SEL-751 Settings Report Overview Information File Name
Configuración Nueva 3
Device
SEL-751
RDB
Setting Version Number Part Number Firmware ID
SELBoot Firmware ID
Relay.rdb 007
751001A0X0X0X811A00
SEL-751-RXXX-V0-Z007003-DXXXXXXXX
SLBT-751-RXXX-V0-Z007003-DXXXXXXXX
Settings Global Group 1
Settings Legend Visible Setting Hidden Setting Invalid Setting
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 2 of 10
Global Setting
Description
Range
Value
FNOM
Rated Frequency (Hz)
Select: 50, 60
60
PHROT
DATE_F
METHRES
Phase Rotation Date Format
Meter Cutoff Threshold
FAULT
Fault Condition (SELogic)
EMP
Messenger Points Enable
SS1
Select Settings Group1 Equation (SELogic)
SS2
Select Settings Group2 Equation (SELogic)
SS3
Select Settings Group3 Equation (SELogic)
SS4
Select Settings Group4 Equation (SELogic)
EPMU
Enable Synchronized Phasor Measurement
UTC_OFF
Offset From UTC (hours, in 0.25 hour increments)
TGR
IRIGC
Group Change Delay (seconds)
IRIG-B Control Bits Definition
DST_BEGM Month To Begin DST 52ABF
52A Interlock in BF Logic
BFD
Breaker Failure Delay (seconds)
50BFP ATD
Breaker-Failure Current Detector Pickup (amps sec.) Auxiliary Timer Delay (seconds)
BFI
Breaker Failure Initiate (SELogic)
IN101D
IN101 Debounce (milliseconds)
EBMON
Enable Breaker Monitor
IN102D
IN102 Debounce (milliseconds)
BKMON
Control Breaker Monitor (SELogic)
COSP1
Close/Open Operations Set Point 1-max
COSP2
Close/Open Operations Set Point 2-mid
KASP1 KASP2
kA(pri) Interrupted Set Point 1-min kA(pri) Interrupted Set Point 2-mid
Select: ABC, ACB
Top
ABC
Select: MDY, YMD, DMY MDY Select: Y, N
Y
Range = 1 to 32, N
N
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Range = 0 to 400
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
50G1P OR 50N1P OR 51P1P OR 51QP OR 50Q1P OR TRIP 3 1 0 0
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Select: NONE, C37.118
NONE
Select: Y, N
N
Range = -24.00 to 24.00
0.00
Range = 1 to 12, OFF Select: Y, N
Range = 0.02 to 2.00 Range = 0.00 to 2.00
OFF N
0.02 0.50
Range = 0.00 to 2.00, OFF OFF Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
R_TRIG TRIP
Range = 0 to 65000, AC
10
Range = 0 to 65000, AC
10
Select: Y, N
Y
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
TRIP
Range = 0 to 65000
10000
Range = 0 to 65000
150
Range = 0.00 to 999.00 Range = 0.00 to 999.00
1.20 8.00
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 3 of 10
COSP3
Close/Open Operations Set Point 3-min
Range = 0 to 65000
12
RSTTRGT
Reset Targets (SELogic)
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
KASP3
kA(pri) Interrupted Set Point 3-max
RSTENRGY Reset Energy (SELogic) RSTMXMN Reset Max/Min (SELogic) RSTDEM
Reset Demand (SELogic)
RSTPKDEM Reset Peak Demand (SELogic) DSABLSET Disable Settings (SELogic) TIME_SRC
IRIG Time Source
89A2P1
Disconnect 1 N/O Contact (SELogic)
89B2P1
Disconnect 1 N/C Contact (SELogic)
89A2P1D
Disconnect 1 Alarm Timer (seconds)
89A2P2
Disconnect 2 N/O Contact (SELogic)
89B2P2
Disconnect 2 N/C Contact (SELogic)
89A2P2D
Disconnect 2 Alarm Timer (seconds)
89A2P3
Disconnect 3 N/O Contact (SELogic)
89B2P3
Disconnect 3 N/C Contact (SELogic)
89A2P3D
Disconnect 3 Alarm Timer (seconds)
89A2P4
Disconnect 4 N/O Contact (SELogic)
89B2P4
Disconnect 4 N/C Contact (SELogic)
89A2P4D
Disconnect 4 Alarm Timer (seconds)
89A2P5
Disconnect 5 N/O Contact (SELogic)
Range = 0.00 to 999.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
20.00
0 0 0 0
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Select: IRIG1, IRIG2
IRIG1
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NOT 89A2P1
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Range = 0.00 to 300.00
5.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NOT 89A2P2
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Range = 0.00 to 300.00
5.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NOT 89A2P3
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Range = 0.00 to 300.00
5.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NOT 89A2P4
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Range = 0.00 to 300.00
5.00
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 4 of 10
89B2P5
Disconnect 5 N/C Contact (SELogic)
89A2P5D
Disconnect 5 Alarm Timer (seconds)
EN_LRC
Global
Enable Local Remote Control
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NOT 89A2P5
Select: Y, N
N
Range = 0.00 to 300.00
5.00
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
Top
03/02/2020
Page 5 of 10
Group 1
Top
Setting
Description
Range
TID
Terminal Identifier (16 characters)
Range = ASCII string with FEEDER RELAY a maximum length of 16.
