4 0 5 MB
RCS-974AG Transformer Auxiliary Relay Instruction Manual
NR Electric Co., Ltd.
RCS-974AG Transformer Auxiliary Relay
Preface Introduction This guide and the relevant operating or service manual documentation for the equipment provide full information on safe handling, commissioning and testing of this equipment. Documentation for equipment ordered from NR is dispatched separately from manufactured goods and may not be received at the same time. Therefore this guide is provided to ensure that printed information normally present on equipment is fully understood by the recipient. Before carrying out any work on the equipment the user should be familiar with the contents of this manual, and read relevant chapter carefully. This chapter describes the safety precautions recommended when using the equipment. Before installing and using the equipment, this chapter must be thoroughly read and understood.
Health and Safety The information in this chapter of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition. When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the equipment must be isolated. Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who: z
Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected;
z
Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it;
z
Are trained in the care and use of safety apparatus in accordance with safety engineering practices;
z
Are trained in emergency procedures (first aid).
NR ELECTRIC CO., LTD
i
RCS-974AG Transformer Auxiliary Relay
Instructions and Warnings The following indicators and standard definitions are used: DANGER
means that death, severe personal injury, or considerable equipment damage will occur if safety precautions are disregarded.
WARNING
means that death, severe personal, or considerable equipment damage could occur if safety precautions are disregarded.
CAUTION
means that light personal injury or equipment damage may occur if safety precautions are disregarded. This particularly applies to damage to the device and to resulting damage of the protected equipment.
WARNING! The firmware may be upgraded to add new features or enhance/modify existing features, please make sure that the version of this manual is compatible with the product in your hand.
WARNING! During operation of electrical equipment, certain parts of these devices are under high voltage. Severe personal injury or significant equipment damage could result from improper behavior. Only qualified personnel should work on this equipment or in the vicinity of this equipment. These personnel must be familiar with all warnings and service procedures described in this manual, as well as safety regulations. In particular, the general facility and safety regulations for work with high-voltage equipment must be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER! Never allow the current transformer (CT) secondary circuit connected to this equipment to be opened while the primary system is live. Opening the CT circuit will produce a dangerously high voltage.
WARNING! z
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage generated is dangerous z
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It takes a few seconds for the voltage to discharge. ii
NR ELECTRIC CO., LTD
RCS-974AG Transformer Auxiliary Relay
CAUTION! z
Earth
The earthing terminal of the equipment must be securely earthed z
Operating environment
The equipment must only be used within the range of ambient environment detailed in the specification and in an environment free of abnormal vibration. z
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they conform to the equipment ratings. z
Printed circuit board
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this may cause the equipment to malfunction. z
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the supply voltage used in order to prevent the connected circuit from overheating. z
Connection cable
Carefully handle the connection cable without applying excessive force.
Copyright Version: R1.01
NR ELECTRIC CO., LTD.
P/N: EN_YJBH1201.0086.0002
69 Suyuan Avenue, Jiangning, Nanjing 211102, China
Copyright © NR 2009. All rights reserved
Tel:
We reserve all rights to this document and to the information
Website: www.nari-relays.com
contained herein. Improper use in particular reproduction and
Email: nr_techsupport @nari-relays.com
86-25-87178185,
Fax: 86-25-87178208
dissemination to third parties is strictly forbidden except where expressly authorized. The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated. We reserve the rights to make technical improvements without notice.
NR ELECTRIC CO., LTD
iii
RCS-974AG Transformer Auxiliary Relay
iv
NR ELECTRIC CO., LTD
RCS-974AG Transformer Auxiliary Relay
Table of Contents Preface .......................................................................................................................................... i Introduction ............................................................................................................................ i Health and Safety ................................................................................................................... i Instructions and Warnings ................................................................................................... ii Table of Contents ........................................................................................................................ v Chapter 1 Introduction ................................................................................................................ 1 1.1 Application....................................................................................................................... 1 1.2 Functions ......................................................................................................................... 1 1.3 Features ........................................................................................................................... 2 1.4 Ordering Options ............................................................................................................ 3 Chapter 2 Technical Data ............................................................................................................ 5 2.1 General Specification ..................................................................................................... 5 2.1.1 Electrical Specifications ....................................................................................... 5 2.1.2 Mechanical Specifications ................................................................................... 6 2.1.3 Ambient Temperature and Humidity Range ........................................................ 7 2.1.4 Rear Communication Port .................................................................................... 7 2.1.5 Type Test ................................................................................................................ 8 2.1.6 Electromagnetic Compatibility (EMC) ................................................................. 9 2.1.7 Certifications ....................................................................................................... 10 2.2 Protective Functions ..................................................................................................... 10 2.2.1 Breaker Failure Initiation .................................................................................... 10 2.2.2 Pole Disagreement Protection ........................................................................... 10 2.2.3 Mechanical Protection ........................................................................................ 10 Chapter 3 Operation Theory of Protection ...............................................................................11 3.1 Overview ........................................................................................................................ 11 3.2 General Fault Detector .................................................................................................. 11 3.2.1 Fault Detector of Pole Disagreement Protection .............................................. 11 3.2.2 Fault Detector of Breaker Failure Initiation....................................................... 12 NR ELECTRIC CO., LTD
v
RCS-974AG Transformer Auxiliary Relay
3.2.3 Mechanical Protection with Time Delay ............................................................ 12 3.3 Protective Fault Detector .............................................................................................. 13 3.4 Mechanical Protection (MR) ......................................................................................... 13 3.4.1 MR for Warning ................................................................................................... 13 3.4.2 Tripping Directly.................................................................................................. 13 3.4.3 Tripping with Time Delay .................................................................................... 14 3.4.4 Logical Diagram of MR Trip with Time Delay .................................................... 15 3.5 Pole Disagreement Protection (PD) ............................................................................. 16 3.5.1 Operation criteria ................................................................................................ 17 3.5.2 Control Element .................................................................................................. 17 3.5.3 Logical Diagram of Pole Disagreement Protection .......................................... 18 3.6 Breaker Failure Initiation (BFI) ..................................................................................... 20 3.6.1 Operation Criteria ............................................................................................... 20 3.6.2 Control Element .................................................................................................. 21 3.6.3 Logic Diagram of Breaker Failure Initiation ...................................................... 21 3.7 CT Circuit Supervision (CTS) ....................................................................................... 22 Chapter 4 Automatic Supervision ............................................................................................ 23 4.1 Overview ........................................................................................................................ 23 4.2 Relay Self-supervision.................................................................................................. 23 4.2.1 Relay Hardware Monitoring................................................................................ 23 4.2.2 Opto-coupler Power Monitoring ........................................................................ 23 4.2.3 Output Tripping Circuit Monitoring ................................................................... 23 4.2.4 Check Setting ...................................................................................................... 24 4.2.5 Voltage and Current Drift Monitoring and Auto Adjusting ............................... 24 4.2.6 DSP Sampling Monitoring .................................................................................. 24 4.2.7 CPU Sampling Monitoring .................................................................................. 24 4.2.8 Fault Detection Monitoring................................................................................. 24 4.2.9 CT Circuit Supervision (CTS) ............................................................................. 24 4.2.10 Pole Disagreement Position of CB monitoring .............................................. 24 4.2.11 External Tripping Input Monitoring .................................................................. 25 vi
NR ELECTRIC CO., LTD
RCS-974AG Transformer Auxiliary Relay
4.2.12 Breaker Failure Initiation Alarm ....................................................................... 25 4.2.13 Other Abnormality Alarm .................................................................................. 25 4.3 Understand the Alarms ................................................................................................. 25 Chapter 5 Metering and Recording .......................................................................................... 29 5.1 Overview ........................................................................................................................ 29 5.2 Metering ......................................................................................................................... 29 5.2.1 Measurement Value ............................................................................................ 29 5.2.2 Phase Angle ........................................................................................................ 29 5.2.3 Binary Input ......................................................................................................... 30 5.3 Recording Function ...................................................................................................... 31 5.3.1 General Description ............................................................................................ 31 5.3.2 Event Recording ................................................................................................. 31 5.3.3 Fault Recording ................................................................................................... 31 5.4 Time Synchronization ................................................................................................... 32 Chapter 6 Hardware Description .............................................................................................. 35 6.1 Overview ........................................................................................................................ 35 6.2 Plug-in Modules ............................................................................................................ 36 6.2.1 Power Supply Module (No.1 PWR) .................................................................... 36 6.2.2 AC Input Module (No.2 AI) .................................................................................. 37 6.2.3 Low-pass Filter Module (No.3 LPF) ................................................................... 38 6.2.4 Module CPU (No.4 CPU) ..................................................................................... 39 6.2.5 Communication Interface Module (No.5 COM) ................................................. 39 6.2.6 Opto-coupler Module (24Vdc) (No.6 BI) ............................................................ 42 6.2.7 Output Relay Modules (No.7~No.8 BO) ............................................................. 44 6.2.8 Mechanical Relay Modules (No.9~No.B IO) ...................................................... 48 6.2.9 Tripping Output Module (No.E RLY) .................................................................. 54 6.3 Scheme Diagram of Input and Output of MR .............................................................. 59 6.4 Output Signals............................................................................................................... 61 Chapter 7 Settings .................................................................................................................... 63 7.1 Equipment Settings ...................................................................................................... 63 NR ELECTRIC CO., LTD
vii
RCS-974AG Transformer Auxiliary Relay
7.2 Protection Settings ....................................................................................................... 65 7.3 IP Address Settings ...................................................................................................... 69 7.4 MR Definition Settings .................................................................................................. 69 Chapter 8 HMI Operation Instruction ....................................................................................... 71 8.1 Overview ........................................................................................................................ 71 8.1.1 Keypad Operation ............................................................................................... 72 8.1.2 LED Indicators..................................................................................................... 73 8.1.3 Communication Port ........................................................................................... 74 8.1.4 TARGET RESET Button ...................................................................................... 74 8.2 Understand the HMI Menu Tree .................................................................................... 74 8.2.1 Overview .............................................................................................................. 74 8.2.2 VALUES................................................................................................................ 75 8.2.3 REPORT ............................................................................................................... 76 8.2.4 PRINT ................................................................................................................... 76 8.2.5 SETTINGS ............................................................................................................ 76 8.2.6 CLOCK ................................................................................................................. 77 8.2.7 VERSION .............................................................................................................. 77 8.2.8 LANGUAGE ......................................................................................................... 77 8.3 Understand the LCD Display ........................................................................................ 77 8.3.1 Main Display under Normal Operation Condition ............................................ 77 8.3.2 Display Tripping Report...................................................................................... 78 8.3.3 Display Abnormal Report ................................................................................... 78 8.3.4 Display Status Change of Binary Input ............................................................. 79 8.3.5 View the Settings ................................................................................................ 79 8.3.6 View Records ...................................................................................................... 80 8.3.7 Printing Reports and Waveform ........................................................................ 81 8.4 Input Operation through Keypad ................................................................................. 82 8.4.1 Change the Settings ........................................................................................... 82 8.4.2 Copy Settings ...................................................................................................... 82 8.4.3 Switch Active Setting Group .............................................................................. 83 viii
NR ELECTRIC CO., LTD
RCS-974AG Transformer Auxiliary Relay
8.4.4 Delete Fault Records and Event Records ......................................................... 83 8.4.5 Adjusting the Clock ............................................................................................ 84 8.4.6 View Software Version ........................................................................................ 84 Chapter 9 Communications...................................................................................................... 87 9.1 Overview ........................................................................................................................ 87 9.2 Rear Communication Port Information ....................................................................... 87 9.2.1 RS-485 Interface .................................................................................................. 87 9.2.2 Ethernet Interface ............................................................................................... 89 9.2.3 IEC60870-5-103 Communication ........................................................................ 90 9.3 IEC60870-5-103 Interface over Serial Port .................................................................. 90 9.3.1 Physical Connection and Link Layer ................................................................ 90 9.3.2 Initialization ......................................................................................................... 90 9.3.3 Time Synchronization ......................................................................................... 91 9.3.4 Spontaneous Events ........................................................................................... 91 9.3.5 General Interrogation ......................................................................................... 92 9.3.6 General Functions .............................................................................................. 92 9.3.7 Disturbance Records .......................................................................................... 93 9.4 IEC60870-5-103 Interface over Ethernet ...................................................................... 93 9.5 Modbus Protocol over Serial Port ............................................................................... 94 9.5.1 Overview .............................................................................................................. 94 9.5.2 Fetch real Time Status (Binary) ......................................................................... 94 9.5.3 Fetch Metering Values of Equipment ................................................................ 96 9.5.4 Fetch Settings Value of Equipment ................................................................... 97 9.5.5 Diagnostics (Function Code: 08H) .................................................................... 98 9.5.6 Exception Responses ......................................................................................... 99 9.6 Messages Description for IEC61850 Protocol ............................................................ 99 9.6.1 Overview .............................................................................................................. 99 9.6.2 Communication Profiles ................................................................................... 100 9.6.3 Server Data Organization ................................................................................. 101 9.6.4 Server Features and Configuration ................................................................. 103 NR ELECTRIC CO., LTD
ix
RCS-974AG Transformer Auxiliary Relay
9.6.5 ACSI conformance ............................................................................................ 105 9.6.6 Logical Nodes ................................................................................................... 109 9.7 Front EIA(RS)232 Interface Communication ..............................................................111 9.8 Communication with Printer ...................................................................................... 112 9.9 Communication with External Time Synchronization Source ................................. 113 Chapter 10 Commissioning and Installation ..........................................................................115 10.1 Introduction ............................................................................................................... 115 10.2 Safety Information..................................................................................................... 116 10.3 Overview .................................................................................................................... 117 10.4 Unpacking and Checking The Protection Equipment ............................................ 117 10.5 Installing the Protection Equipment ........................................................................ 118 10.5.1 Overview .......................................................................................................... 118 10.5.2 Dimensions...................................................................................................... 119 10.5.3 Grounding Guidelines .................................................................................... 119 10.5.4 Cubicle Grounding .......................................................................................... 120 10.5.5 Ground Connection on the Device ................................................................ 121 10.5.6 Grounding Strips and Their Installation ........................................................ 121 10.5.7 Making the Electrical Connections ................................................................ 121 10.6 Check the External Circuitry .................................................................................... 123 10.7 Energizing the Protection Equipment ..................................................................... 124 10.8 Setting the Protection Equipment ........................................................................... 125 10.9 Establishing Connection and Verifying Communication ....................................... 125 10.10 Verifying Settings by Secondary Injection ............................................................ 125 10.10.1 Insulation Test (if required) .......................................................................... 126 10.10.2 Current Measurement Check ....................................................................... 127 10.10.3 Testing the Binary Inputs ............................................................................. 127 10.10.4 Mechanical Protection .................................................................................. 128 10.10.5 Pole Disagreement Protection ..................................................................... 128 10.10.6 Breaker Failure Initiation .............................................................................. 130 10.10.7 Secondary Circuit Abnormality and Failure................................................ 130 x
NR ELECTRIC CO., LTD
RCS-974AG Transformer Auxiliary Relay
10.10.8 Print Fault Report .......................................................................................... 131 10.10.9 Final Check .................................................................................................... 131 Chapter 11 Maintenance ......................................................................................................... 133 11.1 Appearance Check .................................................................................................... 133 11.2 Failure Tracing and Repair ....................................................................................... 133 11.3 Replace Failed Modules ............................................................................................ 134 11.4 Replace Button Battery ............................................................................................. 135 11.5 Cleaning ..................................................................................................................... 135 11.6 Storage ....................................................................................................................... 135 Chapter 12 Decommissioning and Disposal......................................................................... 137 12.1 Decommissioning ..................................................................................................... 137 12.1.1 Switching off ................................................................................................... 137 12.1.2 Disconnecting Cables..................................................................................... 137 12.1.3 Dismantling ..................................................................................................... 137 12.2 Disposal ..................................................................................................................... 137 Chapter 13 Manual Version History ....................................................................................... 139
NR ELECTRIC CO., LTD
xi
Chapter 1 Introduction
Chapter 1 Introduction 1.1 Application The RCS-974 relay is a transformer auxiliary relay applied for the protection of a transformer, which provides mechanical protection, pole disagreement protection and breaker failure initiation. Mechanical signal could be configured as thermal, gas, oil temperature, winding temperature, pressure, oil level and so on.
Figure 1.1-1
Typical Application
1.2 Functions z
Mechanical protection (26: oil and winding temperature; 63: gas, pressure; 71: oil level; etc)
z
Breaker failure initiation (BFI)
z
Pole disagreement function (62PD)
z
CT circuit failure supervision.(CTS)
z
Power supervision of mechanical protection
z
Current drift auto adjustment
z
Self diagnostic test
z
GPS time synchronization
NR ELECTRIC CO., LTD
1
Chapter 1 Introduction
z
z
z
Perfect fault recording function
64 latest tripping records
64 latest alarm records
64 latest binary change records
High resolution oscillography of last 24 oscillograms (compatible with international COMTRADE format)
Rear communication ports:
Ethernet (Optional)
Two RS-485 with IEC 60870-5-103 protocol
One RS-485 for clock synchronization
One RS-232 or RS-485 for printing
Front communication port:
One RS-232 for testing and setting
1.3 Features The RCS-974 relay provides wiring connectors from the relay rear panel to the terminal blocks on the rack or cabinet. This kind of connected wiring makes the on-site commissioning and replacement much easier than that done using the traditional screw terminals on the rear panel. NR provides a special and dedicated test set, HELP-90, for a low-level voltage injection test.
●
The RCS-974 relay provides special measurements to prevent undesirable tripping. The relay has two independent data acquisition paths, one for a fault detector and one for protection and its logic. Tripping outputs are supervised by the fault detector to prevent a maloperation caused by any component failure in the relay. ●
On the premise of 24 samples per cycle, all data measurement, calculation and logic discrimination could be done within one sampling period. The event recording and protection logic calculation are completed simultaneously. ●
15 channels of mechanical signal input are provided, among which 7 are for event recording, 5 for instantaneous tripping and 3 for tripping with time delay. ●
●
Power supply of mechanical quantity input circuit is monitored.
●
Mechanical quantity protection and other auxiliary protection are independent of each other.
Various methods of GPS time synchronization, including PPS (pulse per second), PPM (pulse per minute) and IRIG-B standard. ●
●
2
The HMI with a LCD and a 9-button keypad on the front panel is very friendly to the user.
NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter 1 Introduction ●
The format of event report is compatible with international COMTRADE file.
●
The relay is equipped with Ethernet ports with IEC 61850 or RS-485 ports with the IEC 60870-5-103 protocol.
1.4 Ordering Options z
Two options are available for rated secondary current of CT inputs: 1A or 5A.
z
Four options are available for rated auxiliary voltage: 250V, 220V, 125V, 110V.
z
The communication module No.5 COM is optional: type 5A, type 5B and or type 5E.
NR ELECTRIC CO., LTD
3
Chapter 1 Introduction
4
NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter 2 Technical Data
Chapter 2 Technical Data 2.1 General Specification 2.1.1 Electrical Specifications 2.1.1.1 Power Supply Rated Voltage (Un)
24Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation
(80% ~ 120%)Un
Ripple in the DC auxiliary voltage
Max 15% of the DC value. Per IEC 60255-11
Voltage dips and voltage short interruptions
Per IEC 61000-4-11, IEC 60255-11:1979 20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition Burden
Operating condition
Backup battery type
[I_ROC_PD_CT1] has to be satisfied in order to meet the zero sequence control element. When [Opt_CT_PD] is set as “1”, only 3I0_CT1>[I_ROC_PD_CT1] and 3I0_CT2>[I_ROC_PD_CT2] has to be satisfied at the same NR ELECTRIC CO., LTD
17
Chapter 3 Operation Theory of Protection
time to meet the zero sequence control element.. (2) Control element of phase overcurrent is only for delay 2 of pole disagreement protection by configuring logic setting. The criterion is following: Imax_CT1>[I_OC_BFI_CT1] Where: Imax_CT1: maximum value of three-phase current of CT1. [I_OC_BFI_CT1]: setting of overcurrent element of breaker failure initiation, current from CT1. Settings of phase overcurrent elements used in pole disagreement protection delay 2 and used in breaker failure initiation are the same one [I_OC_BFI_CT1]. (3) The binary input [BI_ExTCtrlPD2] is only used to control delay 2 of pole disagreement protection by configuring logic settings. Logic Diagram of Pole Disagreement Protection
3.5.3 Logical Diagram of Pole Disagreement Protection Logical diagram of pole disagreement protection is presented in Figure 3.5-1.
18
NR ELECTRIC CO., LTD
Chapter 3 Operation Theory of Protection 3I0_CTn>[I_ROC_PD_CTn]
&
[En_ROC_PD]
≥1
≥1
[En_NegOC_PD] I2_CTn>[I_NegOC_PD_CTn]
&
&
[t_PD1]
[Op_PD1]
[BI_PD_CB]
&
[En_PDP1] [EBI_PDP]
[En_ExTCtrlPD2]
≥1 [BI_ExTCtrlPD2]
≥1 Imax_CT1>[I_OC_BFI1 ]
&
≥1
[En_OC_PDP2 ]
&
[t_PD2]
[Op_PD2]
3I0_CTn>[I_ROC_PD_CTn]
&
≥1
[En_ROC_PDP] [En_NegOC_PDP]
& I2_CTn>[I_NegOC_PD_CTn] [BI_PD_CB]
&
[En_PD2] [EBI_PD]
Figure 3.5-1 Logical diagram of pole disagreement protection Where: 3I0_CTn, I2_CTn, [I_ROC_PD_CTn], and [I_NegOC_PD_CTn]: same meanings as those motioned in section 3.5.2. [En_ROC_PD]: the logic setting of enabling control element of zero sequence overcurrent for pole disagreement protection. [En_NegOC_PD]: the logic setting of enabling control element of negative sequence overcurrent for pole disagreement protection. [En_ExTCtrlPD2]: the logic setting of enabling delay 2 of pole disagreement protection controlled by binary input of three-pole tripping from external relay. NR ELECTRIC CO., LTD
19
Chapter 3 Operation Theory of Protection
[En_PD1]: the logic setting of enabling delay 1 of pole disagreement protection. [En_PD2]: the logic setting of enabling delay 2 of pole disagreement protection. [EBI_PD]: binary input of enabling pole disagreement protection. [BI_PD_CB]: the binary input of pole disagreement position of circuit breaker (CB), which can be energized through either terminal 910 or terminal 611. [BI_ExTCtrlPD2]: the binary input of three-pole tripping from external relay. [t_PD1]: the time delay of delay 1 of pole disagreement protection. [t_PD2]: the time delay of delay 2 of pole disagreement protection. [Op_PD1]: the delay 1 of pole disagreement protection operating to issue tripping command. [Op_PD2]: the delay 2 of pole disagreement protection operating to issue tripping command.
