Dimensional tolerances – API 650-14 Sr.

Item

Tolerance  The maximum out-of-Plumbness of the top of the shell relative

13 0 116 KB

Report DMCA / Copyright

DOWNLOAD FILE

File loading please wait...
Citation preview

Dimensional tolerances – API 650-14 Sr.



Item



Tolerance  The maximum out-of-Plumbness of the top of the shell relative to the bottom of the shell shall not exceed 1/200 of the total tank height.



1.



Plumbness (7.5.2)



 The out-of-Plumbness in one shell course shall not exceed the permissible variations for flatness and waviness as specified in ASTM A6M/A6, ASTM A20M/A20, or ASTM A480M/A480, whichever is applicable.  According to Tank Diameter:



2.



Roundness (7.5.3)



3.



Peaking (7.5.4.a)



 Deviations at vertical weld joints shall not exceed 13 mm. (by using Sweep board with 90 cm long with the same radius of the tank)



4.



Banding (7.5.4.b)



 Deviations at horizontal weld joints shall not exceed 13 mm. (by using 90 cm straight edge vertical sweep board)



5.



Flat spots (7.5.4.c)



 Shall not exceed the appropriate plate flatness and waviness as required by ASTM A6, A20 or a480 as applicable)  For horizontal foundation: 1- Where a concrete ring wall is provided under the shell, the top of the ring wall shall be level within ±3 mm in any 9 m of the circumference 2- Where a concrete ring wall is not provided, the foundation under the shell shall be level



6.



Foundations (7.5.5)



within ±3 mm in any 3 m of the circumference  For sloping foundation: 1- Where a concrete ring wall is provided, ±3 mm in any 9 m of circumference 2- Where a concrete ring wall is not provided, ±3 mm in any 3 m of circumference



 Nozzles (excluding manholes) shall be installed within the following tolerances: 1- specified projection from outside of tank shell to extreme face of flange: ±5 mm 2- elevation of shell nozzle or radial location of a roof nozzle: ±6 mm 7.



Nozzles (7.5.6)



3- flange tilt in any plane, measured on the flange face: 



±1/2 degree for nozzles greater than NPS 12 in. nominal diameter







±3 mm at the outside flange diameter for nozzles NPS 12 and smaller



4- flange bolt hole orientation: ±3 mm  Manholes shall be installed within the following tolerances: 8.



Shell Manholes (7.5.87)



1- specified projection from outside of shell to extreme face of flange, ±13 mm 2- elevation and angular location, ±13 mm 3- flange tilt in any plane, measured across the flange diameter, ±13 mm