X-Log Quick Guide Updated 9 October 2015



Cod. INSTUM_01519_en



LSI LASTEM X-Log – Quick Guide



Summary 1. 2. 3. 4. 5.



Introduction .................................................................................................................................. 3 What’s inside X-LOG package .................................................................................................... 3 First start-up ................................................................................................................................. 3 Interface with the datalogger........................................................................................................ 5 Sensors connection ....................................................................................................................... 6 5.1. LSI LASTEM sensors: configuration and wiring ................................................................ 6 6. Get data from X-LOG ................................................................................................................ 12 7. X-Storage ................................................................................................................................... 13 7.1. Activation form .................................................................................................................. 14



2



LSI LASTEM X-Log – Quick Guide



1. Introduction This document is a short introduction to the first use of the X-Log data logger. We suggest you to download the latest version of this guide on X-Log section on the LSI LASTEM web site.



2. What’s inside X-LOG package   



N.1 X-LOG unit N.1 Ethernet cable N.1 USB key



3. First start-up Before connecting data logger to sensors verify that the power switch is on the "0" position (off). Connect the data logger power using the proper connector, utilizing a battery (12 Vdc, min 1 Ah) or an external 230 Vac/12 Vdc power supply according to the following method:  



If you are using only the battery or only the external power supply, connect the terminals to inputs +12Batt and Gnd. If you are using an external power supply and a battery, connect the battery terminals to the +12Batt and Gnd inputs and connect the power supply to the InPS and Gnd inputs. In this configuration the battery is automatically recharged (max 40 Ah) by the data logger, therefore the power supply must have an output of at least 13.5 Vdc.



3



LSI LASTEM X-Log – Quick Guide



Power supply connector Name +12 Bat Gnd In.P.S. +12 out



Function Battery power (+10.5 Vdc ÷ 15 Vdc) Ground terminal block (3 terminals) Power supply input from solar panel or 230 / 13.5 Vdc power supply Auxiliary power output (max 3 A)



Status LED Name Chrg ON Pwr ON R Boot G Boot



Color Red Red Red Green



Function Battery change LED Power LED Boot anomaly indicator LED Boot anomaly indicator LED



Move the power switch to the "1" position (On). A display message will appear with some machine start up and diagnostics information. The first message represents the product serial number. Wait about 90 seconds until the instant data appear in the following format:



* To decode see X-LOG user guide. The readings are shown for about 2 seconds each, passing from one reading to the next based in the machine configuration.



4



LSI LASTEM X-Log – Quick Guide



4. Interface with the datalogger The data logger can be connected to a PC via the 10/100Mbit/s LAN interface. X-Log comes from the factory with a pre-configured IP address necessary for connection; change it according to your LAN configuration. LAN Interface IP: 192.168.1.110



Subnet mask:



255.255.255.0



To connect with the machine you will need to utilize an Ethernet cross cable following the procedure below:



   



Turn on the data logger. Connect the cable to your computer's LAN port. Connect the other end of the cable to the X-Log LAN port. Turn on the computer and set an IP address for your network card which is congruent with the data logger's address. For example 192.168.1.255 and subnet mask 255.255.255.0.



At this point the connection between the computer and the X-Log has been established and you can proceed to the configuration page or the data viewing page as explained in the next paragraph. The main configuration procedure of X-Log can be done only using a web browser. WARNING To correctly view the pages on the PC browser, enable JavaScript and the option to search for the most recent version of the cached pages in the tools or options menu of your browser. With the browser open, enter the IP address of the datalogger in the address bar: http://192.168.1.110 (factory default address) and wait for the first page to open which allows the user to choose between instant data view or configuration (password protected).



5



LSI LASTEM X-Log – Quick Guide



5. Sensors connection There are two interfaces type from sensors to X-Log: a) Using XLA010 interface connector. b) Using XLA009-015-017 sensor protection boards. Each sensors type needs a specific configuration and has to be connected to the X-Log terminals in accordance to the electrical signals it generates. The next section gives some connection instruction for the most used LSI LASTEM sensors.