3.6 Breaker Failure Initiation (BFI) This function is specifically used to detect breaker failure which is that breaker fails to be tripped to clear fault after it receives tripping command. After breaker failure is detected, contacts of initiating breaker failure initiation are sent out to external relay which is responsible for issuing tripping command.
3.6.1 Operation Criteria Breaker failure initiation (BFI) in RCS-974 is initiated by one of three elements: phase overcurrent element, zero sequence current element or negative sequence current element. Followings are criteria of those elements: Imax_CTn>[I_OC_BFI_CTn] 3I0_CTn>[I_ROC_BFI_CTn] I2_CTn>[I_NegOC_BFI_CTn] Where: Imax_CTn: maximum value of three-phase current from CTn. 3I0_CTn: three times zero sequence current calculated from CTn. I2_CTn: negative sequence current calculated from CTn. [I_ROC_BFI_CTn]: current setting of control element of zero sequence overcurrent for pole disagreement protection, for CTn. [I_NegOC_BFI_CTn]: current setting. of control element of negative sequence overcurrent for pole disagreement protection, for CTn Here n is the group number of CT. When logic setting [Opt_CT_BFI] is set as “0”, only first group of CT (CT1) is used and n=1. When logic setting [Opt_CT_BFI] is set as “1”, both of the two 20
NR ELECTRIC CO., LTD
Chapter 3 Operation Theory of Protection
groups of CT are utilized (CT1 and CT2), n has to be equal to 1 and 2 separately. For example, when [Opt_CT_PD] is set as “0”, only 3I0_CT1>[I_ROC_ BFI1] has to be satisfied in order to meet the zero sequence control element. When [Opt_CT_BFI] is set as “1”, only 3I0_CT1>[I_ROC_ BFI 1] and 3I0_CT2>[I_ROC_ BFI 2] has to be satisfied at the same time to meet the zero sequence control element.
3.6.2 Control Element It is configurable whether the breaker failure initiation is blocked by any one of following contacts: pole disagreement position ([BI_PD_CB]), closed state of breaker auxiliary contact ([BI_52a]) or external tripping signal ( [BI_ExTCtrBFI]).
3.6.3 Logic Diagram of Breaker Failure Initiation RCS-974 provides two delays for breaker failure initiation, which logic diagram is showed in below.
Figure 3.6-1
Logical diagram of breaker failure initiation
Where: Imax_CTn, 3I0_CTn, I2_CTn, [I_ROC_BFI_CTn], [I_NegOC_BFI_CTn], and [I_OC_BFI_CT1]: same meanings as those motioned in section 3.6.2. [En_PD_Ctrl_BFI]: the logic setting of enabling binary input [BI_PD_CB] to control breaker failure initiation. [BI_PD_CB]: the binary input of pole disagreement position of CB. [En_52aCtrlBFI]: the logic setting of enabling binary input [BI_52a] to control breaker failure initiation. [BI_52a]: the binary input of normally open auxiliary contact of circuit breaker. NR ELECTRIC CO., LTD
21
Chapter 3 Operation Theory of Protection
[En_ExTCtrlBFI]: the logic setting of enabling binary input [BI_ExTCtrlBFI] to control breaker failure initiation. [BI_ExTCtrlBFI]: the binary input of external tripping contact from other protection equipment. [En_BFI]: the logic setting of enabling breaker failure protection. [En_ROC_BFI]: the logic setting of enabling zero sequence overcurrent element of breaker failure protection. [En_NegOC_BFI]: the logic setting of enabling negative sequence overcurrent element of breaker failure protection. [Alm_Pkp_BFI1]: the pickup of delay 1 of breaker failure initiation alarm element. [Alm_Pkp_BFI2]: the pickup of delay 2 of breaker failure initiation alarm element.
3.7 CT Circuit Supervision (CTS) If negative sequence current of CT1 (first group CT) or/and CT2 (secondary group CT) is greater than 0.06In (In is the secondary rated current.) and it lasts for 10s, RCS-974 will issue an alarm message as [Alm_CTS_CT1] or/and [Alm_CTS_CT2] of CT circuit failure on LCD. For the meantime, LED “ALARM” is lit on and associated normal open contacts of equipment alarm relay are closed to issue annunciation signal, remote signal and event recording. This alarm information can also be sent to SCADA by communication port. At this time, RCS-974 can also endure on service. The LED “ALARM” will be extinguished automatically 20s later after the three-phase current returns to normal state.
22
NR ELECTRIC CO., LTD
Chapter 4 Automatic Supervision
Chapter 4 Automatic Supervision 4.1 Overview Though the protection system is in non-operating state under normal conditions, it is waiting for a power system fault to occur at any time and must operate for the fault without failure. When equipment is in energizing process before the LED “HEALTHY” is on, the equipment needs to be checked to ensure no errors. Therefore, the automatic supervision function, which checks the health of the protection system when startup and during normal operation, plays an important role. The numerical relay based on the microprocessor operations is suitable for implementing this automatic supervision function of the protection system. In case a fatal fault is detected during automatic supervision, the equipment will be blocked out. It means that relay is out of service. Before you must re-energize the relay to make relay back into service, please find out the cause and inform the factory. When a failure is detected by the automatic supervision, it is followed with an LCD message, LED indication and alarm contact outputs. At the same time event recording will record the failure alarm which can be viewed in event recording report and be printed.
4.2 Relay Self-supervision 4.2.1 Relay Hardware Monitoring The RAM, ROM chips on CPU module are monitored to ensure whether they are damaged or have errors. If any one of them is detected damaged or having error, equipment will be blocked and issue alarm [Alm_RAM] and [Alm_ROM]. In the mean time, LED “HEALTH” is extinguished and LED “ALARM” is lit on.
4.2.2 Opto-coupler Power Monitoring Positive power supply of opto-coupler is continually monitored. If a disconnection of opto-coupler power supply happens or an error or damage has occurred, an alarm [Alm_Pwr_Opto] will be issued and the relay will be blocked. In the mean time, LED “HEALTH” is extinguished and LED “ALARM” is lit on. Moreover, [BI_Pwr_Opto] in the menu item or BI STATE is set as “0”.
4.2.3 Output Tripping Circuit Monitoring Chips controlling the output relays in the output circuit are continually monitored. If output relays keeps operating over 10s, alarm or any error or damage is detected in these chips, [Alm_TrpOut] will be given and the relay will be blocked. In the mean time, LED “HEALTH” is extinguished and LED “ALARM” is lit on.
NR ELECTRIC CO., LTD
23
Chapter 4 Automatic Supervision
4.2.4 Check Setting RCS-974 series has 30 setting groups, while only one is active at the same time. The settings of active group are always checked to ensure they are reasonable. If the settings of active group are checked error in DSP chip and CPU chip, an alarm [Alm_Setting] and [Alm_EEPROM] are issued respectively. Meanwhile, LED “HEALTHY” is extinguished and LED “ALARM” is lit on. If these 30 setting groups are not all set, when the equipment is power on first, an alarm [Alm_InvalidGrp] will be issued with equipment being blocked. If the secondary rated current of CT ([I2n]) in equipment settings is changed and the protection settings is not confirmed or some settings in protection settings exceed setting range, an alarm [Alm_InvalidGrp] will be issued with equipment being blocked , LED “HEALTHY” is extinguished and LED “ALARM” is lit.
4.2.5 Voltage and Current Drift Monitoring and Auto Adjusting Zero point of voltage and current may drift influenced by variation of temperature or other environment factors. The equipment continually automatically traces the drift and adjusts it to normal value.
4.2.6 DSP Sampling Monitoring AC current and voltage sampling of DSP chip is monitored and if the samples are detected to be wrong, an alarm [Alm_Smpl_DSP] will be issued and the relay will be blocked. In the mean time, LED “HEALTHY” is extinguished and LED “ALARM” is lit.
4.2.7 CPU Sampling Monitoring The relay compares the CPU sampling and DSP sampling. In normal condition, the sampling should be the same for a certain AC input. If current of voltage sampling in CPU is detected to be different largely with that in DSP, an alarm [Alm_Smpl_CPU] will be issued and the relay will be blocked. In the mean time, LED “HEALTH” is extinguished and LED “ALARM” is lit.
4.2.8 Fault Detection Monitoring When fault detector in CPU module picks up over 10s, an alarm will be issued [Alm_PersistFD] without equipment blocked. In the mean time, LED “ALARM” is lit.
4.2.9 CT Circuit Supervision (CTS) The main purpose of the current transformer (CT) supervision function is to detect faults in the secondary circuits of CT and avoid influence on some protection functions, and remind the user to locate the fault position and solve it. Please refer to the section 3.7 for details.
4.2.10 Pole Disagreement Position of CB monitoring The binary input of pole disagreement position of auxiliary contacts of circuit breaker ([BI_PD_CB]) is continually monitored. When the binary input keeps being energized over 20s, whilst CT circuit failure is not detected by the equipment, RCS-974 will issue an alarm message [Alm_BI_PD] on LCD to indicate an exception external contact connected to [BI_PD_CB]. Meanwhile, LED “ALARM” is lit on and RCS-974 can also endure on service.
24
NR ELECTRIC CO., LTD
Chapter 4 Automatic Supervision
The LED “ALARM” will be extinguished automatically 20s later after the binary input is de-energized ([BI_PD_CB] =0).
4.2.11 External Tripping Input Monitoring The binary input of external tripping signal for controlling breaker failure initiation ([BI_ExTCtrlBFI]) and the binary input of external tripping signal for controlling pole disagreement delay 2 ([BI_ExtCtrlPD2]) are continually monitored. When any one of them keeps being energized for 20s, RCS-974 will issue an alarm message as [Alm_BI_ExTrp] on LCD to indicate an exception external contact connected to [BI_ExTCtrlBFI] or [BI_ExtCtrlPD2]. Meanwhile, LED “ALARM” is lit on, and the relay can also endure on service. The LED “ALARM” will be extinguished automatically 20s later after binary input ([BI_ExTCtrlBFI], or [BI_ExtCtrlPD2]) is de-energized ([BI_PD_CB] =0).
4.2.12 Breaker Failure Initiation Alarm When breaker failure initiation element picks up, an alarm message [Alm_Pkp_BFI1] or [Alm_Pkp_BFI2] will be issued on LCD to indicate the corresponding contacts of breaker failure initiation of the relay operate and the “ALARM” LED is issued at the same time. When the breaker failure initiation element resets, then the “ALARM” LED is extinguished.
4.2.13 Other Abnormality Alarm When a binary input of MR signal (MR4~MR16) arrives at the equipment, the corresponding alarm signal will be issued with “ALARM” LED being lit, and when the signal is gone, the “ALARM” LED is extinguished.
4.3 Understand the Alarms Hardware circuit and operation condition of the equipment are self-supervised continuously. If any abnormal condition is detected, information or report will be displayed and a corresponding alarm will be issued. A common abnormality may block a certain number of protections functions while the other functions can still work. However, if serious hardware failure or abnormality were detected, all protection functions will be blocked and the LED “HEALTHY” will turn off. When hardware failure is detected, all protection functions will be blocked and “equipment failure” alarm signal will be given by contacts output BO_Fail. The equipment then cannot work normally and maintenance is required to eliminate the failure. NOTE: If the equipment is blocked or an alarm signal is issued during operation, do please find out its reason with the help of submenu “ALM REPORT”. If the reason can not be found on site, please inform the factory NR. Please do not simply press “TARGET RESET” button on faceplate of the equipment, press “RESET” button on the protection panel to energize the binary input [BI_RstTarg] or reboot the equipment.
NR ELECTRIC CO., LTD
25
Chapter 4 Automatic Supervision
Table 4.3-1 Alarm message list No.
Alarm Message
Meaning Description
1
Alm_RAM
CPU module RAM is damaged.
2
Alm_ROM
CPU module ROM is damaged.
3
Alm_EEPROM
Settings in active group are found error after setting check in CPU chip.
4
Alm_InvalidGrp
Invalid settings in active setting group
5
Alm_Smpl_CPU
CPU chip sample differs too much from DSP sampling
6
Alm_Smpl_DSP
DSP chip is damaged or DSP sampling is wrong
7
Alm_TrpOut
Driving transistors of binary outputs are damaged.
8
Alm_Setting
Settings in active group are found error after setting check in DSP chip.
9
Alm_Pwr_Opto
Loss of opto-coupler power supply.
When above No.1~No.10 alarm messages are displayed on the LCD, the LED “HEALTHY” is extinguished and the LED “ALARM” is it. At the same time the equipment is blocked. 10
Alm_PersistFD
Fault detector keeps picking up for 10s.
11
Alm_CTS_CT1
The secondary circuit of the first group CT is abnormal.
12
Alm_CTS_CT2
The secondary circuit of the second group CT is abnormal.
13
Alm_BI_PD
The binary input of pole disagreement of circuit breaker is abnormal.
14
Alm_BI_ExTrp
The binary inputs of external tripping signal are abnormal.
15
Alm_Pkp_BFI1
Delay 1 of breaker failure initiation picks up.
16
Alm_Pkp_BFI2
Delay 2 of breaker failure imitation picks up.
17
Alm_MR5
MR5 signal arrives at relay.
18
Alm_MR6
MR6 signal arrives at relay.
19
Alm_MR7
MR7 signal arrives at relay.
20
Alm_MR8
MR8 signal arrives at relay.
21
Alm_MR9
MR9 signal arrives at relay.
22
Alm_MR10
MR10 signal arrives at relay.
23
Alm_MR11
MR11 signal arrives at relay.
24
Alm_MR12
MR12 signal arrives at relay.
25
Alm_MR13
MR13 signal arrives at relay.
26
Alm_MR14
MR14 signal arrives at relay.
27
Alm_MR15
MR15 signal arrives at relay.
28
Alm_MR16
MR16 signal arrives at relay.
When the No.10~No.28 above alarm messages are issued on the LCD, the LED “HEALTHY” is still on without equipment being blocked, and the LED “ALARM” is lit.
26
NR ELECTRIC CO., LTD
Chapter 4 Automatic Supervision
Handling suggestion 1. Inform manufacturer for maintenance.(No.1~No.8) 2. Check the power supply of No.6 BI modules. (No.9) 3. Check secondary circuit and protection settings. (No.10) 4. Check the sample value, and the corresponding CT secondary circuit. (No.11~No.12) 5. Check the contact of pole disagreement position of circuit breaker. (No.13) 6. Check the contacts of external tripping from other equipments. (No.14) 7. Treat it as the operation requirement. (No.15~No.28)
NR ELECTRIC CO., LTD
27
Chapter 4 Automatic Supervision
28
NR ELECTRIC CO., LTD
Chapter 5 Metering and Recording
Chapter 5 Metering and Recording 5.1 Overview The synchronizer also provides some auxiliary functions, such as real-time data metering, binary input status recording, event and disturbance recording, etc. All these make the synchronizer meet the demands of the modern power grid requirements.
5.2 Metering RCS-974 performs continuous measurement of the analogue input quantities. The measurement data shown below is displayed on the LCD of the synchronizer front panel or on the local or remote PC. Equipment samples 24 points per cycle. Calculate the RMS value in each interval and LCD will be updated every 0.5 second. The following system quantities are displayed in RMS values of the secondary side of CT and VT. This device has double CPU system (i.e. CPU and MON module), so the sampled values of both modules will be displayed on LCD through different access menu.
5.2.1 Measurement Value Table 5.2-1 Measured and calculated values No.
Value
Meaning
Unit
1
Ia_1
Phase A current of the first group of CT (i.e. CT1)
A
2
Ib_1
Phase B current of the CT1
A
3
Ic_1
Phase C current of the CT1
A
4
3I0_1
Three times zero-sequence current of the first group of CT (i.e. CT2)
A
5
I2_1
Negative-sequence current of the CT2
A
6
Ia_2
Phase A current of the CT2
A
7
Ib_2
Phase B current of the CT2
A
8
Ic_2
Phase C current of the CT2
A
9
3I0_2
Three times zero-sequence current of the CT2
A
10
I2_2
Negative-sequence current of the CT2
Path
VALUES -> CPU METERING VALUES -> DSP METERING
5.2.2 Phase Angle Table 5.2-2 Phase angles list No.
Value
Meaning
Unit
1
(Ia-Ib)_1
Phase angle between phase A and phase B currents of the CT1
°
2
(Ib-Ic)_1
Phase angle between phase B and phase C currents of the CT1
°
NR ELECTRIC CO., LTD
29
Chapter 5 Metering and Recording
No.
Value
Meaning
Unit
3
(Ic-Ia)_1
Phase angle between phase C and phase A currents of the CT1
°
4
(Ia-Ib)_2
Phase angle between phase A and phase B currents of the CT1
°
5
(Ib-Ic)_2
Phase angle between phase B and phase C currents of the CT1
°
6
(Ic-Ia)_2
Phase angle between phase C and phase A currents of the CT1
°
Path
VALUES -> CPU METERING VALUES -> DSP METERING
5.2.3 Binary Input All the binary input changes are recorded in the equipment, and can be displayed on LCD locally printed or sent to automation system of substation via communication channel. If a certain binary input appears to be “1”, it means that an external binary input signal is energized or a corresponding function/element of the equipment is enabled. On the other side if a certain binary input appears to be “0”, it means that the external binary input signal is de-energized or the corresponding function/element of the equipment is disabled. These binary inputs are listed in the following table. Table 5.2-3 Binary input status list No.
Item
Description
1
BI_MR1
Binary input of MR1 mechanical signal.
2
BI_MR2
Binary input of MR2 mechanical signal.
3
BI_MR3
Binary input of MR3 mechanical signal.
4
EBI_PD
Binary input of enabling pole disagreement protection
5
EBI_Dly_MR
Binary input of enabling mechanical protection which operates with time delay (MR1, MR2 and MR3)
6
BI_ExTCtrlBFI
Binary input of an external trip signal to control breaker failure initiation.
7
BI_ExTCtrlPD2
Binary input of an external trip signal to control pole disagreement protection delay 2.
8
BI_52a
Binary input of the normally open auxiliary contact of CB.
9
BI_Pwr_Opto
Binary input of supervising power supply of opto-coupler.
10
BI_PD_CB
Pole disagreement position of CB
11
BI_TrpOut
Binary input of supervision tripping output circuit.
12
FD_CPU
Virtual binary input of supervising pickup of fault detectors.
13
BI_RstTarg
Binary input of signal reset.
14
BI_BlkComm
Binary input indicating communication function.
15
BI_Print
Binary input used to trigger print function.
16
BI_Pulse_GPS
Binary input from time synchronization pulse.
blocking
rear
four
RS485
ports
Path VALUES->BI STATE
30
NR ELECTRIC CO., LTD
Chapter 5 Metering and Recording
5.3 Recording Function 5.3.1 General Description The RCS-974 series provides the following recording functions:
Event recording
Fault recording
These records are displayed on the LCD of the relay front panel or on the local or remote PC. Navigate the menu to view the report through LCD screen. Access path in menu is:
5.3.2 Event Recording Event recorder includes self-supervision report, status change of binary input report and operating report. The equipment can store 64 records of each kind for self-supervision report and status change of binary input report in non-volatile memory.
Failure alarms of Automatic Supervision
The equipment is under automatic supervision all the time. If there are any failure or abnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged as an event. For detailed alarm reports, please refer to Table 4.3-1.
Change of binary input reports
When there is binary input is energized or de-energized, i.e., its state has changed from “0” to “1” or from “1” to “0”, it will be logged as an event Please refer to Table 5.2-3 or binary input reports.
5.3.3 Fault Recording 5.3.3.1 General Description Disturbance recording is consisted of fault operation report recording and fault waveform recording. Disturbance recording is initiated by fault detection element. There are two types of disturbance recording initiation: with and without pickup of protective elements. 5.3.3.2 Fault Recording Capacity and Information The equipment can store 64 records of operation report in non-volatile memory. If a new fault occurs when 64 faults have been stored, the oldest fault report is overwritten by the latest one. This equipment captures current and voltage waveforms and can store up to 24 oscillography waveform data with COMTRADE format. For each trip report, the following items are included:
Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD.
NR ELECTRIC CO., LTD
31
Chapter 5 Metering and Recording
Date and time of fault occurrence
The time resolution is 1ms using the relay internal clock synchronized via GPS if connected. Initiating time is the moment when a protective fault detector operates.
Operating time
An operating time (not including the operating time of output relays) is recorded in the report.
Protective elements
For the details of designation of each protective element, please refer to Table 8.3-1. 5.3.3.3 Fault Waveform Record Capacity and Information The equipment can save 24 pieces of fault waveform oscillogram. If a new fault occurs when 24 fault waveform records have been stored, the latest waveform record overwrites the oldest one. The equipment stores actual samples that are taken at a rate of 24 samples per cycle. The recording time before fault detection initiation is fixed at 2 cycles (40 ms at 50Hz). The recording time after fault detector initiation is fixed at 6 cycles (120 ms at 50Hz) without protection operation or with protection operation within 6 cycles. If any protection element operates after 6 cycles, then the recording time will be prolonged to another 8 cycles (160ms at 50Hz) in order to show continuous 8 cycle waveform after the protection element operates.
5.4 Time Synchronization As the equipment Real Time Clock has small drift per day, therefore, in order to have a correct time for time tagging of event etc., the operator should set its time periodically or it should be synchronized by a master clock. Time synchronization of RCS-974 can be done by three means: z
IRIG-B signal input from external clock device via a RS-485 port named GPS pulse
z
PPM or PPS input via binary input [BI_Pulse_GPS] terminal 601.
z
Clock message from SACADA by using protocol
The external clock device receives the synchronization signal from GPS antenna and then sends to the equipment using IRIG-B standard, differential signal of PPM or PPS by means of so-called “synchronization bus”. When the differential signal is a PPM input, setting [GPS_Pulse] under submenu “EQUIP SETTINGS” should be set as “1”, while if the differential signal is a PPS input, setting [GPS_Pulse] under “EQUIP SETTINGS” should be set as “0”. A specific GPS PULSE input port RS-485 interface is dedicated for this application. SCADA clock synchronization depends on protocol. The synchronization message is directly acquired by the equipment through the SCADA link. Clock message can provide full information for a certain time as a way of year, date, hour, minute and second while pulse input lacks these information.
32
NR ELECTRIC CO., LTD
Chapter 5 Metering and Recording
Therefore, in general applications, clock message is usually combined with PPM or PPS input via binary input, or combined with differential signal of PPM or PPS by means of GPS Pulse input port RS-485 with an accuracy of ±1ms. Moreover, the user could also set time and data directly using the local human-machine interface (HMI) of the equipment. RCS-974 internal clock will then be adjusted accordingly. When the equipment is synchronized, all events in “TRIP REPORT”,” ALM REPORT” and “BI CHG REPORT” and current measurement have a time tag with synchronized attribute.
