Capillary Tube Sizing Suggested Capillary Tube Data for Domestic and Commercial Refrigeration Applications The following suggestions listed in Table A-1 and the correction factors listed in Table A-2. assume a 115°F (46°C) liquid temperature, no subcooling prior to the heat exchanger, and 3 ft (91cm) of heat exchange with the suction line. Example No. 1 Select the capillary required for a Tecumseh R-22 compressor model AEA5460EXA rated at 6,000 Btu/h at 45°F (7°C) evaporator. From Table A-1, we find 13 ft (396cm) length of 0.064 in capillary tube. Example No. 2 Select the capillary required for a Tecumseh R-134a compressor model AJA7461YXA rated at 6,110 Btu/h at 20°F (-6,5°C) evaporator. From Table A-1, we find 9 ft (274cm) length of 0.052 in capillarytube, 2 required piped in parallel.
Conversi: 1 ft (kaki) = 30,48 cm (Centimeter) = 12 in (inch) Dari Fahrenheit ke Celcius : [°C] = ( [°F] – 32 ) X 5/9 -10°F = -23°C 20°F = -6,5°C 45°F = 7°C 115°F = 46°C
Dari Celcius ke Fahrenheit : [°F] = [°C] X 9/5 + 32