Trane Chiller Data Sheet CVHG [PDF]

  • 0 0 0
  • Suka dengan makalah ini dan mengunduhnya? Anda bisa menerbitkan file PDF Anda sendiri secara online secara gratis dalam beberapa menit saja! Sign Up
File loading please wait...
Citation preview

CCTV Job Information Job01 TIG



Tag



CCTV-1



Quantity



1



Model Number



CVHG0565



Outside the scope of AHRI Standard 550/590.



Sound pressure measured in accordance with AHRI Standard 575-94.



Unit Information Model



TCVHG



Compressor size



565



Impeller size



277



Orifice size



710



Motor size



381



Motor frequency



50 Hz



Motor voltage



415



Incoming line frequency



50 Hz



Incoming line voltage



415



Evap shell size



050L



Cond shell size



080L



Evap bundle size



700



Cond bundle size



710



Evap tube type



IECU



Cond tube type



IECU



Evap tube thickness



0.025"



Cond tube thickness



0.028"



Evap passes



Two pass evap water box



Cond passes



Two pass cond water box



Primary cooling capacity



635.0 tons



HCFC-123 refrigerant charge



454 kg



Primary power



368.0 kW 0.579 kW/ton



Shipping weight



9217 kg



Operating weight



10643 kg



Remote Mounted WyeD



Control Power Voltage



1.84 kW



Application type



Standard cooling



Free cooling option



No



10.0 C



Evap pressure drop



23.9 kPa water



Evaporator entering fluid temp



191.8 m3/hr 20.0 C



Evap fluid type Evaporator fluid concentration



Evaporator fluid flow/capacity



0.0239 L/s/kW



Evap water box type



N/A non-marine



Evaporator fouling factor



0.017610 m2-deg C/kW



Evap water box pressure



150 psig



Condenser entering fluid temp



35.0 C



Cond pressure drop



68.4 kPa



Condenser fluid flow rate



Cond fluid type



water



Condenser leaving fluid temp



453.2 m3/hr 40.0 C



Condenser fluid concentration



Condenser fluid flow/capacity



0.0564 L/s/kW



Cond water box type



N/A non-marine



Condenser fouling factor



0.044025 m2-deg C/kW



Cond water box pressure



150 psig



2880 A



Compressor motor RLA



581.00 A



582.4 A 0.90



Min circuit ampacity



736 A



Design Information



Primary efficiency TWye-delta starter Chiller heat rejected to ambient



Evaporator Information



Evaporator leaving fluid temp Evaporator fluid flow rate



Condenser Information



Electrical Information Motor LRA Primary RLA (Incoming line) Un-corrected power factor



2015/7/16



Product Version



Selection code revision level



Max overcurrent protection



31.8.0.0 10062.00 Each



M0C0E000C100S10



Page 1 of 2



CCTV Job Information Job01 TIG



Tag



CCTV-1



Quantity



1



Model Number



CVHG0565



Information for LEED Projects Primary cooling capacity



635.00 tons



Primary power



368.00 kW



HCFC-123 refrigerant charge



453.59 kg



NPLV



0.467 kW/ton



Note:



Although Trane recognizes and respects the decision by the U.S. Green Building Council to mandate a default assumption of a 2% Refrigerant Leakage Rate (Lr) for all manufacturers of centrifugal chillers, the value used in the calculations for achieving Energy and Atmosphere Credit 4 of LEED-NC (version 2.2), Trane has exhaustively documented and guarantees a low 0.5% leak rate for HCFC-123 CenTraVac centrifugal chillers (models CVHE, CVHF, and CVHG). This documented 0.5% refrigerant leakage rate, as well as our average 1.7 Lb/Ton refrigerant charge, are just some examples of Trane's commitment to safeguarding the environment.



The LEED Green Building Rating Systemâ„¢, developed by the U.S. Green Building Council, provides independent, third-party verification that a building project meets the highest green building and performance measures.



2015/7/16



Product Version



Selection code revision level



31.8.0.0 10062.00 Each



M0C0E000C100S10