CTRN
Neutral (IN) CT Ratio
RID
CTR PTR
DELTA_Y SINGLEV VNOM
Z1MAG Z1ANG
Z0MAG Z0ANG
Z0SMAG Z0SANG LL
EFLOC 50P1P
Relay Identifier (16 characters)
Phase (IA,IB,IC) CT Ratio PT Ratio
Transformer Connection Single Voltage Input
Line Voltage, Nominal Line-to-Line (volts)
Pos. Seq. Line Impedance Magnitude (ohms) Pos. Seq. Line Impedance Angle (degrees)
Zero Seq. Line Impedance Magnitude (ohms) Zero Seq. Line Impedance Angle (degrees)
Zero Seq. Source Impedance Magnitude (ohms) Zero Seq.Source Impedance Angle (degrees) Line Length - unitless
Enable Fault Location
Maximum Phase Overcurrent Trip Pickup (amps sec.)
50P1D
Maximum Phase Overcurrent Trip Delay (seconds)
50P1TC
Maximum Phase Overcurrent Torque Control (SELogic)
50P2P
Maximum Phase Overcurrent Trip Pickup (amps sec.)
50P3P
Maximum Phase Overcurrent Trip Pickup (amps sec.)
50P4P
Maximum Phase Overcurrent Trip Pickup (amps sec.)
50N1P
Neutral Overcurrent Trip Pickup (amps sec.)
50N2P
Neutral Overcurrent Trip Pickup (amps sec.)
50N3P
Neutral Overcurrent Trip Pickup (amps sec.)
50N4P
Neutral Overcurrent Trip Pickup (amps sec.)
50G1P
Residual Overcurrent Trip Pickup (amps sec.)
Value
Range = ASCII string with SEL-751 a maximum length of 16. Range = 1 to 5000
120
Range = 1.00 to 10000.00
180.00
Range = 1 to 5000
Select: WYE, DELTA Select: Y, N
Range = 20.00 to 250.00, OFF Range = 0.50 to 2550.00 Range = 5.00 to 90.00
Range = 0.50 to 2550.00 Range = 5.00 to 90.00
Range = 0.50 to 2550.00 Range = 0.00 to 90.00
Range = 0.10 to 999.00 Select: Y, N
Range = 0.05 to 20.00, OFF
Range = 0.00 to 400.00, OFF
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
120
DELTA N
120.00 10.70 68.86 31.90 72.47 1.80
84.61 4.84 N
5.00 0.05 1
Range = 0.05 to 20.00, OFF
OFF
Range = 0.05 to 20.00, OFF
OFF
Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF
Range = 0.00 to 400.00,
OFF
OFF OFF OFF OFF 7.50
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 6 of 10
50G1D
Residual Overcurrent Trip Delay (seconds)
50G1TC
Residual Overcurrent Torque Control (SELogic)
50G2P
Residual Overcurrent Trip Pickup (amps sec.)
50G3P
Residual Overcurrent Trip Pickup (amps sec.)
50G4P
Residual Overcurrent Trip Pickup (amps sec.)
