System manual
TEM Evolution System List of limit values
Last revised on: 16.11.06 GW2032_161106EN
We reserve the right on necessary technical modification of the product, deviating from this document in order to improve the system. The reproduction, transmission or use of this document or its content is not permitted without express written authority.
TEM Evolution System
This documentation applies for the following series: TCG 2032
Imprint: DEUTZ Power Systems GmbH & Co. KG Anlagen-Engineering MT-E Carl-Benz-Straße 1 D68167 Mannheim, Germany Phone: +49 (0) 6 21 3 84-86 69 Fax: +49 (0) 6 21 3 84-86 58 www.deutzpowersystems.com Printed in Germany All rights reserved
© GW2032_161106EN
Page 1
TEM Evolution System Notes 1
Notes
1.1
Validity
Column
This list of limit values is only valid for gas engines disbributed by DEUTZ Power Systems equipped with the TEM Basic-System. It is only suitable for the engine type indcated on the front page.
Monitoring Monitoring of the measured values The limit values are indicated as standard values. With regard to the parametrizable monitorings the limit values deviate from the standard values. For the limit value refer to the comment.
The list of limit values is valid for the following software release until a new list of limit values will be published. 2.29.31
1.2
Undershooting of a limit value with fault e.g. lube oil pressure low
Please observe the following documents: • Operating instructions >DEUTZ Power Systems TEM System Evolution • System manual of the TEM-Evo systems, particularly the system manual “Operation log”«
Undershooting of a limit value with alarm e.g. lube oil pressure low Undershooting of a limit value with message e.g.. pre-heating failure Exceeding a limit value with fault e.g. excess temperature jacket water inlet
List of limit values
Column
Explanation
Identification
Name of the limit value
Exceeding a limit value with alarm e.g. excess temperature jacket water inlet Exceeding a limit value with message e.g. power reduction due to excess temperature inlet air
Sensor monitoring
Limit value
Limit value for monitoring with delay time RA
Explanation
Limit value for monitoring with unit On parametrizable limit values the standard value is entered.
RA: Remote acknowledgement 10 h: Remote acknowledgement every 10 h possible © GW2032_161106EN
Page 2
TEM Evolution System Notes Column
Explanation
Abbreviations
Explanation
Delay
Time of delay with unit
MK
Jacket water control
RA
RA: Remote acknowledgement 10 h: Remote acknowledgement every 10 h possible
NA
Handling of mains fault
NATL
Comment
Comment
Monitoring of the exhaust gas temperature after exhaust turbocharger
NK
Emergency cooling circuit
NKS
Emergency cooler - dry cooler
NKAT
Monitoring of the exhaust gas temperature after catalyst
NMOT
Monitoring of the exhaust gas temperature after engine
QEÜ
Acknowledgement externalas monitorings
RL1
Cabin ventilation with admixture or frequency-controlled coolers
SATL
Measuring and limitation of the exgaust turbocharger speed
VAWT
Measuring of the heating water temperature before exhaust gas heat exchanger
VSWT
Measuring cooling/heating wateer before lubricaton oil heat exchanger
1.3
Abbreviations options
Abbreviations
Explanation
AES
Demand of external starting preparations
AKR
Anti-knock governor
AVW
Preheating air inlet
BY
Exhaust bypass
CH4
Additional CH4 compensation
CH4K
Extension of option CH4.
