4 0 1 MB
COMMUNICATIONS Protect 8.31
Software Management and Support Dieter Brandt
Communication for Power Supply Systems
Ing. (grad.) Dieter Brandt AEG Power Solutions GmbH Dep.: PS/T1 Software Management and Support Emil-Siepmann-Straße 32 D-59581 Warstein
Tel.: +49/2902/763-594 E-Mail: [email protected]
Fax: +49/2902/763-1211
1954; married; 1 child Apprenticeship
as electrical mechanic
1972
University of Krefeld
special subject: automation techniques
1975
AEG
Development of UPS systems Development of communication units Product Management Software Software Management and Support
1980 1990 1997 1998
p2
UPS Systems Protect 8.31
Possibilities of communication on different transmission media
OPC-Server SCADA = Supervisory Control And Data Acquisition
p3
UPS Systems Protect 8.31 Communication features of Protect 8.31 Graphical Display and Operating Unit (DOU) …new functions…
MCC and remote signaling …customized thresholds of values for signalings…
CompuWatch (Shutdown and UPS Management Software) …Protect 8.31 integration …new control functions and security…
SNMP adapter …Protect 8.31 integration …safety communication for multi-server shutdown…
ETools …Protect 8.31 integration …new functions specially for Protect 8.31
p4
UPS System Protect 8.31
Graphical Display and Operating Unit “DOU”
 Three LEDs for status indication (red, yellow, green)  Graphic LCD with 240 x 64 pixels  Four display keys and one enter key for menu use  One buzzer for signalling of important status change
NEW functions: Output voltage adjustable via DOU (+-3%) Display of rectifier mains current Display of all values of the four BLÜpro Display of customized aux ports
18 languages included German English US English French Italian Spanish Portuguese Swedish Norwegian
Dutch Polish Hungarian Czech Slovakian Turkish Russian Latvian Chinese
p5
UPS System Protect 8.31 Remote signaling Expansion PCB Option OPT Relay
Inverter off
Inverter oper.
Bypass oper. Powerfail Battery low Common alarm
Remote signalling Expansion PCB Standard PCB Option OPT OPT Relay Relay
Common alarm with:
New Hardware: Auxiliary power for opto coupler on board
New Functions: Customizable signals Relay output (all relays K21 up to K31) Common alarm DOU LEDs (yellow, red) DOU text (15 character max.) Protocols (Modbus / Jbus, Profibus DP)
•Rectifier fault •Rectifier fault with switch off •Fault trickle charge voltage •CAN parallel comm fault •Measurement fault (parallel system) •Stack parallel fault •Circuit breaker dropped •Isolation fault •Battery fault •Stack over temperature •Measurement fault DC voltage •Measurement fault power supply •Fan fault •Comm fault to rectifier
•Inverter fault •Inverter fault with switch off •CAN parallel comm fault •DC under voltage •Fan fault •Stack over temperature •Comm fault to inverter
•SBS fault •SBS fault with switch off
•CAN parallel comm fault •Control connector missing •Isolation fault •Stack over temperature •Temp. sensor fault •Fuse dropped •Fan fault •Klixon •Comm fault to SBS p6
UPS System Protect 8.31 Remote signaling Customizable signals from digital and analogue values – Settings of customized thresholds Rectifier Mains voltage (V) Mains frequency (Hz) Battery capacity (%) Autonomy time (minutes) Battery room temperature (°C)
SBS Mains voltage (V) Mains frequency (Hz) Mains current (A)
Inverter Digital input 1, 2, 3 DC voltage (V) Device input temperature (°C) Load (%) Current (A) Real power (KW) Apparent power (KVA)
Configuration of signals via “AEG Configurator” as well as “ETools” – 7 signals are configurable on one control unit on maximum p7
UPS Systems Protect 8.31
Remote UPS monitoring and notification via Telecom with UPS Alarm Management and Modem modules ¾Features: ¾no special software necessary ¾auto call of UPS ¾auto send of SMS ¾cyclic reports of UPS ¾up to five phone no. or alternative phone no. ¾Password protection ¾Call back function CCC required!!! Internal Modem module required!!! • Analogue modem module • ISDN modem module • GSM modem module p8
UPS Systems Protect 8.31
Internal communication with maximum extensions 2 Parallel CAN-Buses Rect.
Control Units
Display and Operation Unit
Invert.
SBS DOU-CAN-BUS
Graphic DOU
Communication Interfaces
Remote signalling Dry contacts/opto.