50Q1P
Negative Sequence Overcurrent Trip Pickup (amps sec.)
50Q2P
Negative Sequence Overcurrent Trip Pickup (amps sec.)
50Q3P
Negative Sequence Overcurrent Trip Pickup (amps sec.)
50Q4P
Negative Sequence Overcurrent Trip Pickup (amps sec.)
51AC
TOC Curve Selection
51AP
51ATD 51ARS
51ACT
51AMR
Time Overcurrent Trip Pickup (amps sec.) TOC Time Dial
EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds)
51ATC
Phase Time Overcurrent Torque Control (SELogic)
51BP
Time Overcurrent Trip Pickup (amps sec.)
51BTD
TOC Time Dial
51BC
51BRS
51BCT
51BMR
TOC Curve Selection EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds)
51BTC
Phase Time Overcurrent Torque Control (SELogic)
51CP
Time Overcurrent Trip Pickup (amps sec.)
51CTD
TOC Time Dial
51CC
51CRS
51CCT
51CMR 51CTC
TOC Curve Selection EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds) Phase Time Overcurrent Torque Control (SELogic)
OFF
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.05 1
Range = 0.05 to 20.00, OFF
OFF
Range = 0.05 to 20.00, OFF
OFF
Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF Range = 0.05 to 20.00, OFF
OFF
OFF OFF OFF OFF
Range = 0.05 to 4.80, OFF 1.20 Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.50 to 15.00 Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
3.00 0.00 0.00 1
Range = 0.05 to 4.80, OFF 1.20 Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.50 to 15.00 Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
3.00 0.00 0.00 1
Range = 0.05 to 4.80, OFF 1.20 Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.50 to 15.00 Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
3.00 0.00 0.00 1
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 7 of 10
51P1P
Time Overcurrent Trip Pickup (amps sec.)
Range = 0.05 to 4.80, OFF 1.15
51P1TD
TOC Time Dial
Range = 0.50 to 15.00
51P1C
51P1RS
51P1CT
51P1MR 51P1TC 51P2P
51P2C
51P2TD 51P2RS
51P2CT
51P2MR 51P2TC 51QP
51QC
51QTD 51QRS
51QCT
51QMR 51QTC 51N1P 51N2P 51G1P
51G1C
51G1TD 51G1RS
51G1CT
51G1MR
TOC Curve Selection EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds)
Maximum Phase Time Overcurrent Torque Control (SELogic) Time Overcurrent Trip Pickup (amps sec.) TOC Curve Selection TOC Time Dial
EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds)
Maximum Phase Time Overcurrent Torque Control (SELogic) Time Overcurrent Trip Pickup (amps sec.) TOC Curve Selection TOC Time Dial
EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds)
Negative Seq. Time Overcurrent Torque Control (SELogic) Time Overcurrent Trip Pickup (amps sec.) Time Overcurrent Trip Pickup (amps sec.) Time Overcurrent Trip Pickup (amps sec.) TOC Curve Selection TOC Time Dial
EM Reset Delay
Constant Time Adder (seconds)
Minimum Response Time (seconds)
51G1TC
Ground Time Overcurrent Torque Control (SELogic)
51G2P
Time Overcurrent Trip Pickup (amps sec.)