NR ELECTRIC CO., LTD
33
Chapter 5 Metering and Recording
34
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
Chapter 6 Hardware Description 6.1 Overview RCS-974 is made of a 4U height 19” chassis for panel flush mounting. Components mounted on
ESC
GRP
its front include a 128×64 dot matrix LCD, a 9 button keypad, 8 LED indicators, a signal reset button, a 9 pin connector for communication with PC and a 15 pin connector for analog quantity inputs by HELP-90A during commissioning. A monolithic micro controller is installed in the equipment for these functions. Figure 6.1-1 and Figure 6.1-2 show front view and rear view of RCS-974.
Figure 6.1-1 Front view of RCS-974 Please refer to chapter “HMI Operation Instruction” for detailed description of LED indicators and keypad on frontplate.
Figure 6.1-2
NR ELECTRIC CO., LTD
Rear View RCS-974
35
Chapter 6 Hardware Description
RCS-974AG and RCS-974AG2 shares the same software, only hardware configurations of them have a slight differences as the table shown in below. Table 6.1-1 Hardware configuration of RCS-974 No
Module
RCS-974AG
RCS-974AG2
Description
1
PWR
●
●
DC power supply
2
AI
●
●
AC current and voltage input
3
LPF
●
●
low-pass filter
4
CPU
●
●
control nucleus of the equipment
5
COM
●
●
communication interface
6
BI
●
●
binary input opto-coupler module (DC 24V)
7
BO
●
●
8
BO
●
●
9
IO
●
●
A
IO
●
●
B
IO
●
●
C
IO
●
●
E
RLY (Type A)
●
-
E
RLY (Type B)
-
●
output relay module Mechanical relay modules (Signal input and signal output modules for mechanical protection)
Tripping output modules for mechanical protection
“●” means protection equipment has this module. “-” means protection equipment has no this module.
6.2 Plug-in Modules 6.2.1 Power Supply Module (No.1 PWR) Power supply (250V/220V/125V/110V) shall be connected to pins 101 (+) and 102 (-). Through interference filter and power switch on the rear, DC/DC converter converts the DC power supply to three voltage class +5V, ±12V and +24V to supply to other modules of the equipment. Pin 104 (+) and pin 105 (-) output ± 24V as power supply of OPT. Pin 106 is surge ground. Figure 6.2-1 shows rear view and connector definition of power supply module.
36
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description 1 PWR
101
Pwr -
102
103
Opto L +
104
Opto L -
105
GND
From DC power supply
To 24V OPT module
106
Figure 6.2-1 Pin No.
+
101
-
102
+
104
-
105
Ground
106
+5V Interference filter
Pwr +
±12V
DC/DC
+24V To other modules
Rear view and connector definition of No1 PWR module
Sign
Description
101
Pwr+
Positive pole of power supply for the protective device (220V/110V)
102
Pwr-
Negative pole of power supply for the protective device (220V/110V)
103
Blank
104
Opto_L+
Output of positive pole of power supply for opto-coupler (24V)
105
Opto_L-
Output of negative pole of power supply for opto-coupler (24V)
106
GND
Ground
NOTE: When ordering, please mark the input voltage class of power supply.
6.2.2 AC Input Module (No.2 AI) Ia_1, Ib_1, and Ic_1 are phase currents of CT1 and Ia_2, Ib_2, and Ic_2 are phase currents of CT2. It is assumed that polarity mark of CT installed on line is at line side. Pin 215 is ground point. It should be connected to ground bar. Figure 6.2-2 shows rear view and typical connection of AC module.
NR ELECTRIC CO., LTD
37
Chapter 6 Hardware Description Isolating Transformer Ia_1
AC
Ian_1 Ib_1 Ibn_1
201
202
203
204
Ic_1
205
206
Icn_1
207
208
209
210
Ia_2
211
212
Ian_2
213
214
Ib_2
215
Figure 6.2-2
201 202
203
To LPF
204 205 206
207 208
209
Ibn_2
210
Ic_2
211
Icn_2
212
To LPF
Rear view and connector definition of No.2 AI module
DANGER: Never allow the current transformer (CT) secondary circuit connected to the AC board to be opened while the primary system is live. Opening the CT circuit will produce a dangerously high voltage. Pin No.
Sign
Description
201
Ia_1
Phase A current of first group CT (CT1) (polarity mark)
202
Ian_1
Phase A current of first group CT (CT1)
203
Ib_1
Phase B current of first group CT (CT1) (polarity mark)
204
Ibn_1
Phase B current of first group CT (CT1)
205
Ic_1
Phase C current of first group CT (CT1) (polarity mark)
206
Icn_1
Phase C current of first group CT (CT1)
207
Ia_2
Phase A current of first group CT (CT2) (polarity mark)
208
Ian_2
Phase A current of second group CT (CT2)
209
Ib_2
Phase B current of second group CT (CT2) (polarity mark)
210
Ibn_2
Phase B current of second group CT (CT2)
211
Ic_2
Phase C current of second group CT (CT2) (polarity mark)
212
Icn_2
Phase C current of second group CT (CT2)
213
Not used
214
Not used
215
GND
Ground point connected to ground bar
6.2.3 Low-pass Filter Module (No.3 LPF) This module is used to filter high frequency disturbance from the AC module, regulate the input level and used as an interface between the equipment and dedicated test instrument HELP-90A
38
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
developed by NR. From module AC
Adder
Low-pass filter
Measurement in CPU
From HELP-90A
Adder
Low-pass filter
Measurement in DSP
Figure 6.2-3 Block diagram of module No.3LFP module
6.2.4 Module CPU (No.4 CPU) Module CPU, control nucleus of the equipment, comprises monolithic micro controller CPU and digital signal processor DSP. CPU finishes the following functions:
General fault detection
Event recorder, fault oscillograph recorder (could be printed via serial port)
Print and communication with HMI
Communication with the host of SCADA system of the substation
DSP finishes the following functions:
Algorithm and logic of protection
Sampling rate of the equipment is 24 points per cycle. Parallel real time data is calculated for algorithm and logic of protection at every sampling point. Hence, very high inherent reliability and security are ensured.
6.2.5 Communication Interface Module (No.5 COM) Module COM performs connection between the equipment and the SCADA system or RTU. Three types are available.
NR ELECTRIC CO., LTD
39
Chapter 6 Hardware Description
Figure 6.2-4 Rear view and connector definition of type A of No.5 COM module Pin No.
Sign
501 502
Description A
COM1
503
SHLD
504
A
505
COM2
506 507 508 509
512
No.2 communication port: EIA RS-485 standardized communication interface for connecting with a SAS or a RTU.
B SHLD
CLK SYN
510 511
No.1 communication port: EIA RS-485 standardized communication interface for connecting with a SAS or a RTU.
B
A EIA RS-485 standard interface for GPS clock synchronization
B SHLD RTS
PRT
TXD/B SGND/SHLD
Interface RS-232 for connecting with a printer or RS-485 with printer controller.
RX
Optic Fibre To supervisory system
COM
TX
RX RX
TX
Optic Fibre To supervisory system
RX
TX
TX
501
A
502
B
503
SHLD
504
RTS/A
505 506
TXD/B
To GPS for clock synchronization
To printer or controller
SGND/SHLD
Type 5B
Figure 6.2-5 Rear view and connector definition of type B of No.5 COM module
40
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
Pin No.
Sign RX
COM1
TX RX
COM2 501 502 503
CLK SYN
504 505
Description
TX
506
No.2 communication port: EIA RS-485 optical fibre communication interface for connecting with a SAS or a RTU.
A B
EIA RS-485 standard interface for GPS clock synchronization
SHLD RTS/A
PRT
No.1 communication port: EIA RS-485 optical fibre communication interface for connecting with a SAS or a RTU.
TXD/B SGND/SHLD
Interface RS-232 for connecting with a printer or RS-485 with printer controller.
Figure 6.2-6 Rear view and connector definition of type E of No.5 COM module Pin No.
Sign COM1
COM2
COM3
COM4 501 502
NET1
No.1 communication port: Ethernet standard communication interface for connecting with a SAS or a RTU at rate of 100Mbit/s or 10Mbit/s.
NET2
No.2 communication port: Ethernet standard communication interface for connecting with a SAS or a RTU at rate of 100Mbit/s or 10Mbit/s.
NET3
No.3 communication port: Ethernet standard communication interface for connecting with a SAS or a RTU at rate of 100Mbit/s or 10Mbit/s .
NET4
No.4 communication port: Ethernet standard communication interface for connecting with a SAS or a RTU at rate of 100Mbit/s or 10Mbit/s.
A COM5
503 504
Description
B SHLD
CLK
NR ELECTRIC CO., LTD
A
No.5 communication port: EIA RS-485 standardized communication interface for connecting with a SAS or a RTU. EIA
RS-485
standard
interface
for
GPS
clock 41
Chapter 6 Hardware Description
Pin No. 505
Sign SYN
Description B
506
SHLD
507
RTS/A
508 509
PRT
synchronization.
TXD/B SGND/SHLD
Interface RS-232 for connecting with a printer or RS-485 with printer controller.
All ports used to communicate with SAS support IEC60870-5-103 protocol. Moreover, Ethernet port in COM modules of type 5E also supports IEC61850. From Figure 6.2-4 to Figure 6.2-6 shows rear view of these types and their connector definition. All type are equipped with a RS-485 port for receiving second pulse signal (PPS-pulse per second) from GPS and a port for printer. Printer port could be configured as RS-232 or RS-485 by setting corresponding jumpers on the PCB (RS-232 default). If logic setting [En_Net_Print] is set to “1”, printer port must be set as RS-485. Transmission rate of printer port can be set by the setting [Printer_Baud] and should be the same with baud rate of the printer. NOTE: For the port used to printer or controller, it can be configured as RS-485 or RS-232 by setting corresponding jumper of module COM. The port is configured as RS-232 by shorting PIN 1 and PIN 2 and as RS-485 by shorting PIN 2 and PIN 3. As shown in the following figure.
Figure 6.2-7 Print port configuration There are three options to finish time synchronization: 1 Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact 2 Receiving PPS, PPM and IRIG-B signal via RS-485 3 Receiving time synchronization message from substation automation system
6.2.6 Opto-coupler Module (24Vdc) (No.6 BI) Following figure shows rear view and connector definition of this No.6 module which voltage level is DC 24V.
42
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
Figure 6.2-8
Rear view and connector definition of No.6 BI module
Pin No.
Sign
601
BI_Pulse_GPS
Binary input of time synchronizing pulse
602
BI_Print
Binary input of initiating printing
603
BI_BlkComm
Binary input of blocking communication between the protective device and SAS
604
EBI_PD
Binary input of enabling pole disagreement protection
605
EBI_Dly_MR
Binary input of enabling mechanical protection which operates with time delay (MR1, MR2 and MR3)
606
BI_ExTCtrlBFI
Binary input of an external trip signal to control breaker failure initiation.
607
BI_ExTCtrlPD2
Binary input of an external trip signal to control pole disagreement protection delay 2.
608
BI_52a
Binary input of the normally open auxiliary contact of CB.
609
BI_Resv4
Reserved for future application
610
BI_Resv5
Reserved for future application
611
BI_RstTarg
Binary input of signal reset
612
BI_PD_CB
Pole disagreement position of CB
613
Description
Not used
614
Opto_L+
Input of positive pole of power supply for opto-coupler (24V)
615
Opto_L-
Input of negative pole of power supply for opto-coupler (24V)
NR ELECTRIC CO., LTD
43
Chapter 6 Hardware Description
Pin No.
Sign
Description
617
BI_Resv7
Reserved for future application
618
BI_Resv8
Reserved for future application
619
BI_Resv9
Reserved for future application
620
BI_Resv10
Reserved for future application
621
BI_Resv11
Reserved for future application
622
BI_Resv12
Reserved for future application
623
BI_Resv13
Reserved for future application
624
BI_Resv14
Reserved for future application
Other pins
Not used
NOTE:
[BI_Pulse_GPS] is used with the setting [GPS_Pulse] for receiving clock synchronization signal from GSP or other equipment used clock synchronization.
[BI_BlkComm] is energized, when the equipment is in maintenance or commissioning status. All of the reports will not be sent via communication port then, but local displaying and printing are still working. This link should be open during normal operation condition.
Besides above binary inputs, there are some virtual binary inputs in RCS-974. So-called virtual binary input is the one that is not actually input from equipment external terminal but logically justified by the CPU and can be displayed under menu item “BI STATE”. ♦
[BI_Pwr_Opto]: If the 24V power supply (from terminal 104 on DC board) is connected to terminal 614 and 24V GND (from terminal 105 on DC board) is connected to terminal 615, [BI_Pwr_Opto] is set as “1”. Otherwise, [BI_ Pwr_Opto] is set to 0 and alarm annunciation is issued.
♦
[BI_TrpOut]: If trip output relay is driven to output contact, it is set as “1”. When [BI_TrpOut] is set as “1” over 10s,[Alm_TrpOut] is issued on LCD.
♦
[FD_CPU]: whenever fault detector in CPU module picks up, If [FD_CPU] is been set over 10s, an alarm annunciation message as [Alm_PersistFD] is popped out on the LCD screen. Meanwhile, LED “ALARM” is lit on and normal open contacts of equipment alarm relay are closed to issue remote signal, annunciation signal and signals to event recording device. Even then, RCS-974 can also endure on service.
6.2.7 Output Relay Modules (No.7~No.8 BO) Theses two modules are used to output various signals and issue trip commands. 6.2.7.1 No.7 BO Module Normally open contacts for pole disagreement protection delay 1 and delay 2 respectively are 44
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
closed to issue trip command to trip circuit when the related element operates. Normally open contacts for breaker failure initiation delay 1 and delay 2 respectively are closed to send signal to BFP (breaker failure protection) in other protection equipment as a criterion when the related element operates.
707 702 704 706 708 710 712 714 716 718 720 722 724 726 728 730
701
709
703
715
705
712
707
714
709
716
711
708
713
710
715
727
717
728
719
711
721
713
723
729
725
730
727
717
729
718 719 720 721 722 723 724 725 726
Figure 6.2-9 Pin No.
FDR Signal
705
Annunciation Signal
703
Binary Output of Breaker Failure Initiation delay 1
706
OUT 1
Binary Output of Breaker Failure Initiation delay 2
704
Binary Output of Pole Disagreement Protection delay 2
702
Binary Output of Pole Disagreement Protection delay 1
701
Remote Signal
Figure 6.2-9 shows the rear view and connector definition of No.7 module. Common BO_Fail BO_Alm_Abnor BO_PD Common BO_Fail BO_Alm_Abnor BO_PD Common Port of Local Signal BO_Fail BO_Alm_Abnor BO_PD BO_BFI1_1
BO_BFI1_2
BO_BFI2_1
BO_BFI2_1
BO_PD2Trp_1
BO_PD2Trp_2
BO_PD2Trp_3 BO_PD1Trp_1
BO_PD1Trp_2
Rear view and connector definition of No.7 BO Module
Sign
Description
Remote signals 701,702
BO_Fail
NC contact, is closed when power supply of the equipment is lost or hardware failures are detected, which means equipment is blocked and out of service.
701, 704
BO_Alm_Abnor
NO contact, is closed protective when device is in abnormal condition but still in service, such as CT circuit failure, etc.
701, 706
BO_PD
NO contact, is closed when pole disagreement protection operates.
Annunciation signals 703,705
BO_Fail
NR ELECTRIC CO., LTD
NC contact, is closed when power supply of the equipment is lost or hardware failures are detected, which means equipment is blocked and out of service.
45
Chapter 6 Hardware Description
Pin No.
Sign
Description
703,707
BO_Alm_Abnor
NO contact, is closed protective when device is in abnormal condition but still in service, such as CT circuit failure, etc.
703,709
BO_PD
NO magnetic latched contact, is closed when pole disagreement protection operates.
FDR signals (Fault and disturbance recording signals) 715,712
BO_Fail
NC contact, is closed when power supply of the equipment is lost or hardware failures are detected, which means equipment is blocked and out of service.
715,714
BO_Alm_Abnor
NO contact, is closed protective when device is in abnormal condition but still in service, such as CT circuit failure, etc.
715,716
BO_PD
NO contact, is closed when pole disagreement protection operates.
Binary outputs of breaker failure initiation 708,710
BO_BFI1_1
727,728
BO_BFI1_2
711,713
BO_BFI2_1
729,730
BO_BFI2_2
NO contact, it will be closed when breaker failure initiation delay 1 operates. NO contact, it will be closed when breaker failure initiation delay 2 operates.
Tripping outputs of pole disagreement protection 717,718
BO_PD2Trp_1
719,720
BO_PD2Trp_2
721,722
BO_PD2Trp_3
723,724
BO_PD1Trp_1
725,726
BO_PD1Trp_2
NO contact, it will be closed when pole disagreement protection delay 2 operates. NO contact, it will be closed when pole disagreement protection delay 1 operates.
NOTE: NO contact: normally open contact; NC contact: Normally closed contact. Same meanings to other NO and NC contacts appeared in following description. 6.2.7.2 No.8 BO Module This module is used to output various signals and issue trip commands with time delay for MR1, MR2 and MR3 mechanical protections which operate with their time delays respectively. Figure 6.2-10 shows the rear view and connector definition of No.8 BO module.
46
NR ELECTRIC CO., LTD
Initiation Annunciation Signal Tripping signal
FDR Signal
Remote Signal
Chapter 6 Hardware Description
Figure 6.2-10 Pin No.
Rear view and connector definition of No.8 BO module
Sign
Description
Remote signals 802,808
BO_Dly_MR1
NO contact, is closed when mechanical protection of MR1 operates with a time delay.
802,810
BO_Dly_MR2
NO contact, is closed when mechanical protection of MR2 operates with a time delay.
802,806
BO_Dly_MR3
NO contact, is closed when mechanical protection of MR3 operates with a time delay.
FDR signals (Fault and disturbance recording signals 813,815
BO_Dly_MR1
NO contact, is closed when mechanical protection of MR1 operates with a time delay.
818,812
BO_Dly_MR2
NO contact, is closed when mechanical protection of MR2 operates with a time delay.
818,814
BO_Dly_MR3
NO contact, is closed when mechanical protection of MR3 operates with a time delay.
Annunciation signals (magnetic latched contact) 827,817
BO_Dly_MR1
NO contact, is closed when mechanical protection of MR1 operates with a time delay.
827,819
BO_Dly_MR2
NO contact, is closed when mechanical protection of MR2 operates
NR ELECTRIC CO., LTD
47
Chapter 6 Hardware Description
Pin No.
Sign
Description with a time delay.
827,821
BO_Dly_MR3
NO contact, is closed when mechanical protection of MR3 operates with a time delay.
827,825
BO_Dly_MR
NO contact, is closed when mechanical protection of MR1, MR2 or MR3 operates with a time delay.
Binary outputs used to initiate trip output relay 828, 820
BO_Dly_MR1
NO contact, is closed when mechanical protection of MR1 operates with a time delay.
828,822
BO_Dly_MR2
NO contact, is closed when mechanical protection of MR2 operates with a time delay.
828,824
BO_Dly_MR3
NO contact, is closed when mechanical protection of MR3 operates with a time delay.
Binary output for reset command used inside of equipment 829
TargetReset+
830
TargetReset-
NO contact, it will be closed when the button [TargetReset] on the front panel is pushed down or binary input [BI_RstTarg] is energized. Pin 829 is connected to positive pole of DC power supply Pin 830 is connected to pins 901, A01, B01 and C01 of following output relay modules
6.2.8 Mechanical Relay Modules (No.9~No.B IO) 6.2.8.1 No.9 IO Module This module is used to output various signals, issue trip commands and accept reset command. Figure 6.2-11 shows the rear view and connector definition of No.9 IO module.
48
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description From power supply + From power supply -
IO
TargetReset-
830 901
Reset Signal
925
908 910 912 914 916 918 920 922 924 926 928 930
903
905
905
907
907
909
909
911
910
913
902
915
904
917
906
919
920
921
912
923
914
925
916
927
930
929
922 924 926 919 911 913 915
Figure 6.2-11 Pin No.
Binary Input Signals for Mechanical protection
High Voltage
906
903
Pwr +
Module Power Input
Input of PDP Signal
Pwr BI_MR1 BI_MR2 BI_MR3 BI_PD_CB Common
Annunciation Signal
904
929
BO_MR1 BO_MR2 BOMR3 Common
MR_Trip Comd. FDR Recording Remote Signal
902
901
ResetInput
BO_MR1 BO_MR2 BO_MR3 Common BO_MR1 BO_MR2 BO_MR3 Common BO_MR1 BO_MR2 BO_MR3
Rear view and connector definition of No.9 IO module
Sign
Description
901
Reset Input
When a reset signal arrives, LEDs labeled as “MECH1”, “MECH2” and “MECH3” are reset to be extinguished.
925
Pwr+
Positive pole of power of the board connected to DC power supply
926
Pwr-
Negative pole of power of the board connected to DC power supply
903
BI_MR1
Binary input of mechanical protection of MR1
905
BI_MR2
Binary input of mechanical protection of MR1
907
BI_MR3
Binary input of mechanical protection of MR3
909
BI_PD_CB
Binary input of pole disagreement protection of circuit breaker, is also called binary input of mechanical protection of MR4
Annunciation signals (magnetic latched contact) 910,902
BO_MR1
NO contact, is closed when binary input [BI_MR1] is energized.
910,904
BO_MR2
NO contact, is closed when binary input [BI_MR2] is energized.
910,906
BO_MR3
NO contact, is closed when binary input [BI_MR3] is energized.
Remote Signals 920,912
BO_MR1
NO contact, is closed when binary input [BI_MR1] is energized.
920,914
BO_MR2
NO contact, is closed when binary input [BI_MR2] is energized.
920,916
BO_MR3
NO contact, is closed when binary input [BI_MR3] is energized.
FDR signals (Fault and disturbance recording signals) 930,922
BO_MR1
NR ELECTRIC CO., LTD
NO contact, is closed when binary input [BI_MR1] is energized. 49
Chapter 6 Hardware Description
Pin No.
Sign
Description
930,924
BO_MR2
NO contact, is closed when binary input [BI_MR2] is energized.
930,926
BO_MR3
NO contact, is closed when binary input [BI_MR3] is energized.
Binary outputs used to initiate tripping relay 919,911
BO_MR1
NO contact, is closed when binary input [BI_MR1] is energized. Not used normally.
919,913
BO_MR2
NO contact, is closed when binary input [BI_MR2] is energized. Not used normally.
919,915
BO_MR3
NO contact, is closed when binary input [BI_MR3] is energized. Not used normally.