DK
Leakage check
GK
Intercooler circuit
GKS
Intercooler-dry cooler
xMW
Parametrizable data
GL
Monitoring of the generator bearing temperatures
xPR
Parametrizable control circuits
HK
Heat utilization with heating circuit
ZG
Dual gas operation with change of the gas type only at a standstill
© GW2032_161106EN
Page 3
TEM Evolution System List of limit values 2
List of limit values
Identification
Sensor
P145 Crank case
Fault
Monitoring RA Monitoring
Limit value
Delay
RA Comment
10 mbar
0 ms
After start-up phase; limit value at rated speed 1800 rpm: 20,0 mbar
-10 mbar
5 min
With engine running
0 ms Fault Alarm
P196 Lube oil before filter
Fault
500 ms
T201 Receiver
Fault
500 ms
T378 Receiver B
T202 Cooling water GK inlet
Fault
Fault
[GK] Fault
57 °C
2s
Limit value: Par. 13800 + 5,0K
Message
55 °C
2s
Limit value: Par. 13800 + 3,0K
Message
52 °C
5 min
Power reduction.; limit value: Par. 13800; island: delay 30s
500 ms
[GK] Fault
57 °C
2s
Limit value: Par. 13800 + 5,0K
Message
55 °C
2s
Limit value: Par. 13800 + 3,0K
Message
52 °C
5 min
Power reduction.; limit value: Par. 13800; island: delay 30s
500 ms
[GK]
© GW2032_161106EN
Page 4
TEM Evolution System List of limit values Identification
Sensor
T203 Inlet Air
Alarm
T377 Air inlet B
T206 Cooling water engine outlet
T501 Main bearing
T202 Cooling water GK inlet
T208 Lube oil
P232 Receiver
Alarm
Fault
Alarm
Fault
Fault
Alarm
Monitoring RA Monitoring
Limit value
Delay
RA Comment
Fault
40 °C
2 min
[RL without T404]; Limit value par. 13900
Alarm
0 °C
0 ms
Limit value par. 23230 - 5.0K
Alarm
35 °C
2 min
[RL without T404]; Limit value par. 13900 - 5.0K
Message
30 °C
0 ms
With [AVW] limit value: Par. 23230/23231 + 3.0K
Alarm
0 °C
0 ms
Par. 23230 - 5.0K
Message
30 °C
0 ms
With [AVW] limit value: Par. 23230/23231 + 3.0K
Fault
98 °C
2s
Alarm
96 °C
2s
Message
20 °C
240 min
500 ms
500 ms
500 ms
500 ms
X
[GLT] [2020] Alarm
0 °C
0 ms
Limit value: T208 lube oil + 25.0 °C
Fault
0 °C
0 ms
Limit value: T208 lube oil + 30.0 °C
Fault
98 °C
2s
Message
75 °C
5 min
Power reduction.; limit value: Par. 13400; island: delay 30s
Fault
90 °C
0 ms
Limit value: Par. 23019
Alarm
85 °C
0 ms
Limit value: Par. 23019 - 5,0K
500 ms
500 ms
500 ms
[REC] © GW2032_161106EN
Page 5
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring
Limit value
Delay
P270 Receiver (B)
Alarm
500 ms
[REC]
P268 Charging-air pressure
Alarm
500 ms
[REC]
L234 Lube oil level
Fault
500 ms
L234.1 Lube oil level
P302 Lube oil after filter
Filtered value
Fault
Fault
30 %
20 s
With the engine at standstill delay 1s
Fault
120 %
20 s
With the engine at standstill delay 1s
Message
50 %
0 ms
Enabling only during oil change
Message
95 %
0 ms
Enabling only during oil change
500 ms
[NFI] Fault
5.3 bar
0 ms
Operational oil pressure 900rpm: limit value 4.8%
Alarm
5.5 bar
0 ms
Operational oil pressure 900rpm: limit value 5.0%
Fault
2 bar
2s
Starting phase: limit value +delay variable
P302.1 Differential pressure lube oil
P371 Starter air press.