EHBL5
Enable Fifth Harmonic Blocking
EHBL2 ELOAD E49IEC
Enable Second Harmonic Blocking Enable Load Encroachment
Enable IEC Thermal Element
Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.80 0.00 0.00 1
Range = 0.05 to 4.80, OFF 1.20 Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.50 to 15.00 Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
3.00 0.00 0.00 1
Range = 0.05 to 4.80, OFF 1.20 Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.50 to 15.00 Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
3.00 0.00 0.00 1
Range = 0.05 to 4.80, OFF OFF Range = 0.05 to 4.80, OFF OFF Range = 0.05 to 4.80, OFF 1.72 Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
U3
Select: Y, N
N
Range = 0.50 to 15.00 Range = 0.00 to 1.00 Range = 0.00 to 1.00
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.80 0.00 0.00 1
Range = 0.05 to 4.80, OFF OFF Select: Y, N
N
Select: Y, N
N
Select: Y, N Range = 1 to 3, N
N N
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 8 of 10
27PP1P
Phase-Phase Undervoltage Trip Level (volts)
27PP2P
Phase-Phase Undervoltage Trip Level (volts)
E27I2
Inverse Time Undervoltage Element Enable
E27I1
59Q1P
Inverse Time Undervoltage Element Enable
Negative-Seq Overvoltage Trip 1 Pickup (volts)
59PP1P
Phase-Phase Overvoltage Trip Level (volts)
59Q2P
Negative-Seq Overvoltage Trip 2 Pickup (volts)
59PP2P
Phase-Phase Overvoltage Trip Level (volts)
E59I2
Inverse Time Overvoltage Element Enable
E59I1 E59I3 E59I4
Inverse Time Overvoltage Element Enable Inverse Time Overvoltage Element Enable Inverse Time Overvoltage Element Enable
LOPBLK
Loss of Potential Block Condition Equation (SELogic)
55LGTP
Power Factor Lag Trip Pickup
55LGAP
Power Factor Lag Alarm Pickup
55LDTP
55LDAP E78VS
81D1TP
Power Factor Lead Trip Pickup
Power Factor Lead Alarm Pickup Enable Vector Shift
Frequency1 Trip Pickup (Hz)
81D2TP
Frequency2 Trip Pickup (Hz)
81D3TP
Frequency3 Trip Pickup (Hz)
81D4TP
Frequency4 Trip Pickup (Hz)
81D5TP
Frequency5 Trip Pickup (Hz)
81D6TP
Frequency6 Trip Pickup (Hz)
E81RF
Enable Fast Rate-of-Change of Frequency Elements
E81R
EDEM
DMTC
PHDEMP
GNDEMP 3I2DEMP EPWR
TDURD
Enable Rate-of-Change of Frequency Elements Demand Metering
Time Constant (mins)
Phase Pickup (amps sec.)
Residual Ground Pickup (amps sec.)
Negative-Sequence Pickup (amps sec.) Enable Three Phase Power Elements Minimum Trip Time (seconds)
Range = 2.00 to 300.00, OFF
OFF
Select: Y, N
N
Range = 2.00 to 300.00, OFF Select: Y, N
Range = 2.00 to 300.00, OFF Range = 2.00 to 300.00, OFF Range = 2.00 to 300.00, OFF Range = 2.00 to 300.00, OFF Select: Y, N Select: Y, N Select: Y, N Select: Y, N
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
OFF N
OFF OFF OFF OFF N N N N 0
Range = 0.05 to 0.99, OFF OFF Range = 0.05 to 0.99, OFF OFF Range = 0.05 to 0.99, OFF OFF Range = 0.05 to 0.99, OFF OFF Select: Y, N
N
Range = 15.00 to 70.00, OFF
OFF
Range = 15.00 to 70.00, OFF Range = 15.00 to 70.00, OFF Range = 15.00 to 70.00, OFF Range = 15.00 to 70.00, OFF Range = 15.00 to 70.00, OFF Select: N, 1-4 Select: Y, N
Select: THM, ROL
Select: 5, 10, 15, 30, 60
OFF
OFF OFF OFF OFF N N
THM 5
Range = 0.10 to 3.20, OFF 1.00 Range = 0.10 to 3.20, OFF 0.20 Range = 0.10 to 3.20, OFF 0.20 Select: N, 3P1, 3P2
Range = 0.0 to 400.0
N
0.5
file:///C:/Users/User/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00/TempR...
03/02/2020
Page 9 of 10
CFD
Close Failure Time Delay (seconds)
Range = 0.0 to 400.0, OFF 1.0
TR
Trip (SELogic)
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
REMTRIP
Remote Trip (SELogic)
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
ULTRIP
Unlatch Trip (SELogic)
52A
Breaker Status N/O Contact (SELogic)
52B
Breaker Status N/C Contact (SELogic)
CL
Close (SELogic)
ULCL
Unlatch Close (SELogic)
Group 1
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
ORED50T OR ORED51T OR ORED81T OR REMTRIP OR OC OR SV04T 0 NOT (51P1P OR 51G1P OR 51N1P OR 52A) 0
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NOT 52A
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
SV03T AND LT02 OR CC