6.2.8.2 No.A IO Module This module is used to output various signals, issue trip commands and accept reset command. Figure 6.2-12 shows the rear view and connector definition of No.A IO module From power supply + From power supply 830 A01
IO
A25 A29 A03 A05
A02 A04 A06 A08 A10 A12 A14 A16 A18 A20 A22 A24 A26 A38 A30
A01 50
Module Power Input
Binary Input Signals of Mechanical protection
ResetInput Pwr+ Pwr BI_MR5 BI_MR6
A01
A07
A03
A09
A05
A10
Common
A07
A02
BO_MR5
A09
A04
BO_MR6
A11
A06
BO_MR7
A13
A08
BO_MR8
A15
A20
Common
A17
A12
BO_MR5
A19
A14
BO_MR6
A21
A16
BO_MR7
A23
A18
Trip_MR8
A25
A30
Common
A27
A22
BO_MR5
A29
A24
BO_MR6
A26
BO_MR7
Figure 6.2-12 Pin No.
TargetResetReset Signal
Sign ResetInput
BI_MR7 BI_MR8
A28
BO_MR8
A19
Common
A11
BO_MR5
A13
BO_MR6
A15
BO_MR7
A17
BO_MR8
Rear view and connector definition of No.A IO module Description
When a reset signal arrives, LED labeled as “MECH5”, “MECH6”, “MECH7” and “MECH8” are reset to be extinguished. NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
Pin No.
Sign
Description
A25
Pwr+
Positive pole of power of the board connected to DC power supply
A26
Pwr-
Negative pole of power of the board connected to DC power supply
A03
BI_MR5
Binary input of mechanical protection of MR5
A05
BI_MR6
Binary input of mechanical protection of MR6
A07
BI_MR7
Binary input of mechanical protection of MR7
A09
BI_MR8
Binary input of mechanical protection of MR8
Annunciation signals (magnetic latched contact) A10,A02
BO_MR5
NO contact, is closed when binary input [BI_MR5] is energized.
A10,A04
BO_MR6
NO contact, is closed when binary input [BI_MR6] is energized.
A10,A06
BO_MR7
NO contact, is closed when binary input [BI_MR7] is energized.
A10,A08
BO_MR8
NO contact, is closed when binary input [BI_MR8] is energized.
Remote Signals A20,A12
BO_MR5
NO contact, is closed when binary input [BI_MR5] is energized.
A20,A14
BO_MR6
NO contact, is closed when binary input [BI_MR6] is energized.
A20,A16
BO_MR7
NO contact, is closed when binary input [BI_MR7] is energized.
A20,A18
BO_MR8
NO contact, is closed when binary input [BI_MR8] is energized.
FDR signals (Fault and disturbance recording signals) A30,A22
BO_MR5
NO contact, is closed when binary input [BI_MR5] is energized.
A30,A24
BO_MR6
NO contact, is closed when binary input [BI_MR6] is energized.
A30,A26
BO_MR7
NO contact, is closed when binary input [BI_MR7] is energized.
A30,A28
BO_MR8
NO contact, is closed when binary input [BI_MR8] is energized.
Binary outputs used to initiate tripping relay A19,A11
BO_MR5
NO contact, is closed when binary input [BI_MR5] is energized.
A19,A13
BO_MR6
NO contact, is closed when binary input [BI_MR6] is energized.
A19,A15
BO_MR7
NO contact, is closed when binary input [BI_MR7] is energized.
A19,A17
BO_MR8
NO contact, is closed when binary input [BI_MR8] is energized.
6.2.8.3 No.B IO Module This module is used to output various signals, issue trip commands and accept reset command. Figure 6.2-13 shows the rear view and connector definition of No.B IO module
NR ELECTRIC CO., LTD
51
Chapter 6 Hardware Description From power supply + From power supply TargetReset-
830 B01
IO
B25 B29 B03
B02 B04 B06 B08 B10 B12 B14 B16 B18 B20 B22 B24 B26 B28 B30
B01 B03 B05
B07 B09
Module Power Input
Binary Input Signals of Mechanical protection
ResetInput Pwr + Pwr BI_MR9 BI_MR10 BI_MR11 BI_MR12
B07
B10
B09
B02
BO_MR9
B11
B04
BO_MR10
B13
B06
BO_MR11
B15
B08
BO_MR12
B17
B20
Commonl
B19
B12
BO_MR9
B21
B14
BO_MR10
B23
B16
BO_MR11
B25
B18
BO_MR12
B27
B30
Common
B29
B22
BO_MR9
B24
BO_MR10
Figure 6.2-13 Pin No.
B05
Reset Signal
Common
B26
BO_MR11
B28
BO_MR12
B19
Common
B11
BO_MR9
B13
BO_MR10
B15
BO_MR11
B17
BO_MR12
Rear view and connector definition of No.B IO module
Sign
Description
B01
ResetInput
When a reset signal arrives, LED labeled as “MECH9”, “MECH10” “MECH11” and “MECH12” are reset to be extinguished.
B25
Pwr+
Positive pole of power of the board connected to DC power supply
B26
Pwr-
Negative pole of power of the board connected to DC power supply
B03
BI_MR9
Binary input of mechanical protection of MR9
B05
BI_MR10
Binary input of mechanical protection of MR10
B07
BI_MR11
Binary input of mechanical protection of MR11
B09
BI_MR12
Binary input of mechanical protection of MR12
Annunciation signals (magnetic latched contact) B10,B02
BO_MR9
NO contact, is closed when binary input [BI_MR9] is energized.
B10,B04
BO_MR10
NO contact, is closed when binary input [BI_MR10] is energized.
B10,B06
BO_MR11
NO contact, is closed when binary input [BI_MR11] is energized.
B10,B08
BO _MR12
NO contact, is closed when binary input [BI_MR12] is energized.
Remote Signals B20,B12
BO_MR9
NO contact, is closed when binary input [BI_MR9] is energized.
B20,B14
BO_MR10
NO contact, is closed when binary input [BI_MR10] is energized.
B20,B16
BO_MR11
NO contact, is closed when binary input [BI_MR11] is energized.
B20,BA18
BO _MR12
NO contact, is closed when binary input [BI_MR12] is energized.
52
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
Pin No.
Sign
Description
FDR signals (Fault and disturbance recording signals) B30,B22
BO_MR9
NO contact, is closed when binary input [BI_MR9] is energized.
B30,B24
BO_MR10
NO contact, is closed when binary input [BI_MR10] is energized.
B30,B26
BO_MR11
NO contact, is closed when binary input [BI_MR11] is energized.
B30,B28
BO _MR12
NO contact, is closed when binary input [BI_MR12] is energized.
Binary outputs used to initiate tripping relay B19,B11
BO_MR9
NO contact, is closed when binary input [BI_MR9] is energized.
B19,B13
BO_MR10
NO contact, is closed when binary input [BI_MR10] is energized. Not used normally.
B19,B15
BO_MR11
NO contact, is closed when binary input [BI_MR11] is energized. Not used normally.
B19,B17
BO_MR12
NO contact, is closed when binary input [BI_MR12] is energized. Not used normally.
6.2.8.4 No.C IO Module This module is used to output various signals, issue trip commands and accept reset command. Figure 6.2-14 shows the rear view and connector definition of No.C IO module
From power supply + From power supply -
IO 830
TargetReset-
C01
C10 C12 C14 C16 C18 C20 C22 C24 C26 C28 C30
C07 C09 C11 C13 C15 C17 C19 C21 C23 C25 C27 C29
C05 C07 C09 C10 C02 C04 C06 C08 C20 C12 C14 C16 C18 C30 C22 C24 C26 C28
Figure 6.2-14
NR ELECTRIC CO., LTD
Binary Input Signals of Mechanical protection
High Voltage
C08
C05
C03
ResetInput
Module Power Input
Annunciation Signal
C06
C03
C29
Remote Signal
C04
C01
FDR Recording
C02
C25
Reset Signal
Pwr + Pwr BI_MR13 BI_MR14 BI_MR15 BI_MR16
Common BO_MR13 BO_MR14 BO_MR15 BO_MR16 Common BO_MR13 BO_MR14 BO_MR15 BO_MR16 Common BO_MR13 BO_MR14 BO_MR15 BO_MR16
Rear view and connector definition of No.C IO module
53
Chapter 6 Hardware Description
Pin No.
Sign
Description
C01
ResetInput
When a reset signal arrives, LED labeled as [MECH13], [MECH14], [MECH15] and [MECH16] are reset to be extinguished.
C25
Pwr+
Positive pole of power of the board connected to DC power supply
C26
Pwr-
Negative pole of power of the board connected to DC power supply
C03
BI_MR13
Binary input of mechanical protection of MR13
C05
BI_MR14
Binary input of mechanical protection of MR14
C07
BI_MR15
Binary input of mechanical protection of MR15
C09
BI_MR16
Binary input of mechanical protection of MR16
Annunciation signals (magnetic latched contact) C10,B02
BO_MR13
NO contact, is closed when binary input [BI_MR13] is energized.
C10,B04
BO_MR14
NO contact, is closed when binary input [BI_MR14] is energized.
C10,B06
BO_MR15
NO contact, is closed when binary input [BI_MR15] is energized.
C10,B08
BO _MR16
NO contact, is closed when binary input [BI_MR16] is energized.
Remote Signals C20,B12
BO_MR13
NO contact, is closed when binary input [BI_MR13] is energized.
C20,B14
BO_MR14
NO contact, is closed when binary input [BI_MR14] is energized.
C20,B16
BO_MR15
NO contact, is closed when binary input [BI_MR15] is energized.
C20,BA18
BO _MR16
NO contact, is closed when binary input [BI_MR16] is energized.
FDR signals (Fault and disturbance recording signals) C30,B22
BO_MR13
NO contact, is closed when binary input [BI_MR13] is energized.
C30,B24
BO_MR14
NO contact, is closed when binary input [BI_MR14] is energized.
C30,B26
BO_MR15
NO contact, is closed when binary input [BI_MR15] is energized.
C30,B28
BO _MR16
NO contact, is closed when binary input [BI_MR16] is energized.
Binary outputs used to initiate trip output relay C19,B11
BO_MR13
NO contact, is closed when binary input [BI_MR13] is energized.
C19,B13
BO_MR14
NO contact, is closed when binary input [BI_MR14] is energized.
C19,B15
BO_MR15
NO contact, is closed when binary input [BI_MR15] is energized.
C19,B17
BO _MR16
NO contact, is closed when binary input [BI_MR16] is energized.
Binary outputs used to initiate trip output relay C19,C11
BO_MR13
NO contact, is closed when binary input [BI_MR13] is energized. Not used normally.
C19,C13
BO_MR14
NO contact, is closed when binary input [BI_MR14] is energized. Not used normally.
C19,C15
BO_MR15
NO contact, is closed when binary input [BI_MR15] is energized. Not used normally.
C19,C17
BO_MR16
NO contact, is closed when binary input [BI_MR16] is energized. Not used normally.
6.2.9 Tripping Output Module (No.E RLY) This module is used to output trip commands to trip circuit breakers. There are two types module to be optional for No.E RLY. 54
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
NOTE: Type A and type B of No.E RLY module are equipped for RCS-974AG and RCS-974AG2 respectively. 6.2.9.1 Type A of No.E RLY All the trip signals issued by No.8 BO module, No.9~No.C IO modules should be led to pin E01 and/ E02 via several isolator links which are mounted on the panel and can be used to enable or disable corresponding tripping output contacts. Figure 6.2-15 shows the rear view and connection definition of this module. From power supply + From power supply E29 E30 E01 E02
RLY
E03 E04 E05
E02 E04 E06 E08 E10 E12 E14 E16 E18 E20 E22 E24 E26 E28 E30
E06
E01
E07
E03
E08
E05
E09
E07
E10
E09
E11
E11
E12
E13
E14
E17
E15
E19
E16
E21
E17
E23
E18
E25
E19
E27
E20
E29
Pwr TrpInput1 TrpInput2 BO_Trp_1
BO_Trp_2
BO_Trp_3
BO_Trp_4
BO_Trp_5
BO_Trp_6 BO_Trp_7
BO_Trp_8
BO_Trp_9
E21
E23 E24 E25 E26
Pin No.
MR Trip Signal Input (high voltage +)
Pwr +
E13
E15
E22
Figure 6.2-15
Module Power Input
BO_Trp_10 BO_Trp_11
BO_Trp_12
E27
Common
E28
BO_LossPwr_MR
Rear view and connector definition of type A of No.E RLY module
Sign
Description
E29
Pwr+
Positive pole of power of the board connected to DC power supply
E30
Pwr-
Negative pole of power of the board connected to DC power supply
MR Trip Signal Input E01
TrpInput1
Trip signal input to initiate the 1st group of MR trip output contacts
E02
TrpInput2
Trip signal input to initiate the 2nd group of MR trip output contacts
1st Group of MR Trip Output Contacts NR ELECTRIC CO., LTD
55
Chapter 6 Hardware Description
Pin No.
Sign
E03,E04
BO_Trp_1
E05,E06
BO_Trp_2
E07,E08
BO_Trp_3
E09,E10
BO_Trp_4
E11,E12
BO_Trp_5
E13,E14
BO_Trp_6
Description
NO contacts, are closed when pin E01 is energized by DC high voltage.
2nd Group of MR Trip Output Contacts E15,E16
BO_Trp_7
E17,E18
BO_Trp_8
E19,E20
BO_Trp_9
E21,E22
BO_Trp_10
E23,E24
BO_Trp_11
E25,E26
BO_Trp_12
NO contacts, are closed when pin E01 is energized by DC high voltage.
Annunciation signals (magnetic latched contact) E27,E28
BO_LossPwr_MR
NC contact, is closed when power of this boardis lost.
6.2.9.2 Type B of No.E RLY This is used to output trip commands to trip circuit breakers. All the trip commands issued No.8 BO module and No.9~No.C IO mdoules should be led to pin E01, E02, E03, E04, E05 and E06 via several isolator links which are mounted on the panel and can be used to enable or disable corresponding tripping output contacts. This module is designed as hardware trip matrix module. See Figure 6.3-3 for schematic diagram of trip matrix and Figure 6.2-17 for rear view and connector definition information.
56
NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
E01
E02
E03
E04
E05
E06
E29
E27
E30
+Heavy voltage
output1
output2
output3
output4
output5
Figure 6.2-16
E28
-Heavy voltage
E07
E08
E09
E10
E11
E12
E13
E14
E15
E16
E17
E18
E19
E20
E21
E22
E23
E24
E25
E26
Schematic diagram of trip matrix
As shown in above figure, the trip matrix is accomplished by diodes. The factory default setting is that any input of the trip matrix will activate all 5 output relays. Whenever any on site modification is required, it is easy to configure the trip matrix by remove or keep the relevant diode. The point to note here is that every output relay has two normal open contacts. Additionally, commissioning test is absolutely necessary when any modification is done on the trip matrix. Refer to chapter 8 for more description about commissioning. Moreover, as presented in above figure, resistor and capacitors series circuit paralling on the two ends of OUTPUT RELAY1 and OUTPUT RELAY 2 are used to spread the tripping command level. Theoretically speaking, after the vanishment of trip matrix inputs, tripping command issued by OUTPUT RELAY 1 and OUTPUT RELAY 2 are extended more than 11ms for rated voltage 110V /125V and 22ms for the rated voltage 220V/250V.
NR ELECTRIC CO., LTD
57
Chapter 6 Hardware Description From power supply + From power supply E29 E30
Module Power Input
MR Trip Signal Input (high voltage +)
E01 E02
RLY
E03 E04 E05
E10 E12 E14 E16 E18 E20 E22 E24 E26 E28 E30
E08
E07
E09
E09
E10
E11
E11
E13
E12
E15
E13
E17
E14
E19
E15
E21
E16
E23
E17
E25
E18
E27
E19
E29
E20 E21 E22
E25
Group 5
E23 E24
E28
Figure 6.2-17 Pin No.
Annunication Signal
E26 E27
Pwr TrpInput1 TrpInput2 TrpInput3 TrpInput4 TrpInput5 TrpInput6 BO_Trp_1-1
Group 1
E08
E05
Group 2
E06
E03
E07
Group 3
E04
E06
Group 4
E02
E01
Pwr +
BO_Trp_1-2
BO_Trp_2-1
BO_Trp_2-1
BO_Trp_3-1
BO_Trp_3-2 BO_Trp_4-1
BO_Trp_4-2
BO_Trp_5-1
BO_Trp_5-2 Common BO_LossPwr_MR
Rear view and connector definition of type B of No.E RLY module
Sign
Description
E29
Pwr+
Positive pole of power of the board connected to DC power supply
E30
Pwr-
Negative pole of power of the board connected to DC power supply
MR Trip Signal Input E01
TrpInput 1
Trip signal Input to initiate MR trip output relays.
E02
TrpInput 2
Trip signal Input to initiate MR trip output relays.
E03
TrpInput 3
Trip signal Input to initiate MR trip output relays.
E04
TrpInput 4
Trip signal Input to initiate MR trip output relays.
E05
TrpInput 5
Trip signal Input to initiate MR trip output relays.
E06
TrpInput 6
Trip signal Input to initiate MR trip output relays.
MR Trip Output Contacts E07,E08
BO_Trp_1-1
E09,E10
BO_Trp_1-2
E11,E12
BO_Trp_2-1
E13,E14
BO_Trp_2-1
E15,E16
BO_Trp_3-1
E17,E18
BO_Trp_3-2
58
NO contacts, 1st group of MR trip output contacts NO contacts, 2nd group of MR trip output contacts NO contacts, 3rd group of MR trip output contacts NR ELECTRIC CO., LTD
Chapter 6 Hardware Description
Pin No.
Sign
E19,E20
BO_Trp_4-1
E21,E22
BO_Trp_4-2
E23,E24
BO_Trp_5-1
E25,E26
BO_Trp_5-2
Description NO contacts, 4th group of MR trip output contacts NO contacts, 5th group of MR trip output contacts
Annunciation signals (magnetic latched contact) E27,E28
BO_LossPwr_MR
NC contact, is closed when power of this module is lost.
6.3 Scheme Diagram of Input and Output of MR According to the difference of the importance of transformer MR protection, the mechanical signals are classified into three groups described in the following sections. They may lead to different equipment operation. (1) Some MR signals (MR5~MR9) needed to issue trip command directly are connected to pins A03, A05, A07, A09, and B03 to initiate trip output relays without time delay and send out warning signals immediately. (2) Some MR signals (MR1~MR3) needed to issue trip command with time delay are connected to pins 903, 905, 907 to initiate trip output relays with time delay which can be configured in the equipment, and send out warning signals immediately. This group, is (3) Some MR signals (MR10~MR16) only needed to issued warning signal are connected to pins B05, B07, B09, C03, C05, C07, C09 to send out warning signals immediately. Binary input of pole disagreement protection [BI_PD_CB] has two input pins: 909 for high voltage input, and 612 for 24Vdc input.
NR ELECTRIC CO., LTD
59
Chapter 6 Hardware Description Ext._Pwr -
Ext._Pwr +
Contact from Transformer MR BI_MR1
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
R
RELAY
903
BI_MR2
929
905
BI_MR3 907 BI_PD_CB
909
BI_MR5
A03
Binary Input of Mechanical Signals
BI_MR6
A29
A05
BI_MR7
A07
BI_MR8
A09
BI_MR9
B03
BI_MR10
B19
B05
BI_MR11 B07 BI_MR12
B09
BI_MR13 C03 BI_MR14
C29
C05
BI_MR15 C07 BI_MR16 C09
Figure 6.3-1
MR input signals association diagram of RCS-974AG/AG2 Ext._Pwr +
Ext._Pwr -
Signals of MR protection without Time Delay to Initiate Trip Output Relay
Signals of MR protection with Time Delay to Initiate Trip Output Relay
Isolator Link BO_Dly_MR1
828
822
R R
Output Relay Group2
E01
BO_Dly_MR2
E30
E02
BO_Dly_MR3 824 Ext._Pwr + BO_MR5 A19
A11
BO_MR6 A13 BO_MR7 A15 BO_MR8 A17 BO_MR9 B19
Figure 6.3-2
60
820
Output Relay Group1
B11
MR tripping output contacts association diagram of RCS-974AG
NR ELECTRIC CO., LTD
Signals of MR protection without Time Delay to Initiate Trip Output Relay
Signals of MR protection with Time Delay to Initiate Trip Output Relay
Chapter 6 Hardware Description
Figure 6.3-3
MR tripping output contacts association diagram of RCS-974AG2
NOTE: MR Tripping output contacts association diagram of RCS-974AG (showed in Figure 6.3-3) is different to that of other RCS-974AG2 (showed in Figure 6.3-2), and tripping matrix is introduced in details in section 6.2.9.2.
6.4 Output Signals RCS-974 provides three kinds of signals for every event, remote signals, annunciation signals and FDR signals. The event may be a mechanical signal from transform mechanical relay, an equipment failure, an equipment alarm or activation of pole-disagreement protection element. All the signals are issued by closing the normal open contacts of signal relays whenever an event happens. What matters is that the local signal relay is a bistable-relay, whenever an event happens, the normal open contact of this relay will pick up and latch. The annunciation signal relay will not drop off automatically after the event disappears except to reset manually. Annunciation signal relays on No.7 BO and No.8 BO modules can be reset by the reset button on the equipment front panel or by the binary input [BI_RstTarg]. And annunciation signals on IO module can be reset by a reset input terminal.
NR ELECTRIC CO., LTD
61
Chapter
62
6
Hardware
Description
NR ELECTRIC CO., LTD
Chapter 7 Settings
Chapter 7 Settings The equipment has 30 setting groups for protection to coordinate with the mode of power system operation, one of which is assigned to be active. However, equipment parameters are common for all protection setting groups. NOTE All current settings in this chapter are secondary current converted from primary current by CT ratio.
7.1 Equipment Settings Table 7.1-1 Equipment setting list No.
Setting Item
Description
Range
1
Active_Grp
Current active group of setting
0~29
2
Comm_Addr
Communication address of the equipment
0~254
3
COM1_Baud
Baud rate of rear RS-485 port 1
4800, 9600, 19200,38400 bit/s
4
COM2_Baud
Baud rate of rear RS-485 port 2
4800, 9600, 19200,38400 bit/s
5
Printer_Baud
Baud Rate of rear printer port
4800, 9600, 19200,38400 bit/s
6
Debug_Baud
Baud rate of front RS-232 port for commissioning
4800, 9600 bit/s
7
fn
System frequency
8
I2n
Secondary rated current of CT
nominal
Remark
50,60 Hz 1 A or 5 A
9
Protocol
communication protocol
0~1
0: IEC 60870-5-103 or IEC 61850 1: LFP
10
Language
Select default displaying language
0~1
0:Chinese 1:English
11
Equip_ID
The identity of substation or plant
12
En_Net_Print
Enable/disable
NR ELECTRIC CO., LTD
a
network
1 or 0
0: net shared printer
63
Chapter 7 Settings
No.
Setting Item
Description
Range
printing
1: local printer
13
En_Auto_Print
Enable/disable automatic printing
1 or 0
14
GPS_Pulse
GPS clock synchronizing pulse
0~1
En_Remote_Cfg
Enable/disable configuring remotely
15
Explanation of Settings description
1.