S492 Speed ATL A
[NFI]
Fault
Alarm
Fault
1.5 bar
2 min
Alarm
-1 bar
2 min
Alarm
1 bar
2 min
500 ms
[2032, 2020 V20] enable with Par. 13030 Fault
4 bar
10 s
Enable: Par. 13030; Limit value: at standstill Par. 23050
Alarm
18 bar
15 s
Enable: par. 13030; limit value: Par. 23050
5s
[SATL] Fault
S493 Speed ATL B
RA Comment
Alarm
683 1/s
5s
60 min
Limit value:Par. 15210 + 5% [SATL+(2020 V20, 2032)]
© GW2032_161106EN
Page 6
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring Fault
T494 Exhaust after ATL A
T495 Exhaust after ATL B
Alarm
Alarm
Limit value
Delay
683 1/s
60 min
500 ms
Fault
500 ms
T205 Cold junction B
Fault
500 ms
Limit value: Par. 15210 + 5% [NATL]
Alarm
550 °C
2s
Limit value: Par. 15111 / 15113
Alarm
550 °C
10 min
Enable from 80% of load
500 ms
T204 Cold junction A
RA Comment
[NATL+(2020 V20, 2032)] Alarm
550 °C
2s
Limit value: Par. 15111 / 15113
Alarm
550 °C
10 min
Enable from 80% of load
Turning device Fault T461 Combustion chamber A1
T471 Combustion chamber B1
Fault
Fault
0 ms
500 ms
For each cylinder individually Fault
500 °C
2s
Fault
240 °C
2 min
Limit value 50K-120K below average value; island operation: 10 min
Alarm
240 °C
20 s
Limit value 50K-120K below average value
500 ms
For each cylinder individually Fault
500 °C
2s
Fault
240 °C
2 min
Limit value 50K-120K below average value; island operation: 10 min
Alarm
240 °C
20 s
Limit value 50K-120K below average value
T46x.7 Combustion chamber average
Average value A side
© GW2032_161106EN
Page 7
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring Fault
Limit value
Delay
400 °C
0 ms
T47x.7 Comb. chamber aver. B
RA Comment Limit value 100K (mains) / 160K (island) above set value Average value side B
Fault
400 °C
0 ms
T4xx.2 Act. combustion chamber
Limit value 100K (mains) / 160K (island) above set value Filtered value
Fault
150 °C
0 ms
T47x.2 Act. combustion chamber B
Filtered value Fault
150 °C
0 ms
Fault
10 °C
5 min
Delay variable
Fault
10 °C
0 ms
Delay variable
Message
4s
Stop position not reached
Alarm
0 ms
Stop position not reached
Message
0 ms
Stop position not reached
Message
4s
Stop position not reached
Alarm
0 ms
Stop position not reached
Message
0 ms
Stop position not reached
Deviation comb. chamber control deviation comb. chamber control B Gas mixer limit stop lean Gas mixer start position OK
Gas mixer B limit stop lean Gas mixer B start position OK
© GW2032_161106EN
Page 8
TEM Evolution System List of limit values Identification
Sensor
S200 Engine speed
Fault
Monitoring RA Monitoring
Limit value
Delay
RA Comment
Fault
1150 rpm
200 ms
Limit value: Par. 11108 + 15% (or. +20%)
Alarm
1150 rpm
0 ms
Limit value: Par. 11108 + 15% (resp. +20%), w. auto acknowledgement
Fault
600 rpm
500 ms
Limit value depending on condition
Alarm
60 rpm
0 ms
Speed bef. start
200 ms
DZR TDC sensor fault
TDC-signal missing Fault
2s
Enable with the engine running
Alarm
0 ms
Enable with the engine running, auto acknowledgement
Fault
2s
Enable with the engine running
Alarm
0 ms
Enable with the engine running, auto acknowledgement
Fault
2s
DZR Tooth number fault
DZR TDC mixed up with gear ring G197.1 Throttle valve position
Fault
0 ms
Feedback voltage
G197.Throttle valve position
Fault
0 ms
G197.2 DZR Ukal 0%
Fault
0 ms
Calibration voltage 0%
G197.3 DZR Ukal 100%
Fault
0 ms
Calibration voltage 100%
DZR Calibration G197.4 DZR Current actuator
Fault
Fault
15 s
Calibration failed
Alarm
5s
Enable during load run
0 ms
DZR Current derating DZR Short circuit power stage © GW2032_161106EN
Page 9
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring
Limit value
Fault
Delay
RA Comment
0 ms
AKR Knock sensor fault bank A
[AKR] Alarm
0 (code)
10 s
AKR Knock sensor fault bank B
Enable from 50% of load [AKR]
Alarm
0 (code)
10 s
ZA Maximum adjustment ignition point
Enable from 50% of load [AKR] Sturdy ZZP-adjustment
Alarm
-3 °
0 ms
Critical fault! Engine test required!
