5 0 219 KB
Daya Teg Ib
Trafo Pelanggan Daya 2250 KVA Teg 20 KV Ib 64.95191 A
2180 KVA 20 KV 62.93118 A
CT
80 Measurment
5A Measurement 1 (Pengukuran)
Primary Values Secondary Values
Measurement 2
Primary Values Secondary Values Primary Power Secondary Power
Synchrocheck
Status
Input
Output Superv State Records
Distrub Record
Superv Event
I0 Events
Device Logs
Settings
ENT
ENT
ENT
ENT
Maka akan tampil :
Maka akan Tampil :
Maka akan tampil :
Maka akan tampil :
Control Logs
ENT
Maka akan tampil :
Clear Record
ENT V
Maka akan tampil :
System settings
ENT V
Maka akan tampil :
Prot Setting
OC Settings
NegOC Settings
EF1 (Ground Fault)
BFP Settings BroknCond Settings SOFT Settings
ThOvLd Settings SETTING OVERLOAD
Volt Prot Settings NegOV Settings ROV Settings Frequency Prot Settings AR Settings Superv Setting CfgB0 Settings Line Settings Copy Settings
CURVE
Power
Trip
Arus
110 DC + 3 5 2 4
Close
R S T
29 31 33 30 32 34 35
Jamper
Password P4 P3 G4 G3 ORL
Pungujian GFR Netral No 36
+ Panah Kiri, Panah Atas, OCR OCR Moment GFR GFR Moment 49
Setting Primer dibagi Ratio CT Contoh
6 8
Setting CT
18 A 10
Setting di Relay
Primary Values
ENT
Secondary Values
ENT
Primary Values
ENT
Secondary Values
ENT
Primary Power
ENT
Secondary Power
ENT
Synchrocheck
ENT
5A 9
Maka akan tampil : Ia Ib Ic I1 I2 3I0_Cal 3I0_Ext1 Ua Ub Uc Uab Ubc Uca U1 U2 3U0_Cal Ux f ThermalState_PhA ThermalState_PhB ThermalState_PhC
0A 0A 0A 0A 0A 0A 0A 0V 0V 0V 0V 0V 0V 0V 0V 0V 0V 0 Hz 0% 0% 0%
Maka akan tampil : P Q COS PHr+ QHr+ PHrQHr-
0 kW 0 kVAr 0% 0 MWh 0 MVAh 0 MWh 0 MVAh
Maka akan tampil : 25A.U_Dif 25A.phi_Dif 25A.f_Dif
0V 0 deg 0 Hz
Arus Phasa R Arus Phasa S Arus Phasa T Arus Posotif Sequence Arus Negatif Sequence Arus Netral
Accumulasi Thermal Accumulasi Thermal Accumulasi Thermal
Power Factor
Maka akan tampil :
Data dari relay yang terganggu seperti : 1. Jenis Relay yang bekerja (misalnya OCR/OCRM/dll) 2. Phasa yang terganggu 3. Besaran Arus dari masing masing phasa R,S,T 4. Waktu Kejadian Gangguan (Tanggal dan Jam) 5. No Gangguan 6. dll
Maka akan Tampil :
Data dari relay yang mengalami gangguan supervisi seperti : 1. Fail device 2. Fail setting 3. dll
Maka akan tampil :
Data dari relay yang mengalami Status Input seperti : 1. Reclaim time 2. 52a 3. 52b 4. dll
Maka akan tampil :
Data Reboot Relay
Maka akan tampil :
Data Relay yang mendapat comand control.
Maka akan tampil :
Menu untuk menghapus semua catatan yang tersimpan pada relay Tekan
Tekan
Maka akan tampil :
: untuk menghapus.
ENT
: untuk keluar.
ESC
Active grup
1
Opt_SysFreq PrimaryEquip
50 Hz -
: Untuk memilih grup : Untuk memilih frequncy : equipment
Prot.I1n
80 A
Prot.I2n
5A
Nue1.I1n
80 A
: CT Primary : CT Secundary : ZCT Primary
Neu1.I2n
5A
Prot.U1n
20 kV
Prot.U2n Syn.U1n
OC Settings
100 V 20 kV
Syn.U2n
100 V
Opt_3I0
1
ENT V
: ZCT Secundary : VT Primary : VT Secundary : VT Primary : VT Secundary : Untuk perhitungan arus netral
Maka akan tampil : Pilihan Untuk Grup yang ingin di setting Active Grup
: 01
Selected Grup
: 01
ENT V
NegOC Settings
EF1 (Ground Fault)
ENT V ENT V
Tidak disetting.
Maka akan tampil : Pilihan Untuk Grup yang ingin di setting Active Grup
: 01
Selected Grup
: 01
ENT V
BFP Settings BroknCond Settings SOFT Settings
ThOvLd Settings
ENT V ENT V
Tidak disetting. Tidak disetting.
ENT V
Tidak disetting.
ENT V
Maka akan tampil : Pilihan Untuk Grup yang ingin di setting
SETTING OVERLOAD
Volt Prot Settings NegOV Settings ROV Settings Frequency Prot Settings AR Settings
ENT V
Active Grup
: 01
Selected Grup
: 01
Tidak disetting.
ENT V
Tidak disetting.
ENT V
Tidak disetting.
ENT V ENT V
Tidak disetting. Tidak disetting.
Superv Setting
ENT V
Tidak disetting.
CfgB0 Settings
ENT V
Tidak disetting.
Line Settings
ENT V
Tidak disetting.
Copy Settings
ENT V
Tidak disetting.