Active_Grp
Remark
setting
1 or 0
0: automatic print 1: manual Print 0: PPS 1: PMS 0: local configuring 1: local and remote configuring
Current active group of setting; Thirty setting groups are provided for selecting, group number from 0 to 29. Equipment setup is shared for 30 setting groups and only protection settings are independent. 2.
Comm_Addr
Communication address between the equipment with the SCADA or RTU via RS-485; 3.
COM1_Baud, COM2_Baud, Printer_Baud
The three settings are the baud rate of RS-485 serial port 1, the baud rate of RS-485 serial port 2 and the baud rate of printer port on the rear panel of No.5 COM board respectively. When configuring [COM1_Baud], [COM2_Baud], please refer to section 6.2.5 for detailed port definition of different type communication modules. COM Type
4.
EQUIP SETTINGS
IP ADDRESS
[COM1_Baud]
[COM2_Baud]
[IP_Addr1]
[IP_Addr2]
[IP_Addr3]
[IP_Addr4]
A
RS-485-1
RS-485-2
Invalid
Invalid
Invalid
Invalid
B
Optic fibre-1
Optic fibre-1
Invalid
Invalid
Invalid
Invalid
E
Don’t modify
RS-485
Ethernet-1
Ethernet-2
Ethernet-3
Ethernet-4
Debug_Baud
Baud rate of front communication port (RS-232 port)for local communication with equipment on PC via the software RCSPC. 5.
En_Net_Print
If it is set as “1”, the equipment’s network printing function is enabled. Here, the printing serial port on rear panel of No.5 COM board must be configured as RS-485 way by setting dependent jumpers. On the contrary, if it is set as “0”, its network printing function is disabled. Report and settings can be printed by its directly connected local printer. At this time, the printing serial port on rear panel of No.5 COM board must be configured as RS-232 way by setting dependent jumpers.
64
NR ELECTRIC CO., LTD
Chapter 7 Settings
Refer to section 6.2.5 for how to set dependent jumpers. 6.
En_Auto_Print
When it is set as “1”, the equipment will print trip report automatically once a tripping command is issued. On the contrary, if it is set as “0”, the equipment’s automatic printing function is disabled. 7.
Protocol
“0” means IEC 60870-5-103 protocol or IEC61850 protocol is selected. Which protocol is selected depends on the type of No.5 COM board. If type A or B is configured, then IEC 60870-5-103 is selected as communication protocol, and if type E is used, the IEC 61850 is selected. “1”: LFP protocol, a proprietary protocol developed by NR. 8.
GPS_Pulse
It is used together with a binary input [BI_Pulse_GPS] on No.6 BI board or with GPS clock synchronization port on No.5 COM board. If [GPS_Pulse] is set as “1”, the pulse input is pulse per minute (PPM), while if [GPS_Pulse] is set as “0”, the pulse input is pulse per second (PPS). 9.
En_Remote_Cfg
If it is set as “1”, the equipment’s settings can be remotely configured by substation automation system depending on the protocol. If it is set as “0”, the function is disabled. The point to be noted here is that no matter [En_Remote_Cfg] is set as “0” or “1”, equipment settings in submenu “EQUIP SETTINGS” can never be remotely modified.
7.2 Protection Settings NOTE: All the protection settings in Table 7.2-1 must be configured on the base of secondary value, where [I2n] is the secondary rated current of CT (refer to section 7.1). NOTE: Zero sequence current setting is configured according to 3I0 and negative sequence current setting is configured according to I2. Table 7.2-1 Protection settings list No.
Setting Item
Description
Range
Step
1
I1n_CT1
primary value of the first group of CT
0kA~650kA
0.01kA
2
I1n_CT2
primary value of the second group of CT
0kA~650kA
0.01kA
3
I_ROC_PD_CT1
zero sequence current setting of the first group of CT for pole disagreement protection
(0.01 ~ 20 )×In
0.01A
4
I_NegOC_PD_CT1
Negative sequence current setting
(0.01 ~ 20 )×In
0.01A
NR ELECTRIC CO., LTD
65
Chapter 7 Settings
No.
Setting Item
Description
Range
Step
I_ROC_PD_CT2
zero sequence current setting of the second group of CT for pole disagreement protection
(0.01 ~ 20 )×In
0.01A
6
I_NegOC_PD_CT2
Negative sequence current setting of the second group of CT for pole disagreement protection
(0.01 ~ 20 )×In
0.01A
7
t_PD1
time delay for pole disagreement protection delay 2
0s - 10s
0.01s
8
t_PD2
time delay for pole disagreement protection delay 2
0s ~ 10s
0.01s
I_OC_BFI_CT1
overcurrent setting of the first group of CT for breaker failure initiation
(0.01 ~ 20 )×In
0.01A
I_ROC_BFI_CT1
zero sequence current setting of the first group of CT for breaker failure initiation element
(0.01 ~ 20 )×In
0.01A
I_NegOC_BFI_CT1
negative sequence current setting of the first group of CT for breaker failure initiation
(0.01 ~ 20 )×In
0.01A
I_OC_BFI_CT2
overcurrent setting of the second group of CT for breaker failure initiation
(0.01 ~ 20 )×In
0.01A
I_ROC_BFI_CT2
zero sequence current setting of the second group of CT for breaker failure initiation
(0.01 ~ 20 )×In
0.01A
14
I_NegOC_BFI_CT2
negative sequence current setting of the second group of CT for breaker failure initiation
(0.01 ~ 20 )×In
0.01A
15
t_BFI1
time delay for initiation delay 1
breaker
failure
0s - 10s
0.01s
16
t_BFI2
time delay for initiation delay 2
breaker
failure
0s ~ 10s
0.01s
17
t_FixDly_MR1
fixed time delay of MR1 for tripping
0s ~ 10s
0.01s
18
t_MR1
time delay of MR1 for tripping
0min ~ 100min
0.01min
19
t_MR2
time delay of MR2 for tripping
0min ~ 100min
0.01min
20
t_MR3
time delay of MR3 for tripping
0min ~ 100min
0.01min
of the first group of CT for pole disagreement protection 5
9
10
11
12
13
Logic setting:
66
NR ELECTRIC CO., LTD
Chapter 7 Settings
No.
Setting Item
Description
Range
Step
“1” for enabling and “0” for disabling corresponding protection or function element 21
En_PD1
enable pole protection delay 1
disagreement
22
En_PD2
enable pole protection delay 2
disagreement
23
En_ROC_PD
enable control element of zero sequence overcurrent for pole disagreement protection
1 or 0
24
En_NegOC_PD
enable control element for negative sequence overcurrent for pole disagreement protection
1 or 0
25
En_BFI
enable breaker failure initiation function.
1 or 0
26
En_ROC_BFI
enable zero sequence overcurrent element of breaker failure initiation
1 or 0
27
En_NegOC_BFI
enable negative sequence overcurrent element of breaker failure initiation
1 or 0
28
En_Dly_MR1
enable MR1 protection to issue a trip command after delay [t_MR1]
1 or 0
29
En_Dly_MR14CtrlMR1
enable MR14 to control MR1 protection
1 or 0
30
En_FixDly_MR1
enable MR1 to issue command after [t_FixDly_MR1]
1 or 0
31
En_Dly_MR2
enable MR2 to issue a trip command after delay [t_ MR2]
1 or 0
32
En_Dly_MR3
enable MR3 to issue a trip command after delay [t_ MR3]
1 or 0
33
Opt_CT_PD
Select CT group for disagreement protection
1 or 0
34
Opt_CT_BFI
Select CT group for breaker failure initiation
1 or 0
35
En_ExTCtrlBFI
enable external tripping signal to control breaker failure initiation
1 or 0
36
En_PD_Ctrl_BFI
enable pole disagreement position of CB to control breaker failure initiation
1 or 0
37
En_DFR_Pkp_DSP
Reserved
1 or 0
38
En_DFR_Trp_DSP
Reserved
1 or 0
39
En_DFR_BI_DSP
Reserved
1 or 0
40
En_VEBI_DSP
Reserved
1 or 0
41
En_ExTCtrlPD2
enable external tripping signal to control pole disagreement protection delay 2
1 or 0
NR ELECTRIC CO., LTD
a
trip delay
pole
1 or 0 1 or 0
67
Chapter 7 Settings
No.
Setting Item
Description
Range
42
En_52aCtrlBFI
enable breaker auxiliary contact controlling breaker failure initiation
1 or 0
43
En_OC_PD2
enable overcurrent for pole disagreement protection delay 2
1 or 0
1.
Step
Explanation of Settings description I1n_CT1, I1n_CT2
These are the primary values of the first group of CT and the second group of CT respectively. These values are set to meet substation automation system’s requirement. If someone is not used, it can be configured at will. 2.
I_OC_BFI_CT1 It is the overcurrent setting of the first group of CT for breaker failure initiation. NOTE: Overcurrent elements used in pole disagreement protection delay 2 and breaker failure initiation are the same one [I_OC_BFI_CT1].
3.
I_ROC_BFI_CT1 It is the zero sequence current setting of the first group of CT for breaker failure initiation.
4.
Opt_CT_PD It is the logic setting of selecting CT group for pole disagreement protection. if it is set “0”, means only the first group of CT is adopted for pole disagreement protection. If it is set “1”, indicates that both the first and the second group of CT are used for pole disagreement protection.
5.
Opt_CT_BFI It is the logic setting of selecting CT group for breaker failure initiation. If it is set “0”, means only the first group of CT is adopted for breaker failure initiation. If it is set “1”, indicates that both the first and the second group of CT are used breaker failure initiation.
6.
En_DFR_Pkp_DSP, En_DFR_Trp_DSP, En_DFR_BI_DSP, En_VEBI_DSP,
[En_DFR_Pkp_DSP] is reserved and must be set as “0”. [En_DFR_Trp_DSP] is reserved and must be set as “1”. [En_DFR_BI_DSP] is reserved and must be set as “0”. [En_VEBI_DSP] is reserved and must be set as “0”.
68
NR ELECTRIC CO., LTD
Chapter 7 Settings
7.3 IP Address Settings These settings are used to set IP address of equipment Ethernet ports, when type 5E communication module is equipped for the equipment. Table 7.3-1 IP address settings list No.
Item
Description
1
IP_Addr1
IP address of Ethernet port 1 (COM1) of the equipment
2
IP_Addr2
IP address of Ethernet port 1 (COM2) of the equipment
3
IP_Addr3
IP address of Ethernet port 1 (COM3) of the equipment
4
IP_Addr4
IP address of Ethernet port 1 (COM4) of the equipment
IP address setting is in form of xxx.xxx.xxx.xxx, such as 198.87.191.25, and each byte section is in range of 0~255. Please refer to settings [COM1_Baud] and [COM2_Baud] in section 7.1 for configuring these settings.
7.4 MR Definition Settings These settings are only appeared in RCSPC software not in local LCD display, which are used to define MR signal to a specific MR name used on site. After new definition of MR is applied, then MR signal will be display in specific MR name in printed report and signals to SAS or RTU, but there are no changes for MR item in local LCD display. Table 7.4-1 MR display settings list No.
Item
Description
1
Definition_MR1
MR1 defined as a specific MR signal
2
Definition_MR2
MR2 defined as a specific MR signal
3
Definition_MR3
MR3 defined as a specific MR signal
4
Definition_MR4
MR4 defined as a specific MR signal
5
Definition_MR5
MR5 defined as a specific MR signal
6
Definition_MR6
MR6 defined as a specific MR signal
7
Definition_MR7
MR7 defined as a specific MR signal
8
Definition_MR8
MR8 defined as a specific MR signal
9
Definition_MR9
MR9 defined as a specific MR signal
10
Definition_MR10
MR10 defined as a specific MR signal
11
Definition_MR11
MR11 defined as a specific MR signal
12
Definition_MR12
MR12 defined as a specific MR signal
13
Definition_MR13
MR13 defined as a specific MR signal
14
Definition_MR14
MR14 defined as a specific MR signal
15
Definition_MR15
MR15 defined as a specific MR signal
16
Definition_MR16
MR16 defined as a specific MR signal
For example, Once “CoolFail” is defined for [Difinition_MR1], when MR1 operates with time delay, then binary input change report [BI_CoolFail] and trip report [Op_CoolFail] are sent to SAS or NR ELECTRIC CO., LTD
69
Chapter 7 Settings
RTU. If corresponding report is printed, then [BI_CoolFail] or [Op_CoolFail are in report instead of [BI_MR1] or [Op_MR1]. However local LDC there is still [BI_MR1] and [Op_MR2] displayed.
70
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
Chapter 8 HMI Operation Instruction The operator can access the protective device from the front panel. Local communication with the protective device is possible using a computer with the RCSPC software via an RS-232 port on the front panel. Furthermore, remote communication is also possible using a PC with the RCS-9700 substation automation system via an RS-485 port. The operator is able to check the protective device status at any time. This chapter describes human machine interface (HMI), and give operator a instruction about how to display or print event report, setting and so on through HMI menu tree and display metering value, including mean current, voltage and frequency etc. through LCD. In the same time, how to change active setting group or a settable parameter value through keypad is also described in details.
8.1 Overview The human-machine interface consists of a human-machine interface (HMI) module which allows a communication to be as simple as possible for the user. The HMI module helps to draw your attention to something that has occurred which may activate a LED or a report displayed on the LCD. Operator can locate the data of interest by navigating the keypad.
Figure 8.1-1 the front panel The function of HMI module: No
Item
NR ELECTRIC CO., LTD
Description
71
Chapter 8 HMI Operation Instruction
No
Item
Description
1
LCD
A 240×128 dot matrix backlight LCD display is visible in dim lighting conditions. The corresponding messages are displayed when there is operation implemented.
2
LED
64 status indication LEDs
3
Keypad
Numeric keypad and command keys for full access to the equipment
4
Front port
DB9 RS-232 port for communication with a PC for local communication and DB15 port for testing by using HELP-90A
ESC
8.1.1 Keypad Operation
Figure 8.1-2 Keypad buttons
No.
Item
Function
1
“▲” and “▼”
move cursor left-fight among selectable target
2
“◄” and “►”
move cursor up-down among selectable target
3
“+” and “-”
add or subtract in the digit
4
ENT
provide Enter/Execute function
5
GRP
setting Group selection
5
ESC
exit the present menu or return to the upper menu
NOTE:
72
Any setting change operation should complete with simply pressing “+”, “◄”, “▲”, and “-” in sequence, as a password. Without the operation, modifying settings is invalid.
Report delete operation should executed by pressing “+”, “-”, “+”, “-”, “ENT” in sequence after exiting the main menu.
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
8.1.2 LED Indicators
Figure 8.1-3 LED Indicators
Label
Status
Description
Off
The equipment is out of service or some hardware fault is detected by self-diagnostic facilities
HEALTH
ALRAM
Steady Green
The equipment is working on a correct order.
Off
The equipment is working on a correct order.
Steady Yellow
Some of CT circuit failure been detected, fault detector picks up over 10s, or breaker failure initiation picks up.
Off
No trip command is issued by pole disagreement protection.
Steady Red
A trip command has been issued by pole disagreement protection.
Off
No trip command is issued by mechanical protection with time delay (MR1-MR3).
Steady Red
A trip command has been issued by mechanical protection with time delay (MR1-MR3).
Off
No mechanical signal from transformer MR arriving at the equipment
Steady Red
A certain mechanical signal MRn arrives at related equipment terminal.
TRIP1
TRIP2
MECHn
NOTE:
The LED “HEALTHY” can only be lit by supplying DC to equipment without alarms blocking equipment.
The LED “ALARM” can be lit when there is some abnormality such as CT circuit abnormality, pickup of breaker failure initiation, and when equipment returns to normal operating state, the LED can go off automatically.
The LED “MECH4” indicates the binary input status of pole disagreement
NR ELECTRIC CO., LTD
73
Chapter 8 HMI Operation Instruction
([BI_PD_CB]). When [BI_PD_CB] is energized via the high voltage input terminal 910 and its status is “1”, LED “MECH4” is lit on, otherwise it is being in off state.
When signal of MRn arrive at RCS-974, whether trip relay is driven to output or not, th corresponding LED “MECHn” is lit.
8.1.3 Communication Port
1
2
Figure 8.1-4 Communication ports No.
Item
1
DB9 RS-232 port for communication with a PC for local communication.
2
DB 15 port for analog test signal injection from HELP-90A tester.
8.1.4 TARGET RESET Button “TARGET RESET” is used to reset the LED “TRIP1” and “TRIP2” to off state and switch the LCD display between the latest alarm report display screen and normal readiness screen. In addition, when pressing the “TARGET RESET”, a normal open contact of reset relay on No.8 BO board via terminals 829-830 is closed. Where, the latest alarm report means the events included in “TRP REPORT”, “ALM REPORT” or “BI CHG REPORT” happen since been reset last time till the minute. All the events are circularly displayed one by one. NOTE:If the equipment is blocked or alarm signal is sent during operation, please find out the cause with the help of self-diagnose record. If the reason can’t be found on site, before the verification done by NR, please never attempt to press “TARGET RESET” button. That is because the fault can never be cleared by just press “TARGET RESET” button since the real cause of the fault has not been figured out.
8.2 Understand the HMI Menu Tree 8.2.1 Overview Please see the total command menu in following diagram which will be introduced in details. In order to enter the main menu, please press “▲” arrow button under the default display condition. If the current display is the latest report display, please press “TARGET RESET” button to return to the default display condition, and then press “▲” arrow button to enter the main menu. Please use the “▲” and ”▼“ buttons to scroll between the submenus, press “ENT” to enter the item chosen or press “ESC” to directly return to the upper level. 74
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction MENU
1:VALUES
4:SETTINGS
1: DSP METERING
1: EQUIP SETTINGS
2: CPU METERING
2: PROT SETTINGS
3: PHASE ANGLE
3: IP ADDRESS
4: BI STATE
4: COPY SETTINGS
0: EXIT
0: EXIT
2:REPORT
5:CLOCK
1: TRP REPORT 2: ALM REPORT 3: BI CHG REPORT 0: EXIT
6:VERSION
3:PRINT 1: SETTINGS 2: TRP REPORT
7:LANGUAGE
3: ALM REPORT 4: BI CHG REPORT 5: PRESENT VALUES 6: VERSION 0: EXIT
0:EXIT
Figure 8.2-1 Menu tree for RCS-974
8.2.2 VALUES This menu displays the sampling value of current, voltage and phase angle and status of binary input, which can fully reflect the operation status of the protective device. Under normal conditions these displayed values should be consistent with the real values that have been injected. “VALUES” has the following submenus. No. 1
Item DSP METERING
Description To display sampled and calculated values on DSP chip.
2
CPU METERING
To display sampled and calculated values on CPU chip.
3
PHASE ANGLE
To display angles between different electric quantities.
4
BI STATE
To display states of binary inputs.
NR ELECTRIC CO., LTD
75
Chapter 8 HMI Operation Instruction
8.2.3 REPORT This menu displays the information recorded by the RCS-974 for the tripping reports, alarm message reports and status change of binary input reports etc. All the reports are stored in non-volatile memory. No.
Item
Description
1
TRP REPORT
To display tripping report
2
ALM REPORT
To display equipment self-supervision and abnormal report
3
BI CHG REPORT
To display status change of binary input report
Please use “▲” and ”▼“ to choose the report under concern, and press “”ENT to display the chosen report. In the report display submenu, the latest report shall be displayed first. Press “-” button to display the previous report, and press “+” to display the next report. In case that a report is too long to be fully displayed on the LCD, you should press “▲” or “▼” to display the other parts of the report. In order to return to the upper submenu, simply press “ESC” button.
8.2.4 PRINT The settings list, wave recorder, tripping report, operation report, abnormality report and status change of binary input can be printed by this submenu. No.
Item
Description
1
SETTINGS
To print all settings of the protective device
2
TRP REPORT
To print tripping report
3
ALM REPORT
To print self-supervision report
4
BI CHG REPORT
To print status change of binary input report
5
PRESENT VALUE
To print current voltage and current value sampled
6
VERSION
To print software version information
Please use “▲” and “▼” to choose the item under concern, and press “ENT” to execute printing.
8.2.5 SETTINGS Use this menu to select and set the different parameters for protection and control functions in the RCS-974. There are 30 selectable and editable setting groups, each independent of the other, to structure desired functions and applications. This menu comprises the following submenus: No.
76
Item
Description
1
EQUIP SETTINGS
To view and modify equipment settings
2
PROT SETTINGS
To view and modify protection settings
3
IP ADDRESS
To view and modify Ethernet settings
4
COPY SETTINGS
To copy active setting group to other setting group
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
Please use “▲” or “▼” to choose the setting under concern, and press “◄” or “►” to move the cursor to the digit to be changed. Press “+” or “-” button to change the data and then press “ENT” to confirm the setting change. If the setting change shall be terminated, simply press “ESC” to return, and the setting will remain unchanged.
8.2.6 CLOCK The internal clock for the RCS-974 can be viewed here. The time is displayed in the form YYYY-MM-DD and hh:mm:ss. All values are presented in digits. Please use “▲”, “▼”, “◄” or “►” to move the cursor to the digit to be changed. Press “+” or “-” button to change the data and then press “ENT” to confirm the change. If the setting change shall be terminated, simply press “ESC” to return, and the setting will remain unchanged.
8.2.7 VERSION This menu displays the version, verification code and creating time of the software applied in the equipment.
8.2.8 LANGUAGE This menu is optional for user to select multi-language display, and this menu may be different according to different customer equipments of language. “VERSION” has following submenus. No.
Item
Description
1
CHINESE
To set the Chinese as default displaying language.
2
ENGLISH
To set the English as default displaying language.
8.3 Understand the LCD Display 8.3.1 Main Display under Normal Operation Condition When the equipment is running normally, the LCD will display the following:
01 - 02 21 : 20 : 50 I_CT1 = 000.00 A I_CT2 = 000.00 A ActiveGrp
NR ELECTRIC CO., LTD
01
77
Chapter 8 HMI Operation Instruction
01-02 21:20:50: shows that the current time and date in format: MM-DD hh;mm:ss. I_CT1: mean value of three phase current from CT1 I_CT2: mean value of three phase current from CT2 ActiveGrp 01: shows the active setting group :shows the communication with SCADA system is in normal state.
8.3.2 Display Tripping Report When the equipment tripping output operates, the LCD will display the report of the latest tripping action.
OP 000
07-02-27
14 : 21 : 51 : 115 MS Op_PD1 02011MS OP000: shows the serial number of the operation report. 07-02-27: shows that the date of the tripping operation report in format YY-MM-DD. 14:21:51:115MS: shows the absolute tripping time in format hh:mm:ss:ms. Op_PD1: shows the element having operated. 02011 MS: shows the operation time of the tripping or reclosing element exclude the operation time of output relay. All tripping or operating reports are list in following table. Table 8.3-1 Tripping reports No.