5.1.



LSI LASTEM sensors: configuration and wiring



Sensor Model



X-Log configuration



Connection using XLA009-015-017



Temperature and relative humidity DMA672.1 Temperature Parameter Value Measure name Temperature Type Temperature Linearization algorithm M0 Min -30 Max 70 Decimals 1 Inst. data 60 Relative humidity Parameter Value Measure name Humidity Type Volt/mA Linearization algorithm (M0/1000000)*100 Min 0 Max 100 Decimals 0 Inst. data 60 Temperature Terminal Wire color 1 Black 2 Violet 3 Yellow 4 Orange 5 6 Relative humidity Terminal Wire color 1 2 White 3 Cable screen 4 Grey 5 6 Green



6



LSI LASTEM X-Log – Quick Guide



Sensor Model



X-Log configuration



Wind speed and direction DNA121 Wind direction Value WindDir Volt/mA (M0/1000000)*360*(M00) 0 60 1 2 Wind direction Wire color



Parameter Measure name Type Linearization algorithm Min Max Decimals Inst. data Parameter Measure name Type Linearization algorithm Min Max Decimals Inst. data



Connection using XLA009-015-017



Terminal 1 2 3 4 5 6



Red Yellow, bridge to terminal 4 Bridge to terminal 3 White Wind speed Wire color



Terminal 1 2 3 4 5 6



Sensor Model



X-Log configuration



Bridge to terminal 6 Black Blue Brown by a 1 kΩ resistor, bridged to terminal 2



Wind speed and direction DNA821 Wind direction Value WindDir Volt/mA ((M0-400000)/1600000)*360 The next algorithm can be used alternatively (implements limits and hysteresis control): (M0399999)*(M02000000)* 360+(M0>2008000)*720



Parameter Measure name Type Linearization algorithm



7



LSI LASTEM X-Log – Quick Guide Min Max Decimals Inst. data



0 360 0 2 Wind speed Value WindSpeed Volt/mA ((M0-400000)/1600000)*60 The next algorithm can be used alternatively (implements limits and hysteresis control): (M0399999)*(M02000000)* 70+(M0>2008000)*140 0 60 1 2 Wind direction Wire color



Parameter Measure name Type Linearization algorithm



Min Max Decimals Inst. data



Connection using XLA009-015-017



Terminal 1 2 3 4 5 6



Red, 100 Ω resistor to terminal 3 Bridge to terminal 4 Screen, bridge to terminal 3



Wind speed Wire color



Terminal 1 2 3 4 5 6



Sensor Model



X-Log configuration



Connection using XLA009-015-017



Black, 100 Ω resistor to terminal 3 Blue White Brown



Wind speed DNA301 Parameter Measure name Type Linearization algorithm Min Max Decimals Inst. data Terminal 1 2 3 4



Value WindSpeed Freq. (0.1607898185 + 0.0690042855*M0)*(M0>0) 0 60 1 2 Wire color Bridge to terminal 6 Black Blue 8



LSI LASTEM X-Log – Quick Guide 5 6



Sensor Model



X-Log configuration



Connection using XLA009-015-017



Sensor Model



X-Log configuration



Connection using XLA009-015-017



Sensor Model



X-Log configuration



Brown by a 1 kΩ resistor, bridged to terminal 2



Wind direction DNA310 Parameter Measure name Type Linearization algorithm Min Max Decimals Inst. data Terminal 1 2 3 4 5 6



Value WindDir Volt/mA (M0/1000000)*360*(M00) (*) 0 1500 0 10 Wire color Brown Blue, bridge to terminal 4 Cable screen, bridge to terminal 3



(*) Calibration factor has to be expressed in the formula in µV/W/m2 units; “*(M0>0)” formula part cuts off values less than zero; remove it from the formula when nightly negative values are needed.



