Inverter DJN1000-S V100R001



User Manual



Issue



04



Date



2013-09-12



HUAWEI TECHNOLOGIES CO., LTD.



Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.



Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.



Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute the warranty of any kind, express or implied.



Huawei Technologies Co., Ltd. Address:



Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China



Website:



http://www.huawei.com



Email:



[email protected]



Issue 04 (2013-09-12)



Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd



i



Inverter DJN1000-S User Manual



About This Document



About This Document Purpose This document describes the inverter DJN1000-S This document provides guides to get the information about how to construct a network.



Intended Audience This document is intended for: 



Installation and commissioning engineers







Technical support engineers



Symbol Conventions The symbols that may be found in this document are defined as follows. Symbol



Description Alerts you to a high risk hazard that could, if not avoided, result in serious injury or death. Alerts you to a medium or low risk hazard that could, if not avoided, result in moderate or minor injury. Alerts you to a potentially hazardous situation that could, if not avoided, result in equipment damage, data loss, performance deterioration, or unanticipated results. Provides a tip that may help you solve a problem or save time. Provides additional information to emphasize or supplement important points in the main text.



Issue 04 (2013-09-12)



Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd



ii



Inverter DJN1000-S User Manual



About This Document



Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues.



Issue 04 (2013-09-12) Change the input frequency and the input frequency.



Issue 03 (2013-05-07) Low wrong revision.



Issue 02 (2012-12-25) Update the security cordon.



Issue 01 (2011-10-11) This issue is used for first office application (FOA).



Issue 04 (2013-09-12)



Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd



iii



Inverter DJN1000-S User Manual



Contents



Contents About This Document .................................................................................................................... ii 1 Summary ........................................................................................................................................ 1 1.1 Products Characteristics ................................................................................................................................... 1 1.2 Technical Specification .................................................................................................................................... 2 1.3 Basic Principles and Structure .......................................................................................................................... 5 1.3.1 Stand-alone Principle .............................................................................................................................. 5 1.3.2 Structure .................................................................................................................................................. 6



2 Installation...................................................................................................................................... 8 2.1 Installation Notice ............................................................................................................................................ 8 2.2 Power Examination .......................................................................................................................................... 9 2.2.1 Base requirements to mains supply ......................................................................................................... 9 2.3 Electric Connection ........................................................................................................................................ 10 2.3.1 Notice .................................................................................................................................................... 10 2.3.2 Cable Wiring ......................................................................................................................................... 11 2.3.3 Grounding ............................................................................................................................................. 11 2.4 System Examination and Test ........................................................................................................................ 11 2.4.1 Electric Connection Examination ......................................................................................................... 11 2.4.2 Inverter Test .......................................................................................................................................... 12 2.5 Load Connection ............................................................................................................................................ 12



3 Usage.............................................................................................................................................. 13 3.1 Notice ............................................................................................................................................................. 13 3.2 Startup Preparation ......................................................................................................................................... 13 3.3 Operation ........................................................................................................................................................ 14 3.3.1 Daily startup and shutdown ................................................................................................................... 14 3.3.2 Operation .............................................................................................................................................. 14



4 Maintenance Guard ................................................................................................................... 15 4.1 Safety Precaution ........................................................................................................................................... 15 4.2 Periodic Preventative Maintenance ................................................................................................................ 15 4.3 Frequent Abnormal Diagnose ......................................................................................................................... 15



A Acronyms and Abbreviations .................................................................................................. 17



Issue 04 (2013-09-12)



Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd



iv



Inverter DJN1000-S User Manual



1 Summary



1



Summary



1.1 Products Characteristics KELONG® DJN1000-S inverter powers of sine wave for communication accord with ISO IEC146-4, GB7260, maintenance regulations of MINPTT, certification and examination details of network admittance quality of the inverter equipment for communication, and can be inverter power supplies in the environments such as post telephone and telegraph, railway, marine etc. and AC uninterrupted power supplies for that such as Chinese teletex facility, telegraph terminals, wireless call facility, data switching exchange, local exchange, microwave communication facility, charging system for the cell type exchange, facsimile apparatus for character and image, kinds of AC instruments and computers etc. DJN1000-S inverter powers, being able to supply high-performance uninterrupted AC power for various precision instruments, have mainly the following characteristics and functions: 



Adopting rack imbed design so as to be more slinky and tide.