Item
Description
1
Op_PD1
Delay 1 of pole disagreement protection operates
2
Op_PD2
Delay 1 of pole disagreement protection operates
3
Op_MR1
MR1 protection operates with time delay
4
Op_MR2
MR2 protection operates with time delay
5
Op_MR3
MR3 protection operates with time delay
8.3.3 Display Abnormal Report When hardware failure is detected during self-check or an abnormality of system happens a new report will be automatically displayed on LCD as follows.
78
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
ALM052
07-02-26
12 : 06 : 03 : 063 MS Alm_CTS_CT1
ALM052: serial number of the report. 07-02-26: shows the happening date of abnormality report in format YY-MM-DD. 12:06:03:063MS: shows the happening time of abnormality report in format hh:mm:ss:ms. Alm_CTS_CT1: shows abnormal element detected. Please refer to Table 4.3-1 for all abnormality alarms.
8.3.4 Display Status Change of Binary Input The LCD will automatically display a status change of binary inputs.
BI 034
07-02-26
12 : 06 : 03 : 441 MS BI_52a 0→1 BI 034: serial number of the report. 07-02-26: date in format of YY-MM-DD. 12:06:03:441MS: shows the happening time of status change in format of hh:mm:ss:ms. BI_52a 0→1: shows binary input name and status change action. Please refer to Table 5.2-3 for the all binary input change reports.
8.3.5 View the Settings Press “▲” to enter the main menu at first. Press key “▼” to select the item “SETTINGS” by scrolling the cursor downward, and then press key “ENT” to enter the submenu.
NR ELECTRIC CO., LTD
79
Chapter 8 HMI Operation Instruction
SETTINGS 1. EQUIP SETTINGS 2. PROT SETTINGS 3. VEBI SETTINGS Press key “▼” to select the item “PROT SETTINGS” by scrolling the cursor downward. Press key “ENT” to display the setting symbols and parameters of the submenu. Please press key “▲” or “▼” to locate the setting. Simply press “ESC” to return without changing, and press “ENT” to input password to confirm the change.
Group 01 Setting I1n_CT1 012.00 kA I2n_CT2 8.3.6 View Records The RCS-974 provides the following recording functions:
Event recording
Event recording are recorded in form of report and can be viewed through LCD or by printing.
Disturbance recording
Disturbance recording is recorded in form of both report and waveform, so report can be display as event report. However waveform must to be printed or displayed with proper software. These recording reports can also be displayed through software by the local or remote PC. Press “▲” enter the main menu at first. Press key “▼” to select the item “REPORT” by scrolling the cursor downward, and then pressing key “ENT” will enter the submenu. Press key “▼” to select the target item by scrolling the cursor downward, and press key “ENT” to the next submenu.
80
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
REPORT 1. TRP REPORT 2. ALM REPORT 3. BI CHG REPORT Then press key “▼” to select “TRP REPORT”, “ALM REPORT” or “BI CHG REPORT” by scrolling the cursor downward. Press key “ENT” to display the report selected. The latest report will be displayed firstly. Pressing key “+”or “-” will display next or previous report. If the report cannot be fully displayed in one screen, key “▲” or “▼” can be used to display the rest of it. Simply press key “ESC” or “ENT” to return the upper submenu.
8.3.7 Printing Reports and Waveform Press “▲” enter the main menu at first. Press key “▼” to select the item “PRINT” by scrolling the cursor downward, and then pressing key “ENT” will enter the submenu. Press key “▼” to select the target item by scrolling the cursor downward, and press key “ENT” to the next submenu.
PRINT 1. SETTINGS 2. TRP REPORT 3. ALM REPORT Then press key “▼” to select “SETTINGS”, “TRP REPORT”, “ALM REPORT” , “BI CHG REPORT”, “PRESENT VALUES” or “VERSION” or by scrolling the cursor downward. Press key “ENT” to print the report selected. Press key “+” or “-” to select next or previous report and press key “ENT”. Simply press key “ESC” to return the upper submenu. Take the “ALM REPORT” as an example.
Press TO Select Report
000 → 053
NR ELECTRIC CO., LTD
81
Chapter 8 HMI Operation Instruction
Press “ENT” to print if there is a printer connected to the relay. If no printer is connected, the following information will be shown “NO Printer”.
8.4 Input Operation through Keypad 8.4.1 Change the Settings Press key “◄” or “►” to move the cursor to locate the setting you want to change by operating the keypad to modify it. Press key “+” and “-” to change the digit. Press key “ESC” to return to the upper level menu with the setting remain unchanged. Press key “ENT”, the LCD will prompt typing of password.
Password :
……
Press keys “+”, “◄”, “▲” and “–” sequentially, then the equipment will check the password automatically. If the password input is correct, modification of setting will be confirmed and the interface will return to submenu. If one or some settings input are detected to be off-limits, the cursor will locate where the first wrong setting is and the LCD will display “xxxxx SetInvalid”. (For example, “I1n_CT1 SetInvalid”) NOTE If the active group number or protection system parameter is changed, protective settings will be invalid and have to be configured again.
8.4.2 Copy Settings The relay stores 30 setting groups from No.0 to No.29. Only present setting group is active, others are provided for different operating conditions. The equipment settings are common for all these setting groups, but the protection settings are independent. Generally the equipment is delivered with default settings stored in active setting group “0”. The contents of other setting groups may be invalid. Therefore after application-specific settings for group No.0 have been ready, it is necessary to copy settings of group No.0 to all the other setting groups, and make some modification afterwards when necessary, so as to avoid entering all settings one by one. Press key “▲” to enter the main menu at first. Move cursor to the item “SETTINGS” and press key “ENT” to enter submenu. Press key “▼” and move cursor to the item “COPY SETTINGS” item 82
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
and press “ENT” to display following interface.
COPY SETTINGS
Active Grp :
00
Target Grp :
01
Press key “+” and “-” to change digit where the cursor stays. Press “ENT” to confirm, then settings group 0 will be totally copied to settings group 1.
8.4.3 Switch Active Setting Group Sometimes it is necessary to switch among different setting groups to fit the different operating conditions. Press key “GRP” to display following interface.
Chg Act Grp
Active Grp :
00
Change to :
01
Press key “+” and “-” to change digit where the cursor stays. Press “ENT” to confirm. If the new active setting group is valid, LCD will display main configuration diagram. Otherwise, an alarm [Alm_InvalidGrp] will be issued and LED “HEALTHY” will go off. Then please modify this group settings to make them valid.
SetRefreshing …
8.4.4 Delete Fault Records and Event Records If you want to delete the content of fault records or event records, press key “▲” to enter the main menu at first and press “+”, “-”, “+”, “-”, “ENT” in sequence after exiting the main menu, then LCD NR ELECTRIC CO., LTD
83
Chapter 8 HMI Operation Instruction
display following interface.
Press Press ESC To Exit
NOTE You have no choice to select which kind of records or which one record to be deleted but to delete all records. Press key “ENT” to delete all records and LCD will display “RptClearing...” then the reports will be deleted, or press key “ESC” to exit to main menu without deletion.
8.4.5 Adjusting the Clock If the clock of the equipment is not correct, please adjust it. Press key “▲” to enter the main menu at first. Move cursor to the item “CLOCK” and press key “ENT” to display following interface.
CLOCK
DATE :
2005 06 25
TIME :
09 08 39
2005 06 25: shows the data in format of YYYY-MM-DD. 09 08 39: shows the time in format of hh:mm:ss. Press keys “▲”, “▼”, “◄” and “►” to select the digit to be modified. Pressing key “+” and “-” to modify data. Press key “ESC” to return without modification. Press key “ENT” to confirm the modification and return to main menu.
8.4.6 View Software Version Press key “▲” to enter the main menu at first. Move cursor to the item “VERSION” and press key “ENT” to display following interface and then press key “ESC” to exit.
84
NR ELECTRIC CO., LTD
Chapter 8 HMI Operation Instruction
RCS-974AG Project :
080110
Ver :
2.00
CRC :
F4B1
RCS-974AG CRC :
F4B1
2008-03-20 20 : 24 SUBQ :
00038913
RCS-974AG: shows the name of the protection program. Project: 070050: shows the project number is 070050. Ver: 2.00: shows the program version number CRC: F4B1: shows CRC (check code) of the program. 2008-03-20 20:24: shows the creating time of the program in format of YY-MM-DD HH:MM SUBQ: 00038913: shows management sequential number of the program. NOTE: What above figure shows is just an example to introduce the meaning of LCD display of software version, the actual version for user is application-specific.
NR ELECTRIC CO., LTD
85
Chapter
86
8
HMI
Operation
Instruction
NR ELECTRIC CO., LTD
Chapter 9 Communications
Chapter 9 Communications 9.1 Overview This section outlines the remote communications interfaces of NR equipment. The protective device supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet), selected via the model number by setting. The protocol provided by the protective device is indicated in the submenu in the “EQUIP SETTINGS” column. Using the keypad and LCD, set the parameter [Protocol], the corresponding protocol will be selected. The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever protocol is selected. The advantage of this type of connection is that up to 32 protective devices can be “daisy chained” together using a simple twisted pair electrical connection. It should be noted that the descriptions contained within this section do not aim to fully detail the protocol itself. The relevant documentation for the protocol should be referred to for this information. This section serves to describe the specific implementation of the protocol in the relay.
9.2 Rear Communication Port Information 9.2.1 RS-485 Interface This protective device provides two rear RS-485 communication ports, and each port has three terminals in the 12-terminal screw connector located on the back of the relay and each port has a ground terminal for the earth shield of the communication cable. Please refer to the section of “Communication Interface module” for details of the connection terminals. The rear ports provide RS-485 serial data communication and are intended for use with a permanently wired connection to a remote control center. 9.2.1.1 EIA RS-485 Standardized Bus The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the product. The connection is polarized and whilst the product’s connection diagrams indicate the polarization of the connection terminals it should be borne in mind that there is no agreed definition of which terminal is which. If the master is unable to communicate with the product, and the communication parameters match, then it is possible that the two-wire connection is reversed. 9.2.1.2 Bus Termination The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end across the signal wires (refer to Figure 9.2-1). Some devices may be able to provide the bus terminating resistors by different connection or configuration arrangements, in which case separate external components will not be required. However, this product does not provide such a facility, so if it is located at the bus terminus then an external termination resistor will be required.
NR ELECTRIC CO., LTD
87
Chapter 9 Communications
Figure 9.2-1 EIA RS-485 bus connection arrangements 9.2.1.3 Bus Connections & Topologies The EIA RS-485 standard requires that each device is directly connected to the physical cable that is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop bus topologies are not part of the EIA RS-485 standard and are forbidden by it also. Two-core screened cable is recommended. The specification of the cable will be dependent on the application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must not exceed 500m. The screen must be continuous and connected to ground at one end, normally at the master connection point; it is important to avoid circulating currents, especially when the cable runs between buildings, for both safety and noise reasons. This product does not provide a signal ground connection. If a signal ground connection is present in the bus cable then it must be ignored, although it must have continuity for the benefit of other devices connected to the bus. At no stage must the signal ground be connected to the cables screen or to the product’s chassis. This is for both safety and noise reasons. 9.2.1.4 Biasing It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal level has an indeterminate state because the bus is not being actively driven. This can occur when all the slaves are in receive mode and the master is slow to turn from receive mode to transmit mode. This may be because the master purposefully waits in receive mode, or even in a high impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss the first bits of the first character in the packet, which results in the slave rejecting the message and consequentially not responding. Symptoms of these are poor response times (due to retries), increasing message error counters, erratic communications, and even a complete failure to communicate. Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There should only be one bias point on the bus, which is best situated at the master connection point. The DC source used for the bias must be clean; otherwise noise will be injected. Note that some devices may (optionally) be able to provide the bus bias, in which case external components will not be required. NOTE:
88
NR ELECTRIC CO., LTD
Chapter 9 Communications
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NR cannot assume responsibility for any damage that may occur to a device connected to the network as a result of incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs) as this may cause noise to be passed to the communication network.
9.2.2 Ethernet Interface This protective device can provide four rear Ethernet interfaces (optional) and they are unattached each other. Parameters of each Ethernet port can be configured in the submenu “IP ADDRESS”. 9.2.2.1 Ethernet Standardized Communication Cable It is recommended to use twisted screened eight-core cable as the communication cable. A picture is shown bellow.
Figure 9.2-2 Ethernet communication cable 9.2.2.2 Connections and Topologies Each equipment is connected with an exchanger via communication cable, and thereby it forms a star structure network. Dual-network is recommended in order to increase reliability. SCADA is also connected to the exchanger and will play a role of master station, so the every equipment which has been connected to the exchanger will play a role of slave unit.
NR ELECTRIC CO., LTD
89
Chapter 9 Communications
Figure 9.2-3 Ethernet communication structure
9.2.3 IEC60870-5-103 Communication The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform communication with protective device. The standard configuration for the IEC60870-5-103 protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. It also supports to use an Ethernet connection. The relay operates as a slave in the system, responding to commands from a master station. To use the rear port with IEC60870-5-103 communication, the relevant settings ot the protective device must be configured. To do this use the keypad and LCD user interface. In the submenu “EQUIP SETTINGS”, set the parameters [Protocol] as “0”, [COM1_Baud] and [COM2_Baud] as “9600”. For using the Ethernet port with IEC60870-5-103 communication, the IP address and submask of each Ethernet port can be set in the submenu “IP ADDRESS”. Please refer to the corresponding section in Chapter “Settings” for further details.
9.3 IEC60870-5-103 Interface over Serial Port The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the protective device as the slave device. It is properly developed by NR. The protective device conforms to compatibility level 2; compatibility level 3 is not supported. The following IEC60870-5-103 facilities are supported by this interface:
Initialization (reset)
Time synchronization
Event record extraction
General interrogation
General functions
Disturbance records
9.3.1 Physical Connection and Link Layer Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this protective device. The transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit/s. The link layer strictly abides by the rules defined in the IEC60870-5-103.
9.3.2 Initialization Whenever the protective device has been powered up, or if the communication parameters have been changed, a reset command is required to initialize the communications. The protective device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU will clear any unsent messages in the transmit buffer.
90
NR ELECTRIC CO., LTD
Chapter 9 Communications
The protective device will respond to the reset command with an identification message ASDU 5, the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB depending on the nature of the reset command.
9.3.3 Time Synchronization The protective device time and date can be set using the time synchronization feature of the IEC60870-5-103 protocol. The protective device will correct for the transmission delay as specified in IEC60870-5-103. If the time synchronization message is sent as a send/confirm message then the protective device will respond with a confirmation. Whether the time-synchronization message is sent as a send confirmation or a broadcast (send/no reply) message, a time synchronization class 1 event will be generated/produced. If the protective device clock is synchronized using the IRIG-B input then it will not be possible to set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via the interface will cause the protective device to create an event with the current date and time taken from the IRIG-B synchronized internal clock.
9.3.4 Spontaneous Events Events are categorized using the following information:
1.
Type identification (TYP)
Function type (FUN)
Information number (INF)
The following table contains a complete listing of all events produced by the protective device. For the details about this events. TYP
ASDU 2
ASDU 1
NR ELECTRIC CO., LTD
FUN
INF
COT
Event Name
194
116
1
Op_PD1
194
117
1
Op_PD2
194
102
1
Op_MR1
194
181
1
Op_MR2
194
182
1
Op_MR3
194
84
1
EBI_PD
194
85
1
EBI_Dly_MR
194
18
1
BI_ExTCtrlBFI
194
17
1
BI_ExTCtrlPD2
194
83
1
BI_52a
194
83
1
Reserved
194
189
1
BI_Pwr_Opto
194
83
1
BI_PD_CB
194
189
1
BI_TripOut
194
176
1
BI_MR1
194
177
1
BI_MR2
91
Chapter 9 Communications
TYP
FUN
INF
COT
Event Name
194
178
1
BI_MR3
194
194
1
Alm_RAM
194
195
1
Alm_ROM
194
196
1
Alm_EEPROM
194
86
1
Alm_InvalidGrp
194
33
1
Alm_Smpl_CPU
194
214
1
Alm_PersistFD
194
104
1
Alm_Smpl_DSP
194
247
1
Alm_TrpOut
194
103
1
Alm_Setting
194
180
1
Alm_BI_PD
194
202
1
Alm_Pwr_Opto
194
119
1
Alm_Pkp_BFI1
194
180
1
Alm_BI_ExTrp
194
3
1
Alm_CTS_CT1
194
3
1
Alm_CTS_CT2
194
119
1
Alm_Pkp_BFI2
194
10
1
Alm_MR5
194
11
1
Alm_MR6
194
12
1
Alm_MR7
194
135
1
Alm_MR8
194
248
1
Alm_MR9
194
134
1
Alm_MR10
194
132
1
Alm_MR11
194
249
1
Alm_MR12
194
148
1
Alm_MR13
194
136
1
Alm_MR14
194
145
1
Alm_MR15
194
179
1
Alm_MR16
194
20
1
BI_BlkComm
9.3.5 General Interrogation The GI can be used to read the status of the relay, the function numbers, and information numbers that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined in the IEC60870-5-103. Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
9.3.6 General Functions The generic functions can be used to read the setting and protection measurement of the relay, and modify the setting. Two supported type identifications are ASDU 21 and ASDU 10. For more details about generic functions, see the IEC60870-5-103 standard.
92
NR ELECTRIC CO., LTD
Chapter 9 Communications
Group Number 0
Group type Device Description
1
Equip Settings
2
Setting Group
3
Setting
9
Measurement
11
Net Setting
NOTE:If the setting [En_Remote_Cfg] in the submenu “EQUIP SETTINGS” is set as “0”, to modify protection settings remotely will not be allowed. Moreover, equipment parameters are not allowed to be modified remotely whether the item [En_Remote_Cfg] is “1” or “0”.
9.3.7 Disturbance Records This protective device can store up to eight disturbance records in its memory. A pickup of the fault detector or an operation of the relay can make the protective device store the disturbance records. The disturbance records are stored in uncompressed format and can be extracted using the standard mechanisms described in IEC60870-5-103. ACC 64
Content Ia_1
65
Ib_1
66
Ic_1
67
I30_1
68
Ia_2
69
Ib_2
70
Ic_2
71
3I0_2
9.4 IEC60870-5-103 Interface over Ethernet The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave device. It is properly developed by NR too. All the service of this relay is based on generic functions of the IEC60870-5-103. The following table lists all the group number of this relay. And this relay will send all the relevant information about group caption to the SAS or RTU after establishing a successful communication link. Group Number
NR ELECTRIC CO., LTD
Group Caption Description
0
Device Description
1
Device Parameter
2
Setting Group
3
Setting
93
Chapter 9 Communications
Group Number
Group Caption Description
9
Measurement
10
Fault Data
11
Net Setting
12
Enabling BI
13
Operation Element
14
Alarm Info
15
Disturbance Info List
9.5 Modbus Protocol over Serial Port 9.5.1 Overview The RCS-985T relay support several communications protocols to allow the connection to the equipment such as personal computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus RTU protocol is the most basic protocol supported by the RCS-985T. Modbus is available via RS485 serial links or via Ethernet (using the Modbus/TCP specification). The following information is provided primarily for users who wish to develop their own master communication drivers and applies to the serial Modbus RTU protocol. The characteristics are listed below: z
Standard: Modicon Modbus Protocol Reference Guide, PI-MBUS-300 Rev.E
z
Physical Layer Setup: RS485, 1 start bit,8 data bits, no bit for parity,1 stop bit
z
Link Layer Setup: Only RTU Mode Supported
z
Frame Length Up limit: 256 Bytes
z
Baud Rate: Configurable
z
Device Address: Configurable
z
Parity: no
The following Modbus function codes are supported but re-defined by the relay: 02 Read Input Status-Get real-time statuses (binary) 03 Read Holding Registers- Get Settings 04 Read Input Registers- Get metering values of equipment
9.5.2 Fetch real Time Status (Binary) Function Code: 02H This function reads the ON/OFF status of discrete inputs in the slave. The status in the response message is packed as one input per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF.
