CSU501B Configuration Manual [PDF]

  • 0 0 0
  • Suka dengan makalah ini dan mengunduhnya? Anda bisa menerbitkan file PDF Anda sendiri secara online secara gratis dalam beberapa menit saja! Sign Up
File loading please wait...
Citation preview

CSU CONFIGURATION - SWAP ORURO POTOSI TARIJA - ENTEL CSU Administrator User Log in Item



1



Parameter Name



Log in as Administrator



Default Value



Customer



2



Item



Parameter Name



Battery Type



Parameter Name



2. Select Administrator



3. Insert password 0063



Password: 0063



System Parameters Item



1. Select User Type



Set up Value



Set every Battery Bank according to the number required at each Site Default Value



FeLiPO4 Batt.



Default Value



Set up Value



1. Select Para. Set



2. Select System Para.



3. Change to Lead Batt. If needed



1. Select Para. Set



2. Select System Para.



3. Select the Batt Bank in Lines 1/38 and 2/38



1. Select Para. Set



2. Select Batt. Para.



3. Set the Float Voltage to 53.5V. Line 2/69



1. Select Para. Set



2. Select Batt. Para.



3. Set the Float Voltage to 56.4V. Line 3/69



1. Select Para. Set



2. Select Batt. Para. And Select Chg. Curr. Coeff.



3. Adjust the current coeff. To 0.100C10. Line 10/69



1. Select Para. Set



2. Select Batt. Para. And Select Chg. Curr. Coeff.



3. Set the LLVD1 Voltage to 44.0V



1. Select Para. Set



2. Select Batt. Para. And Select Chg. Curr. Coeff.



3. Set the LLVD2 Voltage to 44.0V



Lead Batt.



Set up Value



3



Battery Cap.-1#



800AH



135AH



4



Battery Cap.-2#



800AH



135AH



5



Battery Cap.-3#



0AH



135AH



6



Battery Cap.-4#



0AH



135AH (if is Rural Solution)



Battery Management Parameters Item



7



Item



8



Item



9



Item



10



Item



11



Parameter Name



Float Voltage



Parameter Name



Equalized Voltage



Parameter Name



Chg. Curr. Coeff.



Parameter Name



LLVD1 Voltage



Parameter Name



LLVD2 Voltage



Default Value



53,5V



Default Value



56.4V



Default Value



0.150C10



Default Value



45.0V



Default Value



44.0V



Set up Value



53,5V



Set up Value



56.4V



Set up Value



0.100C10



Set up Value



44.0V



Set up Value



44.0V



Notes: ……………………..………………………………………………………...……………………………………………...………………………………………………..…………………………….. ……………………..………………………………………………………...……………………………………………...………………………………………………..…………………………….. ……………………..………………………………………………………...……………………………………………...………………………………………………..…………………………….. ……………………..………………………………………………………...……………………………………………...………………………………………………..…………………………….. ……………………..………………………………………………………...……………………………………………...………………………………………………..…………………………….. ……………………..………………………………………………………...……………………………………………...………………………………………………..…………………………….. ……………………..………………………………………………………...……………………………………………...………………………………………………..……………………………..