ENT V
PENGUJIAN RELAY ID Pel Nama Alamat Daya Tarip
I > OCR Curve Delay (ms)
7.08 1 0.05
I >> OCR M Curve Delay
28 0 0
80 5 CT Terpasang A Ib 63 Merk Relay Trafo Pel 2250 KVA Type A In Trafo 65 SN PEMERIKSAAN WAKTU KERJA RELAY OVERLOAD
1.05 Iset 1.2 Iset 1.5 Iset 4 Iset
Kriteria Waktu TDL 2003 > 3600 < 1200 < 600 di koordinasikan
NR
PCS-9691
1.05 xI set 1.2 xI set 1.5 xI set 4 xI set
PEMERIKSAAN WAKTU KERJA RELAY OCR/GFR OVER CURRENT
Pengujian
MENURUT RUMUS Arus di Arus Relay Injek Waktu Trip (detik) (Ampere) (Ampere)
M Arus (Ampere) R-S
43.2
1.5 Iset 2 Iset 3 Iset 4 Iset
169.91 226.55 339.83 453.10
10.62 14.16 21.24 28.32
0.860 0.501 0.315 0.249
GROUND FAULT
Pengujian Arus Phasa R Arus Phasa S Arus Phasa T Arus Posotif Sequence Arus Negatif Sequence Arus Netral
Accumulasi Thermal Accumulasi Thermal Accumulasi Thermal
Power Factor
1.5 Iset 2 Iset 3 Iset 4 Iset
MENURUT RUMUS Arus di Arus Relay Injek Waktu Trip (detik) (Ampere) (Ampere) 1.22 19.49 0.860 1.62 25.98 0.501 2.44 38.97 0.315 3.25 51.96 0.249
M Arus (Ampere) R-N
Untuk OCR pilih 50/51P4 50/51P4.I_set
7.08 A
Arus setting
50/51P4.t_Op
0
50/51P4.En_VCE
0
50/51P4.Opt_Dir
0
50/51P4.En_Hm_Blk
0
50/51P4.En
1
Pilih ''1'' Untuk Enable atau ''0'' Untuk Disable
50/51P4.OutMap
1
pilih output BO_01 untuk Trip.
50/51P4.Opt_Curve
1
Pilih ''1'' Untuk standar inverse
Diabaikan Karena hanya untuk setting deffinite
50/51P4.TMS
0.05
Setting Waktu Curva TD
50/51P4.tmin
0.02
Default
50/51P4.K
0.14
Default
50/51P4.C
0
Default
0.02
Default
50/51P4.Alpha
Untuk OCR MOMEN pilih 50/51P3 50/51P3.I_Set
28.32 A
50/51P3.t_Op
0s
50/51P3.En_VCE
0
50/51P3.Opt_Dir
0
Arus setting Waktu
50/51P3.En_Hm_Blk
0
50/51P3.En
1
Pilih ''1'' Untuk Enable atau ''0'' Untuk Disable
50/51P3.OutMap
1
pilih output BO_01 untuk Trip.
Untuk EFR pilih 50/51G4 50/51G4.3I0_Set
0.81 A
50/51G4.t_Op
Arus setting Diabaikan Karena hanya untuk setting deffinite
50/51G4.Opt_Dir
0
Directional tdk boleh diaktifkan
50/51G4.En_Hm_Blk
0
50/51G4.En
1
Pilih ''1'' Untuk Enable atau ''0'' Untuk Disable
50/51G4.OutMap
1
pilih output BO_01 untuk Trip.
50/51G4.Opt_Curve
1
Pilih ''1'' Untuk standar inverse
50/51G4.TMS
0.05
Setting Waktu Curva TD
50/51G4.tmin
0.02
Default
50/51G4.K
0.14
Default
50/51G4.C
0
Default
0.02
Default
50/51G4.Alpha
Untuk EFR MOMEN pilih 50/51G3 50/51G3.3I0_Set
3.25 A
Arus setting
50/51G3.t_Op
0s
Waktu
50/51G3.Opt_Dir
0
50/51G3.En_Hm_Blk
0
50/51G3.En
1
Pilih ''1'' Untuk Enable atau ''0'' Untuk Disable
50/51G3.OutMap
1
pilih output BO_01 untuk Trip.
49.Ib_Set
4.13 A
Arus
49.Tau
820 s
Waktu
49.C_Disspt
5
Default
49.K_Trp
1
Default
49.K_Alm
0.8
Default
49.En_Trp
1
Pilih ''1'' Untuk Enable atau ''0'' Untuk Disable
49.En_Alm
1
Pilih ''1'' Untuk Enable atau ''0'' Untuk Disable
49.OutMap
1
pilih output BO_01 untuk Trip.
GUJIAN RELAY Io > GFR Curve Delay
0.8 1 0.05
Io >> GFR M Curve Delay
3.2 0 0
NR
PCS-9691
49 RMS SETTING OVER LOAD 49.Ib_Set 3.42 Arus 49.Tau 820 s 49.C_Disspt 5 Default 49.K_Trp 1 Default 49.K_Alm 0.8 Default 49.En_Trp 1 49.En_Alm 1 49.OutMap 1
HASIL PENGUJIAN Arus di Relay (A) 66.08 75.52 94.40 251.72
Arus Injek (Ampere) 4.13 4.72 5.90 15.73
Arus Uji (Ampere)
6.22
waktu trip (detik)
529
MENURUT ALAT UJI Arus (Ampere) Waktu Trip (Detik) R-T
S-T
R-S
R-T
S-T
11.35 15.01 22.32 30.28
0.899 0.533 0.344 0.076
MENURUT ALAT UJI Arus (Ampere) Waktu Trip (Detik) S-N
T-N
R-N
S-N
T-N
Depok, Penguji
(.......................................................)