94
NR ELECTRIC CO., LTD
Chapter 9 Communications
The LSB of the first data byte contains the input addressed in the query. The other inputs follow toward the high order end of this byte, and from ‘low order to high order’ in subsequent bytes. Example 1: If the master wants to fetch Trip Information (0000H~0003H), the query frame would be as follows (Suppose the slave address was 1): 01
02
00
00
00
04
79
C9
Slave Addr
Function Code
Start Register Addr Hi
Start Register Addr Lo
Num of Status Hi
Num of Status Lo
CRC Lo
CRC Hi
The response fame would be as follows (Suppose the value of 0000H~0003H equal to 1,1,0,1 respectively): 01
02
01
0B
E0
4F
Slave Addr
Function Code
Length
Status
CRC Lo
CRC Hi
Example 2: If the master wants to fetch Trip Information (0002H~000DH), the query frame would be as follows (Suppose the slave address was 1): 01
02
00
02
00
0C
D9
CF
Slave Addr
Function Code
Start Register Addr Hi
Start Register Addr Lo
Num of Status Hi
Num of Status Lo
CRC Lo
CRC Hi
The response fame would be as follows (Suppose the value of 0002H~000DH equal to 1,1,0,1,0,0,1,0,1,1,1,0 respectively): 01
02
02
07
4B
FB
BF
Slave Addr
Function Code
Length
Status Hi
Status Lo
CRC Lo
CRC Hi
9.5.2.1 Trip Information Value of corresponding Bit=1: operate, 0: drop back or not operate Address
Item Name
Address
Item Name
0000H
Op_PD1
0003H
Op_MR2
0001H
Op_PD2
0004H
Op_MR3
0002H
Op_MR1
9.5.2.2 Alarm Information “1” means alarm,”0” for no alarm or draw off. Address
Item Name
Address
Item Name
1000H
Alm_Smpl_DSP
1013H
Alm_MR8
1001H
Alm_TrpOut
1014H
Alm_MR9
1002H
Alm_Setting
1015H
Alm_MR10
NR ELECTRIC CO., LTD
95
Chapter 9 Communications
Address
Item Name
Address
Item Name
1003H
Alm_BI_PD
1016H
Alm_MR11
1004H
Alm_Pwr_Opto
1017H
Alm_MR12
1005H
Alm_Pkp_BFI1
1018H
Alm_MR13
1006H
Alm_BI_ExTrp
1019H
Alm_MR14
1007H
Alm_CTS_CT1
101AH
Alm_MR15
1008H
Alm_CTS_CT2
101BH
Alm_MR16
1009H
Alm_Pkp_BFI2
101CH
Reserved
100AH
Reserved
101DH
Reserved
100BH
Reserved
101EH
Reserved
100CH
Reserved
101FH
Reserved
100DH
Reserved
1020H
Alm_RAM
100EH
Reserved
1021H
Alm_ROM
100FH
Reserved
1022H
Alm_EEPROM
1010H
Alm_MR5
1023H
Alm_InvalidGrp
1011H
Alm_MR6
1024H
Alm_Smpl_CPU
1012H
Alm_MR7
1025H
Alm_PersistFD
9.5.2.3 BinaryInput Change Information “1” means binary change,”0” for no change or draw off. Address
Item Name
Address
Item Name
2000H
EBI_PD
2008H
BI_PD_CB
2001H
EBI_Dly_MR
2009H
BI_TripOut
2002H
BI_ExTCtrlBFI
200AH
BI_MR1
2003H
BI_ExTCtrlPD2
200BH
BI_MR2
2004H
BI_52a
200CH
BI_MR3
2005H
Reserved
200DH
Reserved
2006H
Reserved
200EH
Reserved
2007H
BI_Pwr_Opto
200FH
FD_CPU
9.5.3 Fetch Metering Values of Equipment Function Code: 04H The metering values in the response message are packed as two bytes per register. For each register, the first byte contains the high order bits and the second contains the low order bits. Register
96
Content
Unit
0000H
PhaseACurr1
(2 digits decimal)
A
0001H
PhaseBCurr1
(2 digits decimal)
A
0002H
PhaseCCurr1
(2 digits decimal)
A
0003H
ZeroSeqCurr1
(2 digits decimal)
A
0004H
NegSequenceCurr1(2 digits decimal)
A
0005H
PhaseACurr2
A
(2 digits decimal)
NR ELECTRIC CO., LTD
Chapter 9 Communications
0006H
PhaseBCurr2
(2 digits decimal)
A
0007H
PhaseCCurr2
(2 digits decimal)
A
0008H
ZeroSeqCurr2
(2 digits decimal)
A
0009H
NegSequenceCurr2(2 digits decimal)
A
9.5.4 Fetch Settings Value of Equipment Function Code: 03H 9.5.4.1 Equipment Settings Table 9.5-1 Register
Equipment settings Content
0000H
Active_Grp
0001H
Comm_Addr
0002H
COM1_Baud
Bps
0003H
COM2_Baud
Bps
0004H
Printer_Baud
0005H
Debug_Baud
0006H
fn
0007H
I2n
0008H
Protocol
0009H
Equip_ID (H byte)
000AH
Equip_ID (M byte)
000BH
Equip_ID (Lbyte)
A
Bit0: En_Net_Print 000CH
Control word
Bit1: En_Auto_Print Bit2: GPS_Pulse Bit3: En_Remote_Cfg Bit4: Iec103.Inf
9.5.4.2 Protection Settings Table 9.5-2 Register
Protection settings Content
Unit
1000H
I1n_CT1 (2 digits decimal)
kA
1001H
I1n_CT2 (2 digits decimal)
kA
1002H
I_ROC_PD_CT1 (2 digits decimal)
A
1003H
I_NegOC_PD_CT1 (2 digits decimal)
A
1004H
I_ROC_PD_CT2 (2 digits decimal)
A
1005H
I_NegOC_PD_CT2 (2 digits decimal)
A
1006H
T_PD1(2 digits decimal)
s
1007H
T_PD2(2 digits decimal)
s
1008H
I_OC_BFI_CT1 (2 digits decimal)
A
NR ELECTRIC CO., LTD
97
Chapter 9 Communications
Register
Content
Unit
1009H
I_ROC_BFI_CT1 (2 digits decimal)
A
100AH
I_NegOC_BFI_CT1 (2 digits decimal)
A
100BH
I_OC_BFI_CT2 (2 digits decimal)
A
100CH
I_ROC_BFI_CT2 (2 digits decimal)
A
100DH
I_NegOC_BFI_CT2 (2 digits decimal)
A
100EH
t_BFI1(2 digits decimal)
s
100FH
t_BFI2(2 digits decimal)
s
1010H
t_FixDly_MR1 (2 digits decimal)
min
1011H
t_MP1(2 digits decimal)
min
1012H
t_MP2(2 digits decimal)
min
1013H
t_MP3(2 digits decimal)
s
Bit0: En_PD1 Bit1: En_PD2 Bit2: En_ROC_PD Bit3: En_NegOC_PD Bit4: En_BFI Bit5: En_ROC_BFI Bit6: En_NegOC_BFI 1014H
Control word 1
Bit7: En_Dly_MR1 Bit8: En_Dly_MR14CtrlMR1 Bit9: En_FixDly_MR1 Bit10: En_Dly_MR2 Bit11: En_Dly_MR3 Bit12: Opt_CT_PD Bit13: Opt_CT_BFI Bit14: En_ExTCtrlBFI Bit15: En_PD_Ctrl_BFI Bit0: En_DFR_Pkp_DSP Bit1: En_DFR_Trp_DSP
1015H
Control word 2
Bit2: En_DFR_BI_DSP Bit3: En_VEBI_DSP Bit4: En_ExTCtrlPD2 Bit5: En_52aCtrlBFI Bit6: En_OC_PD2
9.5.5 Diagnostics (Function Code: 08H) Modbus function 08 provides a series of tests for checking the communication system between the master and slave, or for checking various internal error conditions within the slave. The function uses a two–byte sub-function code field in the query to define the type of test to be performed. The slave echoes both the function code and sub-function code in a normal response. The listing below shows the sub-function codes supported by the equipment. 98
NR ELECTRIC CO., LTD
Chapter 9 Communications
Table 9.5-3
Diagnostics information
Sub function No.
Description
00H
Query link layer status
01H
Reset communication
04H
Listen only mode
0BH
Number of Frames received
0CH
Number of Frames that CRC are wrong
0DH
Number of Frames that make device exceptional
0EH
Number of Frames that address is same to device or is broadcast and the device has processed.
0FH
Number of Frames that device have no response.
9.5.6 Exception Responses Except for broadcast messages, when a master device sends a query to a slave device it expects a normal response. If the slave receives the query without a communication error but the salve cannot handle it (for example, if the request is to read a non–existent coil or register), the slave will return an exception response informing the master of the nature of the error. The listing below shows the exception codes supported by the equipment. Code
Description
01H
Illegal Function
02H
Illegal Data Address
9.6 Messages Description for IEC61850 Protocol 9.6.1 Overview The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic equipment to produce standardized communications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, substation design and configuration, testing, environmental and project standards. The complete set includes:
IEC 61850-1: Introduction and overview
IEC 61850-2: Glossary
IEC 61850-3: General requirements
IEC 61850-4: System and project management
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs IEC 61850-7-1: Basic communication structure for substation and feeder equipment Principles and models IEC 61850-7-2: Basic communication structure for substation and feeder equipment -
NR ELECTRIC CO., LTD
99
Chapter 9 Communications
Abstract communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment – Common data classes IEC 61850-7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes and data classes IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3 IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multidrop point to point link IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3 IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with any IEC 61850 implementation obtain this document set.
9.6.2 Communication Profiles The RCS-900 series relay supports IEC 61850 server services over TCP/IP communication protocol stacks. The TCP/IP profile requires the RCS-900 series to have an IP address to establish communications. These addresses are located in the submenu “IP ADDRESS“. Please refer to section 7.3 for further details. 1.
MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer of real-time data. This protocol has been in existence for a number of years and provides a set of services suitable for the transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract services in IEC61850-8-1. 2.
Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and communication activity is controlled by the client. IEC61850 clients are often substation computers running HMI programs or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, transformer, tap changers, or bay controllers. 3.
Peer-to-peer
This is a non-connection-oriented, high speed type of communication usually between substation equipment, such as protection relays. GOOSE is the method of peer-to-peer communication. 4.
Substation configuration language (SCL)
A substation configuration language is a number of files used to describe the configuration of substation equipment. Each configured device has an IEC Capability Description (ICD) file and a 100
NR ELECTRIC CO., LTD
Chapter 9 Communications
Configured IED Description (CID) file. The substation single line information is stored in a System Specification Description (SSD) file. The entire substation configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individual ICD files and the SSD file.
9.6.3 Server Data Organization IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device can contain one or more logical device(s) (for proxy). Each logical device can contain many logical nodes. Each logical node can contain many data objects. Each data object is composed of data attributes and data attribute components. Services are available at each level for performing various functions, such as reading, writing, control commands, and reporting. Each IED represents one IEC61850 physical device. The physical device contains one logical device, and the logical device contains many logical nodes. The logical node LPHD contains information about the IED physical device. The logical node LLN0 contains information about the IED logical device. 9.6.3.1 Digital Status Values The GGIO logical node is available in the RCS-900 series relays to provide access to digital status points (including general I/O inputs and warnings) and associated timestamps and quality flags. The data content must be configured before the data can be used. GGIO provides digital status points for access by clients. It is intended that clients use GGIO in order to access digital status values from the RCS-900 series relays. Clients can utilize the IEC61850 buffered reporting features available from GGIO in order to build sequence of events (SOE) logs and HMI display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the chances of missing data state changes. All needed status data objects are transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control block (BRCB) is defined in LLN0. 9.6.3.2 Analog Values Most of analog measured values are available through the MMXU logical nodes, and metering values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data from a IED current/voltage “source”. There is one MMXU available for each configurable source. MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the following data for each source:
MMXU.ST.Hz: frequency
MMXU.ST.PPV.phsAB: phase AB voltage magnitude and angle
MMXU.ST.PPV.phsBC: phase BC voltage magnitude and angle
MMXU.ST.PPV.phsCA: Phase CA voltage magnitude and angle
NR ELECTRIC CO., LTD
101
Chapter 9 Communications
MMXU.ST.PhV.phsA: phase AG voltage magnitude and angle
MMXU.ST.PhV.phsB: phase BG voltage magnitude and angle
MMXU.ST.PhV.phsC: phase CG voltage magnitude and angle
MMXU.ST.A.phsA: phase A current magnitude and angle
MMXU.ST.A.phsB: phase B current magnitude and angle
MMXU.ST.A.phsC: phase C current magnitude and angle
9.6.3.3 Protection Logical Nodes The following list describes the protection elements for all RCS-900 series relays. The specified relay will contain a subset of protection elements from this list.
PDIF: current differential and transfer trip
PDIS: phase-to-phase distance, phase-to-ground distance and SOTF distance
PTUC: undercurrent
PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS
PTUV: undervoltage
PTUF: underfrequency
PTOV: overvoltage and auxiliary overvoltage
RREC: automatic reclosing
The protection elements listed above contain start (pickup) and operate flags, instead of any element has its own start (pickup) flag separately, all the elements share a common start (pickup) flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For the RCS-900 series relay protection elements, these flags take their values from related module for the corresponding element. Similar to digital status values, the protection trip information is reported via BRCB, and it also locates in LLN0. 9.6.3.4 LLN0 and Other Logical Nodes Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address common issues for Logical Devices. Most of the public services, the common settings, control values and some device oriented data objects are available here. The public services may be BRCB, URCB and GSE control blocks and similar global defines for the whole device; the common settings include all the setting items of communication settings. System settings and some of the protection setting items, which can be configured to two or more protection elements (logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local operation for complete logical device, when it is true, all the remote control commands to the IED will be blocked and those commands make effective until the item Loc is changed to false. In RCS-900 series relays, besides the logical nodes we describe above, there are some other logical nodes below in the IEDs:
102
NR ELECTRIC CO., LTD
Chapter 9 Communications
LPHD: Physical device information, the logical node to model common issues for physical device. PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or more protection functions to a common “trip” to be transmitted to XCBR. In addition or alternatively, any combination of “operate” outputs of protection functions may be combined to a new “operate” of PTRC. RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System” (IEC 60255-24). All enabled channels are included in the recording, independently of the trigger mode.
9.6.4 Server Features and Configuration 9.6.4.1 Buffered/unbuffered Reporting IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured to transmit information of protection trip information (in the Protection logical nodes), binary status values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The reporting control blocks can be configured in CID files, and then be sent to the IED via an IEC61850 client. The following items can be configured.
TrgOps: Trigger options. The following bits are supported by the RCS-900 series relays: - Bit 1: Data-change - Bit 4: Integrity - Bit 5: General interrogation
OptFlds: Option Fields. The following bits are supported by the RCS-900 series relays: - Bit 1: Sequence-number - Bit 2: Report-time-stamp - Bit 3: Reason-for-inclusion - Bit 4: Data-set-name - Bit 5: Data-reference - Bit 6: Buffer-overflow (for buffered reports only) - Bit 7: EntryID (for buffered reports only) - Bit 8: Conf-revision - Bit 9: Segmentation
IntgPd: Integrity period.
BufTm: Buffer time.
NR ELECTRIC CO., LTD
103
Chapter 9 Communications
9.6.4.2 File Transfer MMS file services are supported to allow transfer of oscillography, event record or other files from a RCS-900 series relay. 9.6.4.3 Timestamps The timestamp values associated with all IEC61850 data items represent the time of the last change of either the value or quality flags of the data item. 9.6.4.4 Logical Node Name Prefixes IEC61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of:
A five or six-character name prefix.
A four-character standard name (for example, MMXU, GGIO, PIOC, etc.).
A one or two-character instantiation index.
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable. Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is recommended that a consistent naming convention be used for an entire substation project. 9.6.4.5 GOOSE Services IEC61850 specifies the type of peer-to-peer data transfer services: Generic Object Oriented Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Devices that transmit GOOSE messages also Devices that transmit GOOSE messages also function as servers. Each GOOSE publisher contains a “GOOSE control block” to configure and control the transmission. The transmission is also controlled via device setting “GOOSE Group ID” in the setting submenu “EQUIP SETUP”. The “GOOSE Group ID” setting item defines a definite IED group in which the IED can communicate with each other via GOOSE protocol, and if GOOSE Group ID is configured to “0”, GOOSE service is blocked in this IED. IEC61850 recommends a default priority value of 4 for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More details are specified in IEC61850 part 8-1. IEC61850 recommends that the Ether-type Application ID number be configured according to the GOOSE source. The RCS-974 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this dataset that is transferred using GOOSE message services. The GOOSE related dataset is configured in the CID file and it is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between RCS-900 series relays. IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must
104
NR ELECTRIC CO., LTD
Chapter 9 Communications
be correct to achieve the successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact match in terms of data structure, and that the GOOSE addresses and name strings match exactly. The general steps required for transmission configuration are: 1.
Configure the transmission dataset.
2.
Configure the GOOSE service settings.
3.
Configure the data.
The general steps required for reception configuration are: 1.
Configure the reception dataset.
2.
Configure the GOOSE service settings.
3.
Configure the data.
9.6.5 ACSI conformance 9.6.5.1 ACSI Basic Conformance Statement Services
Client
Server
RCS-974
Client-Server Roles B11
Server side (of Two-party Application-Association)
-
C1
Y
B12
Client side (of Two-party Application-Association)
C1
-
N
SCSMS Supported B21
SCSM: IEC 61850-8-1 used
N
N
Y
B22
SCSM: IEC 61850-9-1 used
N
N
N
B23
SCSM: IEC 61850-9-2 used
N
N
N
B24
SCSM: other
N
N
N
Generic Substation Event Model (GSE) B31
Publisher side
-
O
Y
B32
Subscriber side
O
-
Y
Transmission Of Sampled Value Model (SVC) B41
Publisher side
-
O
N
B42
Subscriber side
O
-
N
Where: C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared O: Optional M: Mandatory Y:
Supported by RCS-900 series relays
N: Currently not supported by RCS-900 series relays
NR ELECTRIC CO., LTD
105
Chapter 9 Communications
9.6.5.2 ACSI Models Conformance Statement Services
Client
Server
RCS-974
M1
Logical device
C2
C2
Y
M2
Logical node
C3
C3
Y
M3
Data
C4
C4
Y
M4
Data set
C5
C5
Y
M5
Substitution
O
O
Y
M6
Setting group control
O
O
Y
M7
Buffered report control
O
O
Y
M7-1
sequence-number
Y
Y
Y
M7-2
report-time-stamp
Y
Y
Y
M7-3
reason-for-inclusion
Y
Y
Y
M7-4
data-set-name
Y
Y
Y
M7-5
data-reference
Y
Y
Y
M7-6
buffer-overflow
Y
Y
Y
M7-7
entryID
Y
Y
Y
M7-8
BufTm
N
N
N
M7-9
IntgPd
Y
Y
Y
M7-10
GI
Y
Y
Y
M8
Unbuffered report control
M
M
Y
M8-1
sequence-number
Y
Y
Y
M8-2
report-time-stamp
Y
Y
Y
M8-3
reason-for-inclusion
Y
Y
Y
M8-4
data-set-name
Y
Y
Y
M8-5
data-reference
Y
Y
Y
M8-6
BufTm
N
N
N
M8-7
IntgPd
N
Y
Y
M9
Log control
O
O
N
M9-1
IntgPd
N
N
N
M10
Log
O
O
N
M12
GOOSE
O
O
Y
M13
GSSE
O
O
N
M14
Multicast SVC
O
O
N
M15
Unicast SVC
O
O
N
M16
Time
M
M
Y
M17
File transfer
O
O
Y
Reporting
Logging
GSE
Where: C2: Shall be "M" if support for LOGICAL-NODE model has been declared 106
NR ELECTRIC CO., LTD
Chapter 9 Communications
C3: Shall be "M" if support for DATA model has been declared C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared C5: Shall be "M" if support for Report, GSE, or SMV models has been declared M: Mandatory Y:
Supported by RCS-900 series relays
N: Currently not supported by RCS-900 series relays 9.6.5.3 ACSI Services Conformance Statement Service
Server/Publisher
RCS-974
Server S1
ServerDirectory
M
Y
Application association S2
Associate
M
Y
S3
Abort
M
Y
S4
Release
M
Y
M
Y
Logical device S5
LogicalDeviceDirectory
Logical node S6
LogicalNodeDirectory
M
Y
S7
GetAllDataValues
M
Y
S8
GetDataValues
M
Y
S9
SetDataValues
M
Y
S10
GetDataDirectory
M
Y
S11
GetDataDefinition
M
Y
S12
GetDataSetValues
M
Y
S13
SetDataSetValues
O
S14
CreateDataSet
O
S15
DeleteDataSet
O
S16
GetDataSetDirectory
M
Y
M
Y
Data
Data set
Substitution S17
SetDataValues
Setting group control S18
SelectActiveSG
M/O
Y
S19
SelectEditSG
M/O
Y
S20
SetSGValuess
M/O
Y
S21
ConfirmEditSGValues
M/O
Y
S22
GetSGValues
M/O
Y
NR ELECTRIC CO., LTD
107
Chapter 9 Communications
Service S23
Server/Publisher GetSGCBValues
RCS-974
M/O
Y
Reporting Buffered report control block S24
Report
M
Y
S24-1
data-change
M
Y
S24-2
qchg-change
M
Y
S24-3
data-update
M
Y
S25
GetBRCBValues
M
Y
S26
SetBRCBValues
M
Y
Unbuffered report control block S27
Report
M
Y
S27-1
data-change
M
Y
S27-2
qchg-change
M
Y
S27-3
data-update
M
Y
S28
GetURCBValues
M
Y
S29
SetURCBValues
M
Y
Logging Log control block S30
GetLCBValues
O
S31
SetLCBValues
O
S32
QueryLogByTime
O
S33
QueryLogAfter
O
S34
GetLogStatusValues
O
Log
Generic substation event model (GSE) GOOSE control block S35
SendGOOSEMessage
M
Y
S36
GetGoReference
O
S37
GetGOOSEElementNumber
O
Y
S38
GetGoCBValues
M
Y
S39
SetGoCBValuess
M
Y
S51
Select
O
S52
SelectWithValue
M
Y
S53
Cancel
M
Y
S54
Operate
M
Y
S55
Command-Termination
O
Y
S56
TimeActivated-Operate
O
Control
File transfer S57
GetFile
M/O
Y
S58
SetFile
O
Y
108
NR ELECTRIC CO., LTD
Chapter 9 Communications
Service
Server/Publisher
S59
DeleteFile
S60
GetFileAttributeValues
RCS-974
O M/O
Y
M
Y
Time SNTP
9.6.6 Logical Nodes 9.6.6.1 Logical Nodes Table The RCS-974 relays support IEC61850 logical nodes as indicated in the following table. Note that the actual instantiation of each logical node is determined by the product order code. Nodes
RCS-974
L: System Logical Nodes LPHD: Physical device information
YES
LLN0: Logical node zero
YES
P: Logical Nodes For Protection Functions PDIF: Differential
-
PDIR: Direction comparison
-
PDIS: Distance
-
PDOP: Directional overpower
-
PDUP: Directional underpower
-
PFRC: Rate of change of frequency
-
PHAR: Harmonic restraint
-
PHIZ: Ground detector
-
PIOC: Instantaneous overcurrent
-
PMRI: Motor restart inhibition
-
PMSS: Motor starting time supervision
-
POPF: Over power factor
-
PPAM: Phase angle measuring
-
PSCH: Protection scheme
-
PSDE: Sensitive directional earth fault
-
PTEF: Transient earth fault
-
PTOC: Time overcurrent
YES
PTOF: Overfrequency
-
PTOV: Overvoltage
-
PTRC: Protection trip conditioning
YES
PTTR: Thermal overload
-
PTUC: Undercurrent
-
PTUV: Undervoltage
-
PUPF: Underpower factor
-
PTUF: Underfrequency
-
PVOC: Voltage controlled time overcurrent
-
NR ELECTRIC CO., LTD
109
Chapter 9 Communications
Nodes
RCS-974
PVPH: Volts per Hz
-
PZSU: Zero speed or underspeed
-
R: Logical Nodes For Protection Related Functions RDRE: Disturbance recorder function
YES
RADR: Disturbance recorder channel analogue
-
RBDR: Disturbance recorder channel binary
-
RDRS: Disturbance record handling
-
RBRF: Breaker failure
-
RDIR: Directional element
-
RFLO: Fault locator
-
RPSB: Power swing detection/blocking
-
RREC: Autoreclosing
-
RSYN: Synchronism-check or synchronizing
-
C: Logical Nodes For Control CALH: Alarm handling
-
CCGR: Cooling group control
-
CILO: Interlocking
-
CPOW: Point-on-wave switching
-
CSWI: Switch controller
-
G: Logical Nodes For Generic References GAPC: Generic automatic process control GGIO: Generic process I/O GSAL: Generic security application
- YES -
I: Logical Nodes For Interfacing And Archiving IARC: Archiving
-
IHMI: Human machine interface
-
ITCI: Telecontrol interface
-
ITMI: Telemonitoring interface
-
A: Logical Nodes For Automatic Control ANCR: Neutral current regulator
-
ARCO: Reactive power control
-
ATCC: Automatic tap changer controller
-
AVCO: Voltage control
-
M: Logical Nodes For Metering And Measurement MDIF: Differential measurements
-
MHAI: Harmonics or interharmonics
-
MHAN: Non phase related harmonics or interharmonic
-
MMTR: Metering
-
MMXN: Non phase related measurement
-
MMXU: Measurement MSQI: Sequence and imbalance
110
YES -
NR ELECTRIC CO., LTD
Chapter 9 Communications
Nodes MSTA: Metering statistics
RCS-974 -
S: Logical Nodes For Sensors And Monitoring SARC: Monitoring and diagnostics for arcs
-
SIMG: Insulation medium supervision (gas)
-
SIML: Insulation medium supervision (liquid)
-
SPDC: Monitoring and diagnostics for partial discharges
-
X: Logical Nodes For Switchgear TCTR: Current transformer
-
TVTR: Voltage transformer
-
Y: Logical Nodes For Power Transformers YEFN: Earth fault neutralizer (Peterson coil)
-
YLTC: Tap changer
-
YPSH: Power shunt
-
YPTR: Power transformer
-
Z: Logical Nodes For Further Power System Equipment ZAXN: Auxiliary network
-
ZBAT: Battery
-
ZBSH: Bushing
-
ZCAB: Power cable
-
ZCAP: Capacitor bank
-
ZCON: Converter
-
ZGEN: Generator
-
ZGIL: Gas insulated line
-
ZLIN: Power overhead line
-
ZMOT: Motor
-
ZREA: Reactor
-
ZRRC: Rotating reactive component
-
ZSAR: Surge arrestor
-
ZTCF: Thyristor controlled frequency converter
-
ZTRC: Thyristor controlled reactive component
-
1)
9.7 Front EIA(RS)232 Interface Communication The front communication port is provided by a DB9 female D-type connector located under the small hinged cover on the front panel. It provides RS232 serial data communication and is intended for use with a PC locally to the relay (up to 15m distance). This port supports the courier communication protocol only. Courier is the communication language developed by NR (NR) to allow communication with its range of protection relays. The front port is particularly designed for use with relays settings program RCSPC which is a Windows based software package.