Sturdy ZZP-adjustment; limit value: Par. 11503 - 3.0° [AKR] Maximum ZZP-adjustment
Fault
-9 °
6s
AKR Speed signal
Limit value: Par. 11502-1.0°; at least 3.0 ° [AKR] Error speed signal
Alarm
0 ms
Anti-knock governor available
enable during load run [AKR]
Alarm
0 ms
ZA ignites
AKR-card missing Feedback from ZA
Fault
3s
ZA Fault code
Ignition does not ignite Fault message from ZA
Fault
0 (code)
3s
Alarm
0 (code)
0 ms
ZA Capacitor discharge bank A
5min after appearance of alarm: Delay = 0 Error capacitor discharge
Alarm
0 (code)
1 min
Message
0 (code)
0 ms
ZA Capacitor discharge bank B
Error capacitor discharge Alarm
0 (code)
© GW2032_161106EN
1 min Page 10
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring Message
Limit value
Delay
0 (code)
0 ms
RA Comment
ZA Condition serial connection S
Timeout ZA-communication Fault
10 s
ZA Condition serial connection W
Error ZA-communication Message
0 ms
xxxx Number of start attempts Fault T209 Generator-winding U
T210 Generator-winding V
T211 Generator-winding W
T459 Generator bearing A
T460 Generator bearing B
T487 Generator-air inlet
Fault
Fault
Fault
Fault
Fault
Fault
3
0 ms
500 ms
X [GK]
Fault
140 °C
10 s
Limit value: Par. 13500
Alarm
135 °C
10 s
Limit value: Par. 13500 - 5,0K
500 ms
[GK] Fault
140 °C
10 s
Limit value: Par. 13500
Alarm
135 °C
10 s
Limit value: Par. 13500 - 5,0K
500 ms
[GK] Fault
140 °C
10 s
Limit value: Par. 13500
Alarm
135 °C
10 s
Limit value: Par. 13500 - 5,0K
500 ms
[GL] Fault
60 °C
2s
Limit value: Par. 13501
Alarm
55 °C
2s
Limit value: Par. 13501 - 5.0K
500 ms
[GL] Fault
60 °C
2s
Limit value: Par. 13501
Alarm
55 °C
2s
Limit value: Par. 13501 - 5.0K
500 ms
[GLU] Fault
80 °C
2s
Limit value: Par. 13030
Alarm
75 °C
2s
Limit value: Par. 13030 - 5.0K
© GW2032_161106EN
Page 11
TEM Evolution System List of limit values Identification
Sensor
T488 Generator air outlet
Fault
Monitoring RA Monitoring
Limit value
Delay
RA Comment
500 ms
[GLU] Fault
80 °C
2s
Limit value: Par. 13030
Alarm
75 °C
2s
Limit value: Par. 13030 - 5.0K
E121 Generator protection
Input security chain Fault
E198 Actual power generator
Fault
500 ms
0 ms
X
X
E198.2 Actual power
Filtered value Fault
105 %
2 min
Overload; limit value: Par. 13100 + 5%
Fault
120 %
5s
Overload
Fault
-5 %
12 s
X
Reverse power; delay Par. 13510
Fault
1060 kW
15 min
X
Minmum load; V12: 800kW, V16: 1060 kW
Alarm
1060 kW
10 min
E198.8 Actual power in KW
Power reduction due to receiver temperature
Minmum load; V12: 800kW, V16: 1060 kW [GK]
Message
0%
0 ms
Enable with message T201/T378
Message
0%
0 ms
Enable with message T207
Fault
-40 %
0 ms
Message
0%
2 min
Power reduction due to jacket water temperature Power reduction due to throttle
Power reduction due to CH4-value
Island: delay 30s [CH4]
Message
0%
© GW2032_161106EN
0 ms
Enable with message Q311 Page 12
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring
Limit value
Delay
RA Comment