SNMP Adapter
(100 kbps)
MultiCom “CCP” UPS modem analogue/ISDN/GSM CAN Comm. Profibus DP
MultiCOM “CCC” CAN Comm. Controller
12Vdc
COM Server
Port1
Port 2
CAN
Port1
(50 kbps)
Status Signals
UPS
(500kbps)
Telecom
Port1
Port 2
CAN
(50 kbps)
CompuWatch CompuWatch SNMP-Adapter SNMP-Adapter Alarm Monitoring Management Service-Tools UPS CompuWatch via NMS (SNMP), local Management SNMP-Adapter USW, UNMS Modbus/Jbus Remote monitoring Software Profibus DP WEB Browser P1-Interface via ETools2 Service-Tools CompuWatch UPS Telecom Remote DOU Management and SMS MultiServer Shutdown Software Notify via Net message, E-Mail Remote DOU
p9
UPS Systems Protect 8.31 SNMP Adapter for UPS with CAN
Features: Agent for RFC1628 MIB UPS standard MIB Embedded Web-Server Monitoring via Web and Wap Configuration via Web
Embedded Event Manager Start of different Jobs Net Broadcast E-Mail
Monitoring of environmental conditions Temperature, Humidity, GenSet, Fire, Air condition, Smoke shutter...
Support Software products Network Management Software „NMS“ NMS special for Power Supply Systems Shutdown Software “CompuWatch” Direct multi-server shutdown of different OS with communication modules with SSL coding p 10
UPS Systems Protect 8.31
Environment Manager for SNMP Adapter Features: Eight analogue inputs for sensor Temperature sensor Humidity sensor Kombi sensor Custom sensor (0-10V)
Four digital inputs Smoke detector Motion detector 0-48V
Four digital outputs Flash Light 500mA
Configuration and Monitoring Via embedded Web server of SNMP Adapter p 11
UPS Systems Protect B, C, 1, 1.M,3.M, 2, 3, 4, 5, 8.31
Configuration of SNMP adapter
“List of UPS types”
p 12
UPS Systems Protect 8.31
Configuration of customized threshold events
p 13
UPS Systems Protect 8.31
Visualisation of UPS and Environment via Web
p 14
UPS Systems Protect 8.31
Visualisation of UPS and Environment via Web
p 15
UPS Systems Protect 8.31 Monitoring of UPS and Data Centre with SNMP adapter and Environment Manager Transmission of net-messages and E-Mails Power failure UPS-alarm Room-temperature high Air-condition fault Smoke detector active
Server-Raum UPS
Smoke-shutter
Air condition
GS: WS: EZA: Menü: Betriebsdauer:
Log Saving of all events
Shutdown-control via SSL Autonomy time near end Smoke-shutter closed Air-condition fault
Intranet UPS Monitor Internet Explorer E-Mail
SMS
p 16
UPS Systems Protect 8.31 CompuWatch the SHUTDOWN and UPS Management Software Technology Application Management MultiServer Shutdown Graphical Front-end Control function
Client/Server (UPSMonitor/UPSMANager) UPSMANager works as a back round process Control of workstation, sub networks, networks A workstation can monitor an unlimited number of UPS devices Special communication modules for different operating systems installed on client servers with SSL coding Display all important status and values of the UPS Real time synchronization and download of UPS data logger
p 17
UPS Systems Protect 8.31
Graphical front-end of CompuWatch
Normal operation
p 18
UPS Systems Protect 8.31 Extended control window of CompuWatch
Synchronization of UPS real time clock Download of internal UPS data logger p 19
UPS Systems Protect 8.31 ETOOLS for service guys with display of all extended new values for Protect 8.31 » Current version 2.06 …for example….. Stack temperature, device input temperature Fan control Rectifier mains current etc.
p 20
UPS Systems Protect 8.31 ETOOLS for customized remote signaling ….examples….
p 21
UPS Systems Protect 8.31 Next steps ETools More extensions for service support of Protect 8 (…new version will be 2.07) » (requirements from service department Belecke)
SNMP Adapter features New internal hardware with 16Mbyte flash Internal Real Time Clock GoldCap buffered » Manual adjustment of real time clock New UPS web page Web server with safety connection via https UPS-Real-Time synchronization via time server in a network Download of internal UPS data-logger Send of e-mail attachment DHCP function (Dynamic host configuration protocol) » Automatically configuration of SNMP adapter
MCE Interface (Multicom CAN to Ethernet for industrial applications) New hardware (dimensions like MCC) with:
– COM server function (point to point connection via network) – IEC 61850 protocol (more or less the standard protocol for power plants) UPS Management Software for up to 4 UPS in parallel Update for Protect 8.31 p 22
UPS Systems Protect communication
Questions or Comments?
p 23
UPS Systems Protect communication
... thanks a lot for listening and paying attention to my presentation … AEG Power Solutions GmbH Software and Support Dieter Brandt
p 24