Sensor Model



X-Log configuration



Sunshine duration and direct radiation DPD504 Direct radiation Parameter Value Measure name DirectRad Type Volt/mA Linearization algorithm ((M0-60000)/240000)*1500 Min 0 Max 1500 Decimals 0 Inst. data 60 Sunshine duration Parameter Value Measure name SunshineDuration Type Linearization algorithm M0>1250000 Min 0 Max 60 Decimals 0 10



LSI LASTEM X-Log – Quick Guide Inst. data



Connection using XLA009-015-017



60 Direct radiation Wire color



Terminal 1 2 3 4 5 6



Black Blue White Brown Sunshine duration Wire color TBD



Terminal 1 2 3 4 5 6



11



LSI LASTEM X-Log – Quick Guide



6. Get data from X-LOG X-LOG dataloggers series sample, process and store/transmit data according to the configuration settings. X-Log stores data files in text format ("*.txt") inside an internal back-up area of about 32 MB. Besides this area, files are stored in an industrial type external USB storage device connected to one of the two USB ports of the machine; X-Log supports 512 MB to 4 GB USB memory sticks. If a GPRS communication terminal is connected to the X-LOG, a copy of the data is sent via FTP protocol to a predisposed internet area. In other words, there are always at least 2 or 3 (in case of GPRS) areas where all of the historical data acquired can be found. LSI LASTEM provides a program (compatible with Internet Explorer only), which allows the historical data files to be downloaded and converted from ASCII into Excel® format for immediate processing and interpretation. Besides the conversion, this application allows a backup to be made of the data, dividing it by switchboard ID, year and month. This application, called X-COM, can be downloaded using LSI WebInstaller program from our web site http://www.lsilastem.com/Download-Software.aspx



12



LSI LASTEM X-Log – Quick Guide



7. X-Storage X-Storage is a web service provided by LSI LASTEM for X-Log users. There is no cost for the service, only a charge for its configuration. X-Storage received the data measured by X-Log whenever one of the three FTP sites programmed (read part 3.3 of the X-Log user’s manual) is programmed as LSI FTP site. X-Storage web software features:   



Current weather station data display in a real-time on the computer. Production of charts using archived weather data on an hourly, daily, weekly, monthly basis. Data collection from X-Log data logger on the computer in Excel format.



An example of X-Storage web site is http://www-lsi-lastem-xstorage.com/LSI-LASTEM. In order to activate the X-Storage service, LSI LASTEM requires the activation form at §7.1 correctly compiled on all its parts.



13



LSI LASTEM X-Log – Quick Guide



7.1.



Activation form



The following information are required to program the X-Storage service on web. Contact LSI LASTEM to purchase the X-Storage configuration service. Complete and send this module to [email protected]. This form is also available on the LSI LASTEM web site (http://www.lsi-lastem.com) in the X-Log section. Measures list: list of the ordered measures configured in the X-LOG Input N.



Measurement description (add your description, 15 characters at maximum)



1 2 3 4 5 6 7 8 10 11 12 13 General information X-LOG Serial Number Station Name Description (max 2 lines of text)



Latitude (degree, minute, second) Longitude (degree, minute, second) Record time (*) Station Id Number (*) Folder name for your web site (**) Station image or webcam link (***) NOTES: 14



LSI LASTEM X-Log – Quick Guide



(*) As set in the station configuration first page



(**) Your station data will be available at URL:http:// www.lsi-lastem-xstorage.com/folder_name; folder_name must be a valid folder name (avoid use of special characters and spaces). (***) Attach an image of the station (jpg or png format) or insert an URL that point to the webcam. After receiving this module, LSI LASTEM will send you the FTP parameters to configure X-LOG for sending data to the X-Storage website. IMPORTANT notice: X-Storage service is free of charge. It is free password service, no data control or access control is provided by LSI LASTEM. -



LSI LASTEM is not responsible for any wrong values and/or information shown on the XStorage web pages LSI LASTEM is not responsible for any interruption (random or definitive) of X-Storage service. LSI LASTEM is not responsible for any loss or missing data inside the X-Storage data base. LSI LASTEM is not responsible for any data download and/or data usage made by not authorized users.



Accepted by Name: _______________________ Date: ______________________________ Company: __________________________ Position: ___________________________ Signature: _________________________