Power reduction due to AKR
[AKR] Message
0%
2 min
Island: delay 30s
Power reduction due to ATL speed
[SATL] Message
E199 Demand analog
Fault
0%
0 ms
Island: delay 30s
500 ms
Only on demand 4..20mA
E199.7 Demand active Message
30 %
0 ms
Fault
5%
5 min
Deviation power control On start and retrace of the engine: limit value 20%
Synchronization Fault
10 min
X
E104 Mains fault
Timeout synchronization [NA]
Fault
30 s
Alarm
0 ms
Message
0 ms
Mains fault sequencial fault
[NA] Fault
0 ms
Fault
0 ms
P124 Gas pressure gas control system A
P125 Leakage check gas A
X
[CH4] Auto acknowledgement (par. 12900) [DK]
Fault
1 min
Timeout leakage check
T147 Temperature monitor gas control system © GW2032_161106EN
Page 13
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring
Limit value
Fault Q311 CH4-value
Fault
Delay 0 ms
2s
[CH4] Fault
38 %
5 min
Limit value: Par. 12806
Message
38 %
0 ms
Limit value: Par. 12806
Message
0%
30 s
Deselection; enable/limit value: Par. 12810, Par. 12811
Message
50 %
5 min
Power reduction.; limit value: Par. 12803; Island: delay 30s
Stop due to CH4 calibration
T289 Heating water-return
RA Comment
[CH4K]
Alarm
Fault
75 min
Timeout calibration
Alarm
75 min
Timeout calibration
500 ms
[HK] Enable with Par. 14009 Message
80 °C
0 ms
[NK]; Limit value: Par. 24510
T290 Heating water before KWT
Alarm
500 ms
[VKWT]
T291 Heating water flow
Fault
500 ms
[HK] Enable with par. 14008
T384 Heat. water at emergency cooler
Alarm
500 ms
[NK+VNK]
T385 Heating water before AWT
Alarm
500 ms
[VAWT]
T386 Heating water before SWT
Alarm
500 ms
[VSWT]
T286 Exh. after engine
Alarm
500 ms
[NMOT] Alarm
T287 Exhaust after KAT
Fault Fault Alarm
Limit value: Par. 15111 / 15113 [NKAT]
550 °C
2s
500 ms
Limit value: Par. 15111 / 15113 [NKAT]
Fault T288 Exhaust after AWT
2s
500 ms Fault
T496 Exhaust gas after KAT B
550 °C
550 °C
0 ms
500 ms
Limit value: Par. 15111 / 15113 [NAWT]
Alarm
180 °C
© GW2032_161106EN
2s
Limit value: Par. 15112 Page 14
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring
Limit value
Delay
RA Comment
P157 Exhaust back press. too high
Limit value switch Alarm
50 mbar
2 min
Exhaust bypass AWT limit stop closed
[HK+BY] Message
500 ms
T276 Overtemperature limiter 1
[HK] Input security chain Fault
0 ms
X
T277 Safety temperature monitor
[HK] Input security chain Fault
0 ms
X
P278 Overpressure limiter a
[HK] Input security chain Fault
0 ms
X
P278.1 Overpressure limiter b
[HK] Input security chain Fault
0 ms
X
P279 Overpressure limiter 1
[HK] Input security chain Fault
0 ms
X
L280 Low water heating circuit
[HK] Input security chain Fault
0 ms
X
P281 Heating circuit pump
[HK] Input security chain Fault
0 ms
X
P457 Pump coupling circuit
[HK] Input security chain Fault
0 ms
X
T435 Overtemperature limiter 2
[HK] Input security chain Fault
0 ms
X
P437 Overpressure limiter 2
[HK] Input security chain Fault
S397 Position HK-control valve
Alarm
500 ms
0 ms
X [HKV]