Guard of input polarity opposition −







Normal startup −







Issue 04 (2013-09-12)



The inverter will send out alarm noise every 0.5 seconds but continue normal power supply to loads as the input voltage above the over-voltage alarm point. When the DC input voltage is higher than the over-voltage protection point, the inverter will shut down automatically for protection with no output.



Communication −







The inverter will send out alarm noises every 0.5 seconds but continue normal power supply to loads as the DC voltage below the low-voltage alarm point. When the DC input voltage is lower than the low-voltage protection point, the inverter will stop inversion, sending out long alarm noise and highlight the BATH/L indicator on the panel, so as to avoid the damage to the DC power resulting from low-DC-voltage.



Over-voltage alarm and protection for DC input −







The inverter will supply normal voltage in 5s–20s after the on/off key on the panel pressed if the DC input voltage is in the required range for the normal startup.



Low-voltage alarm and protection for DC input −







When DC input polarity terminals reversely connected, the inverter would not work but not be destroyed.



The inverter offers dry connector. Through the dry connector, the work status can be monitored.



Self-startup when input voltage resumes to normal



Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd



1



Inverter DJN1000-S User Manual



1 Summary −







Over-voltage protection for output −







The inverter will stop inversion and send out continuous sound-light alarm if the load undergoes short circuit. Restart the inverter manually once the trouble is eliminated.



Bypass auto-lock −







The inverter will stop inversion and turn to bypass output, sending out sound-light alarm as overload for period of time. Once the load resume to normal, the inverter will turn to inversion output automatically. The overload protection drop is about 10%.



Short circuit protection for AC output −







When the temperature of the main radiator goes beyond the over-temperature protection point the inverter will stop inversion and turn to bypass output, sending sound-light alarm. The temperature drop is about 20°C.



Overload protection −







The inverter will stop inversion and turn to bypass output, sending out sound-light alarm as the output voltage below the low-voltage protection point. Restart manually the inverter once the trouble is eliminated.



Over-temperature protection −







The inverter will stop inversion and turn to bypass output, sending out sound-light alarm as the output voltage above the over-voltage protection point. Restart manually the inverter once the trouble is eliminated.



Low-voltage protection for output −







The DC input voltage out of normal startup range will results in self-shutdown of the inverter, bypass output and sound-light alarm. When the voltage recovers, the inverter will restart automatically.



To avoid frequent conversion, the inverter will be auto-locked to bypass output with continuous sound-light alarm when the inverter switches to bypass output 3 times continuously in 5 minutes. Restart manually the inverter once the trouble is eliminated.



AC input abnormal status alarm −



If Li, Ni reversely connected, the buzzer will alarm intermittently.



1.2 Technical Specification Table 1-1 Technical Specification of DJN1000-S Item



Specification and Parameter



Model NO.



DJN1000-S



Rated Output Capacity



1000 VA/700 W



AC Input



AC input



220 V AC



Frequency



55-65 Hz



ECO AC input range



(195–265 V AC)±10 V AC



BYPASS range



220 V AC±30%



Frequency range



(45–55 Hz)±0.5 Hz



Issue 04 (2013-09-12)



Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd



2



Inverter DJN1000-S User Manual



1 Summary



Item DC Input



AC output



Specification and Parameter Rated voltage



48 V DC



Rated current



18 A



DC Input range



(40–57 V DC)±1V DC



Start input max impact current



Less than 150% rated current



DC Input range of normal start



(42–56)±1 V DC



Low voltage alarm of DC input



44.0±1 V DC



High voltage alarm of DC input



58±2 V DC



Low voltage protection of DC input



40.0±1 V DC



Over voltage protect of DC input



60±2 V DC



Input terminal reverse comparable broad range static current