www.joongwon.co.kr ISO9001



ISO14001



15kV - 38kV Recloser Polymer Insulated Type Type of Recloser : JWREC



-6A



td CopyrightⒸ 2015 JOONGWON Corporation All rights reserved



Rev. 2015/ 1 /REC



Introduction The Joongwon Recloser is designed to meet increasing requirement of the electric utility industry, providing a safe, maintenance free, long life, economical device to perform fault current interrupting and reclosing on overhead distribution lines. The Joongwon Recloser is applicable to 12(max.15)kV, 24(max.27)kV, 36(max.38)kV power distribution systems and substation. It can be operated manually(if applicable) or electrically via controller with FTU and should be mounted to the pole and substation mounting base.



Features - Proven design rated for 10,000 full load operations - Hydrophobic Cyloaliphatic Epoxy (HCEP) insulation provides industry leading reliability - Air insulation for an environmentally friendly design - Minimal maintenance required for the high voltage unit - Web Human Machine Interface (web HMI) software for field configuration - Remote Communication : MODBUS, DNP3.0, DNP3.0 over TCP/IP, IEC 60870-5-101, IEC 60870-5-104 over TCP/IP



Recloser Design



• • •



Magnetic actuator : 10,000 full load operations Vacuum interrupters : Lasting quality with 10,000 full load operations Pole assembly - UV protected for environmental durability - Molded design reduces risk of tampering



• HCEP insulating material - The Recloser insulating material is Hydrophobic Cycloaliphatic Epoxy(HCEP). Hydrophobic means resistant to water. This capability is advantageous because it prevents water from developing completely wetted, resistively conductive surfaces on outdoor insulation.



BUSHING TERMINAL LIFTING LUG



GROUND CONNECTOR



TRIP HANDLE



CLOSING HANDLE



Front View Of Recloser



RECEPTACLE



Rear View Of Recloser



td CopyrightⒸ 2015 JOONGWON Corporation All rights reserved



15kV - 38kV Polymer Insulated Outdoor Vacuum Recloser for Distribution Automation Ratings Ratings and technical data RATINGS



ITEM RATED SYSTEM VOLTAGE



12 (max. 15)



36 (max. 38)



630



RATED CONTINUOUS CURRENT RATED INTERRUPTING CURRENT



24 (max. 27)



kV A



12.5 / 16



12.5 / 16



12.5 / 16



kA



DRY (1 MIN.)



50



60



70



kV



WET (10 SEC.)



45



50



60



kV



110



150



170



kV



POWER FREQUENCY WITHSTAND VOLTAGE



LIGHTNING IMPULSE WITHSTAND VOLTAGE RATED FREQUENCY PHASE SPACING



Hz



50 / 60 320



320



394



mm



EXTERNAL CREEP DISTANCE, H2-GROUND



1 486



1 486



1 502



mm



EXTERNAL CREEP DISTANCE, H1-H2



1 344



1 344



1 376



mm



MIN. EXTERNAL STRIKE DISTANCE



284



284



448



mm



MIN. INTERRUPTING TIME



0.050



sec



MAX. CLOSING TIME



0.070



sec



INSULATING MATERIAL



Epoxy -25 to 70



°C



HUMIDITY



≤100



%



ALTITUDE



≤ 2,000



m



AMBIENT TEMPERATURE



DEGREE OF PROTECTION



IP X 8 O - 0.3s - CO - 1s - CO - 1s - CO - lockout



RATED STANDARD OPERATION DUTY



10,000 times



MECHANICAL ENDURANCE



AC 110 - 220 V / DC 24 V



RATED CONTROL VOLTAGE WEIGHT (BODY) WEIGHT (CONTROLLER) APPLIED STANDARD



120



150



230



kg kg



40 IEC 62271-111, ANSI C37.60 & KEPCO spec.



Note : According to the user’s demand, Joongwon can supply Recloser with different ratings not indicated above.



td CopyrightⒸ 2015 JOONGWON Corporation All rights reserved



15kV - 38kV Polymer Insulated Outdoor Vacuum Recloser for Distribution Automation Recloser control RATINGS RATED FREQUENCY



50 or 60 Hz



CONTROL VOLTAGE



AC 110 - 220 V / DC 24 V



ENVIRONMENTAL



AMBIENT TEMPERATURE RANGE



STORAGE -40°C TO +85°C, OPERATION -25°C TO +70°C



OUTDOOR (HUMIDITY)



100%



DEGREE OF PROTECTION



IP65 .



INSULATION TEST VOLTAGE



2 kV 50/60Hz, ONE MINUTE



IMPULSE VOLTAGE WITHSTAND



6 kV PEAK, 1.5/50µs, ANSI C62.45, IEC61000-4-5



INTERFERENCE TEST WITHSTAND



SWC ANSI C37.90.1, IEC 61000-4-4



RADIO FREQUENCY INTERFERENCE



IEC 255-22-3 CLASS III, ANSI C37.90.2



GENERAL PROTECTION ( CT RATIO 1000 : 1 A) PHASE TIME OVERCURRENT



CT RATIO X (0.005 ̴ 1.60), (5 ̴ 1600A)



PHASE INSTANTANEOUS OVER CURRENT



CT RATIO X (1.00 ̴ 20.00), (1000 ̴ 20000A)



GROUND TIME OVER CURRENT



CT RATIO X (0.0025 ̴ 0.80), (2.5 ̴ 800A)



GROUND INSTANTANEOUS OVER CURRENT



CT RATIO X (1.00 ̴ 20.00), (1000 ̴ 20000A)



SENSITIVE EARTH FAULT



CT RATIO X (0.0025 ̴ 0.160), (2.5 ̴ 160A)



PHASE AND GROUND TIME CURVE



IEEE C37.112, IEC 60225-3, USER PROGRAMMABLE CURVE 37



RECLOSER RECLOSER TIMES RECLOSING ( DEAD ) TIMES



PROGRAMMABLE FROM 1 TO 4 1st RECLOSER : 0.3-600SEC IN 0.01SEC STEPS. 2nd RECLOSER : 1.0-600SEC IN 0.01SEC STEPS. 3rd RECLOSER : 1.0-600SEC IN 0.01SEC STEPS. 4th RECLOSER : 1.0-600SEC IN 0.01SEC STEPS.



RESET (RECLAIM) TIME



1-600SEC IN 1SEC STEPS



METERING ( AT RATED VOLTAGE AND CURRENT ) CURRENT



±1%



VOLTAGE



±2.5%



WATT HOURS



±5%



VARS HOURS



±3%



DEMANDS



±3%



POWER FACTOR



±0.05%



FREQUENCY



±0.05Hz



RECORDING WAVEFORM CAPTURE



LAST 32 EVENTS WITH 20 cycles & 128 SAMPLES



SYSTEM EVENT



LAST 2048 EVENTS



DIAGNOSTIC EVENT



LAST 512 EVENTS



LOAD PROFILE



LAST 1024 EVENTS, 42 DAYS / 60 Min. (5,10,15,20,30,60 Min INTERVAL)



COUNTER



TRIP, FAULT, SYSTEM RESTART, PQM



RECLOSER WEAR



PHASE A,B,C



PQM



LAST 100 EVENTS