© GW2032_161106EN
Page 15
TEM Evolution System List of limit values Identification
Sensor
Monitoring RA Monitoring
Limit value
Delay
RA Comment
HK Ctrl. valve limit stop cold
[MK, HK] Message
500 ms
HK Ctrl. valve limit stop warm
[MK, HK] Message
500 ms
Fault
3s
P126 Jacket water pump L123 Low water engine cooling circuit
Input security chain Fault
0 ms
Alarm
2s
X
T156 Pre-heating genset S000 Position intercooler-control valve
Alarm
500 ms
[GKV] Position feedback
GK Ctrl. valve limit stop warm
[GK] Message
500 ms
GK Ctrl. valve limit stop cold
[GK] Message
500 ms
P309 Intercooler pump
[GK] Fault
3s
X
L308 Low water intercooler circuit
[GK] Input security chain Fault
0 ms
X
T405 Intercooler-dry cooler outlet
Alarm
500 ms
[GKS] Enable with par. 13085
S000 Position NK-control valve
Alarm
500 ms
[NKV] Feedback position
NK Control valve limit stop warm
[NK] Message
500 ms
NK Control valve limit stop cold
[NK] Message © GW2032_161106EN
500 ms Page 16
TEM Evolution System List of limit values Identification
Sensor
T419 Emergency cooler-dry cooleroutlet
Alarm
Monitoring RA Monitoring
Limit value
Delay
RA Comment
500 ms
[NKS] Enable with Par. 14055
Air inlet VW limit stop warm
[AVW] Message
500 ms
Air inlet VW limit stop cold
[AVW] Message
T404 Cabin air
Alarm
500 ms
500 ms
[RL1x] Enable with Par. 13092 Fault
40 °C
2s
Limit value: Par. 13900
Alarm
35 °C
2s
Limit value: Par. 13900 - 5,0K
Message
32 °C
2s
Limit value: Par. 13900 - 8,0K
Cabin ventilation
[RL] Fault
3s
Delay during start 60s
Cabin ventil. flap limit stop warm
[RL1x] Message
500 ms
Cabin ventil. flap limit stop cold
[RL1x] Message
500 ms
P127 Gas pressure gas control system B
[ZG] Fault
0 ms
P128 Leakage check gas B
[CH4] Auto acknowledgement (Par. 12900) [ZG+DK]
Fault T131 Temperature monitor gas control system B E149 Supply voltage
X
1 min
Timeout leakage check [ZG]
Fault Fault
0 ms
500 ms Alarm
20 V
© GW2032_161106EN
0 ms Page 17
TEM Evolution System List of limit values Identification
Exxx Earth leakage monitor switching cabinet
Sensor
Fault
Monitoring RA Monitoring
Limit value
Delay
Alarm
30 V
0 ms
Alarm
10 kOhm
5s
RA Comment
0 ms
G143 Circuit breaker TEM swtiching cabinet Fault
0 ms
Fault
0 ms
H141 Internal quick stop H117 Ext. quick stop without heat removal
Input security chain Fault
0 ms
H116 Ext. quick stop with heat removal
Input security chain Fault
0 ms
X
Security chain
Security chain open Fault
0 ms
X
Parametrizable message 01
[xM] Par. message; free text Message
Parametrizable measured value 01
Alarm
0 ms
X
500 ms
Limit value, delay, enable parametrizable [xMW] Par. measured value; free text
Message
0
0 ms
X
Limit value, delay, enable parametrizable
Message
0
0 ms
X
Limit value, delay, enable parametrizable
Control deviation parametrizable controllers 1
[xPR] control deviation par. governor; XX=1..3 Message
10
© GW2032_161106EN
0 ms
X
Limit value, delay, enable parametrizable
Page 18