points. 10. Check all field devices are properly supported & secured. 11. Check for proper identification of all Fire alarm cables.



Commissioning Procedure for Fire Alarm System 1. Ensure



that



all



the



pre



commissioning



checks



are



carried



out



successfully. 2. Switch ON the power supply to the Fire Alarm Panel. 3. Presence of each device shall be proven by electrical operation of the device & its location shall be checked to correlate with the approved shop drawings. 4. Cause



&



effect



programming



the specification requirements.



shall



be



undertaken



in



line



with



5. Simulate one of the the smoke detector by artificial smoke/magnet & observe the following: Ringing of Bells Sounding of speakers Flashing of strobes Closure of Fire Dampers & its status indication Indication of Fire Zone in the Panel Communication of Fire Status to Control Room Shut down of AHUs Starting of extract fans Operation of Staircase pressurization units Elevators recall Signals to existing towers as per cause & effect. 6. Reset the Fire Alarm panel & check the above after simulating a Heat detector. 7.



Each



initiating



device



shall



be



tested



in



accordance



with



the manufacturer’s recommendations & witnessed to indicate a fire on the control panel.



Eaton: Fire Safety - Safe Evacuations. Planning For Safe Evacuation Of Commercial & Industrial Buildings Is … Ad



uk.eaton.com



Learn more 8. Similarly use the manual call point to check the operational features of the system. 9. Each test fire will be witnessed to trigger the necessary cause & effect or evacuation fire plan. 10. In areas where audible alarms are given the sound levels will be verified in accordance with the specification requirements. Test for Fireman’s telephone System



1. Turn ON fire alarm & voice evacuation panel. 2. Trigger any break glass for fire simulation. 3. Check



for



voice



message



through



speakers



Insert



fire



man’s



telephone in any floor jack & announce a message. 4. Check the recorded message through the speakers are interrupted and the announcement is heard. ATTACHMENTS Precommissioning check sheet for Fire Alarm System Commissioning check sheet for Fire Alarm System



Risk Assesment Advertisement



Eaton: Fire Safety Safe Evacuations. Planning For Safe Evacuation Of Commercial & Industrial Buildings Is Imperative.



OPEN



uk.eaton.com



Share this method statement: Share 0



Share



Method Statement For Testing & Commissioning Of Disabled Toilet Alarm DTA System May 2, 2015 In "Electrical Method Statements"



Testing & Commissioning Method Statement For Fire Fighting Pumps Below is a complete step wise Testing & Commissioning Method Statement For Fire Fighting Pumps. The May 10, 2015 In "Fire Fighting Systems"



Electrical Method Statements



VESDA System Testing and Commissioning Method Of Statement Jun 6, 2015 In "Fire Fighting Systems"



Fire Fighting Systems



Testing &



Commissioning FA System Testing



Fire Alarm Method Of Statement



T&C Of Fire Alarm



System



«« Testing & Commissioning Method Testing & Commissioning Of Fire Statement For Fire Fighting Pumps



Fighting System Hosereel & Sprinkler System »»



Popular Categories Civil Method Statements



Electrical Method Statements Fire Fighting Systems HVAC Method Statements Oil & Gas Systems Plumbing Method Statements Technical Guides Testing & Commissioning



Recent Method Statements Honeycomb Concrete Repair Method Statement Safe Work Method Statement SWMS Explained – Quality Awareness Chasing Work on Block Wall for PVC Conduits GRP Fins Installation Method of Statement Epoxy Paint Application Method Statement Procedure Floating Floor System Installation Method Statement Tower Crane Erection and Dismantling Method Statement Irrigation Pump Installation Method Statement



Top Posts & Pages Download Safe Work Method Statements Testing & Commissioning Method Statement For Fire Fighting Pumps Method Of Statement For Installation of Earthing, Bonding & Lightning Protection System Method Statement For Installation Of Light Fixtures & Fittings Method Statement For Installation of Diesel Generator Set Testing & Commissioning Of Water Supply Piping System Network Method Of Statement For Cleaning Flushing And Passivation Of Chilled Water Piping METHOD STATEMENT FOR INSTALLATION OF WATER SUPPLY PUMP (HOT & COLD)



Testing &



Testing & Commissioning Procedure For Jockey



Pumps - Fire Fighting Commissioning System Procedure For Jockey Pumps - Fire Fighting System