NR ELECTRIC CO., LTD
111
Chapter 9 Communications
The pin connections of relay’s DB9 front prot are as follows: Pin No.2 Tx Transmit data Pin No.3 Rx Receive data Pin No.5 common None of the other pins are connected in the relays. The relays should be connected to the serial port of a PC, usually called as COM1 or COM2. The serial port pin connections, which is DB9 male, is as below (if in doubt check you PC manual): Pin No.2 Rx Transmit data Pin No.3 Tx Receive data Pin No.5 common For successful data communication, the Tx pin on the relays must be connected to the Rx pin on the PC, and Rx pin on the relay must be connected to Tx pin on the PC as shown in Figure 9.7-1. NOTE: The baud rate for this port is fixed at 9600 bps.
Figure 9.7-1
Front panel RS232 port communication connection
9.8 Communication with Printer When communicating locally with a printer using the rear series port, a special connection line is necessary which is provided by manufacture of the equipment. There are two parameters need to be set in RCS-974 for communication with printer, [Printer_Baud] and [En_Auto_Print], the former decides the communication speed and the later decides the printer’s activating way. Please refer to the section “Equipment Settings” for details.
112
NR ELECTRIC CO., LTD
Chapter 9 Communications
9.9 Communication with External Time Synchronization Source The clock function (Calendar clock) is used for time-tagging for the following purposes:
Event records
Disturbance records/Fault records
Metering
Automatic supervision
Display of the system quantities in LCD
Display of the fault records in LCD
Display of the automatic monitoring results in LCD
When the relays are connected to the GPS clock, all the relay clocks are synchronized with the external clock. Please refer to the section “Time Synchronization” for details.
NR ELECTRIC CO., LTD
113
Chapter 9 Communications
114
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
Chapter 10 Commissioning and Installation 10.1 Introduction The chapter contains instructions on how to install, commission and maintenance the protection equipment. It can also be used as a reference if a periodic test is performed. The chapter covers procedures for mechanical and electrical installation, energizing and checking of external circuitry, setting and configuration as well as verifying settings and performing a directionality test. The chapter contains the following information: 1)
The “Safety information” presents warning and note signs, which the user should draw attention to.
2)
The “Overview” gives an overview over the major task when installing and commissioning the protection equipment.
3)
The “Unpacking and checking the protection equipment” contains instructions on how to receive the protection equipment.
4)
The “Installing the protection equipment” contains instructions on how to install the protection equipment.
5)
The “Checking the external circuitry” contains instructions on how to check that the protection equipment is properly connected to the protection system.
6)
The “Energizing the protection equipment” contains instructions on how to start-up the protection equipment.
7)
The “Setting the protection equipment” contains instructions on how to download settings and configuration to the protection equipment.
8)
The “Establishing connection and verifying communication” contains instructions on how to verify the communication.
9)
The “Verifying settings by secondary injection” contains instructions on how to verify that each included function operates correctly according to the set value.
10) The “Final check” contains instructions on how to do final check to make the equipment ready for being put into service. The chapter is addressing the installation, commissioning and maintenance personnel responsible for taking the protection into normal service and out of service. The installation personnel must have a basic knowledge in handling electronic equipment. The commissioning and maintenance personnel must be well experienced in using protection equipment, test equipment, protection functions and the configured functional logics in the protection.
NR ELECTRIC CO., LTD
115
Chapter 10 Commissioning and Installation
10.2 Safety Information This section contains safety information. Warning signs are presented which attend the user to be careful during certain operations in order to avoid human injuries or damage to equipment.
Warning signs WARNING!
Strictly follow the company and country safety regulations. Working in a high voltage environment requires serious approach to avoid human injuries and damage to equipment.
Do not touch circuitry during operation. Potentially lethal voltages and currents are present.
Always avoid touching the circuitry when the cover is removed. The product contains electronic circuitries which can be damaged if exposed to static electricity (ESD). The electronic circuitries also contain high voltage which is lethal to humans.
Always use suitable isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present.
Never connect or disconnect a wire and/or a connector to or from a protection equipment during normal operation. Hazardous voltages and currents are present that may be lethal. Operation may be disrupted and protection equipment and measuring circuitry may be damaged.
Always connect the protection equipment to protective ground, regardless of the operating conditions. This also applies to special occasions such as bench testing, demonstrations and off-site configuration. Operating the protection equipment without proper grounding may damage both terminal and measuring circuitry, and may cause injuries in case of an accident.
Never disconnect a secondary connection of current transformer circuit without short-circuiting the transformer’s secondary winding. Operating a current transformer with the secondary winding open will cause a massive potential build-up that may damage the transformer and may cause injuries to humans.
Never unmount the front or back cover from a powered equipment or from a protection equipment connected to powered circuitry. Potentially lethal voltages and currents are present.
Caution signs CAUTION!
116
Always transport modules using certified conductive bags. Always handle modules using NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
a conductive wrist strap connected to protective ground and on a suitable antistatic surface. Electrostatic discharge (ESD) may cause damage to the module.
Do not connect live wires to the protection equipment. Internal circuitry may be damaged.
Always use a conductive wrist strap connected to protective ground when replacing modules. Electrostatic discharge (ESD) may damage the module and protection equipment circuitry.
Take care to avoid electrical shock if accessing wiring and connection protection equipment when installing and commissioning.
Note signs NOTE!
Changing the active setting group will inevitably change the protection equipment’s operation. Be careful and check regulations before making the change.
The protection assembly is designed for a maximum continuous current of four times rated value.
Activating the other setting group without proper configuration may seriously affect the protection equipment’s operation.
10.3 Overview The settings for each function must be calculated before the commissioning task can start. A configuration, made in the configuration and programming tool, must also be available if the protection equipment does not have a factory configuration downloaded. The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle. The connection to the protection system has to be checked in order to verify that the installation was successful. The installation and commissioning task starts with configuring the digital communication modules, if included. The protection equipment can then be configured and set, which means that settings and a configuration has to be applied if the protection equipment does not have a factory configuration downloaded. Then the operation of each included function according to applied settings has to be verified by secondary injection. A complete check of the configuration can then be made. A conformity test of the secondary system has also to be done. When the primary system has been energized a directionality check should be made.
10.4 Unpacking and Checking The Protection Equipment Procedure 1)
Remove the transport casing.
NR ELECTRIC CO., LTD
117
Chapter 10 Commissioning and Installation
2)
Visually inspect the protection equipment.
Carefully examine the protection panel, protection equipment inside and other parts inside to see that no physical damage has occurred since installation. The rating information should be given for the protection equipment. The rating information of other auxiliary protections should be checked to ensure it is correct for the particular installation.
Panel wiring: Check the conducting wire used in the panel to assure that their cross section meet the requirement. Carefully examine the wiring to see that they are no connection failure exists. Label: Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to make sure that their labels meet the requirements of this project. Equipment plug-in modules: Check each plug-in module of the equipments on the panel to make sure that they are well installed into the equipment without any screw loosened. Earthing cable: Check whether the earthing cable from the panel terminal block is safely screwed to the panel steel sheet. Switch, keypad, isolator links and push button: Check whether all the switches, equipment keypad, isolator links and push buttons work normally and smoothly. 3)
Check that all items are included in accordance with the delivery documents.
The user is requested to check that all software functions are included according to the delivery documents after the terminal has been energized. 4)
Check for transport damages.
These product checks cover all aspects of the protection, which should be checked to ensure that the protection not only has not been physically damaged prior to commissioning but also functions correctly and all input quantity measurements are within the stated tolerances.
10.5 Installing the Protection Equipment 10.5.1 Overview The mechanical and electrical environmental conditions at the installation site must be within permissible range according to the technical data of the protection equipment. Dusty, damp places, places liable to rapid temperature variations, powerful vibrations and shocks, surge 118
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
voltages of high amplitude and fast rise time, strong induced magnetic fields or similar extreme conditions should be avoided. Please refer to Chapter 2 for details. Sufficient space must be available in front of and at rear of the protection panel to allow access for maintenance and future modifications. Flush mounted protection equipment should be mounted so that equipment modules can be added and replaced without excessive demounting.
10.5.2 Dimensions The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral faceplate and plug terminal block on backboard for external connections. RCS-974 is IEC 4U high and 19” wide. Following two figures shows its dimensions and the panel cut-out. 482.6 291
465.0
177.0 101.6
NANJING NARI-RELAYS ELECTRIC CO.,LTD.
MECH 9
HEALTH ALARM TRIP1
MECH 10
TRIP2
MECH 11
MECH 1
MECH 12
MECH 2
MECH 13
MECH 3
MECH 14
MECH 4
MECH 15 MECH 16
GR P
MECH 8
RCS-974 TRANSFORMER AUXILIARY RELAY
ESC
MECH 7
ENT
MECH 5 MECH 6
TARGET RESET
Equipment Dimensions
179.0
101.6
Figure 10.5-1
Figure 10.5-2
Panel cut-out dimensions
10.5.3 Grounding Guidelines Switching operations in HV installations generate transient over voltages on control signal cables. There is also a background of electromagnetic RF fields in electrical installations that can induce spurious currents in the devices themselves or the leads connected to them. All these influences can influence the operation of electronic apparatus. On the other hand, electronic apparatus can transmit interference that can disrupt the operation of other apparatus.
NR ELECTRIC CO., LTD
119
Chapter 10 Commissioning and Installation
In order to minimize these influences as far as possible, certain standards have to be observed with respect to grounding, wiring and screening. NOTE:
All these precautions can only be effective if the station ground is of good quality.
10.5.4 Cubicle Grounding The cubicle must be designed and fitted out such that the impedance for RF interference of the ground path from the electronic device to the cubicle ground terminal is as low as possible. Metal accessories such as side plates, blanking plates etc., must be effectively connected surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF interference. The contact surfaces must not only conduct well, they must also be non-corroding. NOTE: If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it forming a resonant circuit at certain frequencies that would amplify the transmission of interference by the devices installed and also reduce their immunity to induced interference. Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be effectively grounded to the frame by three braided copper strips (refer to Figure 10.5-3). The metal parts of the cubicle housing and the ground rail are interconnected electrically conducting and corrosion proof. The contact surfaces shall be as large as possible. NOTE: For metallic connections please observe the voltage difference of both materials according to the electrochemical code. The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip (braided copper).
Figure 10.5-3 Cubicle grounding system
120
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
10.5.5 Ground Connection on the Device There is a ground terminal on the rear panel (refer to Figure 10.5-4), and the ground braided copper strip can be connected with it. Take care that the grounding strip is always as short as possible. The main thing is that the device is only grounded at one point. Grounding loops from unit to unit are not allowed. There are some ground terminals on some connectors of the equipments, and the sign is “GND”. All the ground terminals are connected in the cabinet of this equipment. So, the ground terminal on the rear panel (refer to Figure 10.5-4) is the only ground terminal of this device.
Figure 10.5-4 Ground terminal
10.5.6 Grounding Strips and Their Installation High frequency currents are produced by interference in the ground connections and because of skin effect at these frequencies, only the surface region of the grounding strips is of consequence. The grounding strips must therefore be of (preferably tinned) braided copper and not round copper conductors, as the cross-section of round copper would have to be too large. Data of braided copper strip: threaded M4, 4.0mm2. Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected. The surfaces to which the grounding strips are bolted must be electrically conducting and non-corroding. The following figure shows the ground strip and termination.
Figure 10.5-5 Ground strip and termination
10.5.7 Making the Electrical Connections Always make sure established guidelines for this type of terminal is followed during installation. When necessary, use screened twisted-pair cables to minimize susceptibility. Otherwise, use any kind of regular nonscreened tinned RK cable or equivalent. NR ELECTRIC CO., LTD
121
Chapter 10 Commissioning and Installation
When using screened cabling always use 360° full screen cable bushing to ensure screen coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing current and voltage measuring signals in the same cable. Also use separate cables for control and measuring circuits. 1)
Connecting the CT circuits:
Heavy-duty terminal block, M4 threaded terminal ends. 2)
Connecting the auxiliary power:
Auxiliary power cords can be directly screw fixed on the rear panel of DC board. Refer to section 6.2.1. 3)
Input/output signal connectors:
Welding terminals. Those devices are supplied with sufficient M4 screws for making connections to the rear mounted terminal blocks using ring terminals, with a recommended maximum of two ring terminals per terminal. To meet the insulation requirements of the terminal block, for the sake of safety, an insulating sleeve should be fitted over the ring terminal after crimping. The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks, except the EIA RS-485 port, should have a minimum voltage rating of 300Vrms. It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits must never be open. 4)
Connecting to protective ground:
Connect the unit to the grounding bar of the cubicle with green/yellow conductor; connected to the protective Earthing terminal at the back of the PWR board. Refer to section 6.2.1. Attend that the earth wire must be as short as possible. All cautions have to be taken to ensure the best electrical conductivity, particularly the contact quality, stainless conductor. The impedance between the equipment Earthing terminal and the Earth must be less than 20mΩ under 12Volt, 50Hz. What matters is that the device has to be only grounded at one point. Loop grounding from unit to unit is not allowed. 5)
Installing the optic fibres
Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey (transmit) back-side connectors. Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with loose fit. NOTE: Always hold the connector, never the cable, when connecting or disconnecting
122
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
optical fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre damping thus making communication impossible. 6)
Installing the RS-485 serial port communication cables:
When using galvanic connection between the synchronizer equipment and communication equipment or point-to-point galvanic connection between two equipments it is essential that the cable installation is carefully done. This is true regardless of type of module used, only the possible length of the cable differs. The factors that must be taken into account is the susceptibility for noise disturbance, due to that the levels of the communication signal are very low. For a best result, a cable with twisted pairs with screen should be used. RS-485 serial communication interface, a termination 120-ohm resistor has to be connected at each extremity of the bus. Refer to Chapter 9.
10.6 Check the External Circuitry The user must check the installation, which includes verifying that the relay is connected to the other parts of the protection system. This is done with the relay and all connected circuits de-energized. 1)
Checking the CT circuits
Check that the wiring is in strict accordance with the supplied wiring diagram. Test the circuitry. The following tests are recommended:
Polarity check
CT circuit current measurement (primary injection test)
Grounding check
The polarity check verifies the integrity of the circuits and the phase relationship. The check should be performed as close as possible to the relay. The primary injection test verifies the CT ration and the wiring all the way through from the primary system to the relay. Injection must be performed for each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases and the neutral line are measured. 2)
Checking the power supply
Check that the value of the auxiliary supply voltage remains with the permissible range under all operating conditions. Check that the polarity is correct according to the instruction manual on the rear plate of DC board. Refer to section 6.2.1. 3)
Checking binary input circuits
Preferably, disconnect the binary input connector form the binary input cards. Check all connected signals so that both input level and polarity are in accordance with the relay’s specifications.
NR ELECTRIC CO., LTD
123
Chapter 10 Commissioning and Installation
NOTE The binary inputs may be energized from an external dc auxiliary supply (e.g. the station battery) in some installations. Check that this is not the case before connecting the field voltage otherwise damage to the protection may result. The status of each binary input can be viewed using either RCSPC software installed in a portable PC or by checking the front man-machine interface LCD. When each binary input is energized the display will change to indicate the new state of the inputs. 4)
Checking binary output circuits
Preferably, disconnect the binary output connector form the binary output cards. Check all connected signals so that both load and polarity are in accordance with the relay’s specifications.
10.7 Energizing the Protection Equipment Before the procedures in this section can be carried out the connection to external circuitry must have been checked which ensures that the installation was made correctly. The user must energies the power supply to the relay to start it up. This could be done in a numerous of ways, from energizing a whole cubicle to energizing a single relay. The user should reconfigure the relay settings. The relay time must be set. The self-supervision function should also be checked to verify that the relay unit operates properly. The user could also check the software version, the relay’s serial number, the installed modules, and their ordering number to ensure that the relay is according to delivery and ordering specifications. 1)
Checking front panel LCD display
Connect the relay to DC power supply correctly and turn the relay on. Check program version and forming time displayed in command menu to ensure that are corresponding to what ordered. 2)
Setting the date and time of the protective device
If the time and date is not being maintained by substation automation system, the date and time should be set manually. Set the date and time to the correct local time and date using menu item “CLOCK”. Refer to the section “Adjust the Clock” for detailed procedures. In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will be maintained. Therefore when the auxiliary supply is restored the time and date will be correct and not need to set again. To test this, remove the auxiliary supply from the relay for approximately 30s. After being re-energized, the time and date should be correct. 3)
Checking light emitting diodes (LEDs)
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
124
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
the protective device is healthy. The relay has latched signal relays which remember the state of the trip, auto-reclose when the relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing required for that that LED because it is known to be operational. It is likely that alarms related to voltage transformer supervision will not reset at this stage.
10.8 Setting the Protection Equipment The customer specific values for each setting parameter have to be available. Each function included in the relay has several setting parameters which has to be set in order to make the relay behave as intended. A default value is provided for each parameter from factory. All settings can be:
Download from a PC or laptop with RCSPC software or remotely by SCADA. Front port communication has to be established before the settings can be downloaded. Input manually through the local HMI (refer to section “Input Operation through Keypad”).
To change settings through the local HMI need a password which is “+”, “◄”, “▲” and “-” keyboard on the front panel. Unless previously agreed to the contrary, the customer will be responsible for determining the application-specific settings to be applied to the protection and for testing of any scheme logic applied by external wiring and/or configuration of the protection’s internal programmable scheme logic.
10.9 Establishing Connection and Verifying Communication This test should only be performed where the protection is to be accessed from a remote location and will vary depending on the communications standard being adopted. It is not the intention of the test to verify the operation of the complete system from the relay to the remote location, just the protection’s rear communications port and any protocol converter necessary.
10.10 Verifying Settings by Secondary Injection Required tools for testing of a protective device: Minimum equipment required:
Multifunctional dynamic current and voltage injection test set with interval timer.
NR ELECTRIC CO., LTD
125
Chapter 10 Commissioning and Installation
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V respectively.
Continuity tester (if not included in the multimeter).
Phase angle meter.
Phase rotation meter. NOTE: Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for insulation resistance test when required). A portable PC, with appropriate software (this enables the rear communications port to be tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
An EPSON® 300K printer.
RCS-9000 serials dedicated protection tester TEST or HELP-90.
At the same time, the calculated settings, substation configuration diagram, the protective device diagram and the instruction manual is essential to test the protective device. The equipment has to be set before the testing can start. Only the functions that are used should be tested. The response from a test can be viewed in different ways:
Binary output signals
Service values in the local HMI
A PC with RCSPC software or SCADA or master station
All used setting groups should be tested. The user can release the functions to be tested and prevent other functions from operation by setting the corresponding parameters. The user could also energize the binary input [BI_BlkComm] to disable communication function to ensure that no events are reported to remote station during the test. The setting checks ensure that all of the application-specific protection settings (i.e. both the protection’s function and programmable scheme logic settings), for the particular installation, have been correctly applied to the protection.
10.10.1 Insulation Test (if required) Insulation resistance tests are only necessary during commissioning if it is required for them to be done and they have not been performed during installation. Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation 126
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
Voltage transformer circuits
DC power supply
Optic-isolated control inputs
Output contacts
Communication ports
The insulation resistance should be greater than 100MΩ at 500V.
10.10.2 Current Measurement Check This test verifies that the accuracy of voltage measurement is within the acceptable tolerances. Checking its magnitude using a multimeter. The corresponding reading either in the protection’s menus “DSP METERING”, “CPU METERING” or a portable computer connected to the front communication port with software RCSPC. The measurement accuracy of the protection is ±5%. However, an additional allowance must be made for the accuracy of the test equipment being used. NOTE: The closing circuit should remain isolated during these checks to prevent accidental operation of the associated circuit breaker. Group No.
Item
Input Value
Measurement (on LCD) Angle
Value
Angle
Ia_1 The first group of CT
Ib_1 Ic_1 3I0_1 I2_1 Ia_2
The second group of CT
Ib_2 Ic_2 3I0_2 I2_2
10.10.3 Testing the Binary Inputs This test checks that all the binary inputs on the equipment are functioning correctly. The binary inputs should be energized one at a time, see external connection diagrams for terminal numbers. Ensure that the voltage applied on the binary input must be within the operating range. The status of each binary input can be viewed using menu item “BI STATE”. Sign “1” denotes an energized input and sign “0” denotes a de-energized input. NR ELECTRIC CO., LTD
127
Chapter 10 Commissioning and Installation
Binary Inputs testing checkout Terminal No.
Signal Name
BI Status on LCD
Correct?
Test method: To unplug all the terminals sockets of this protective device, and do the Insulation resistance test for each circuit above with an electronic or brushless insulation tester. On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the protection.
10.10.4 Mechanical Protection 10.10.4.1 MR for Warning Energize certain binary input of [BI_MRn], n = 10, 11,…16. Related LED labeled as [MECHn] is lit on and relevant normal open contacts of signal relays are closed. Also, check the [ALM REPORT]. 10.10.4.2 Tripping Directly Energize certain binary input of [BI_MRn], n = 5, 6, 7, 8, 9. Related LED labeled as [MECHn] is lit on and relevant normal open contacts of signal relays and output relays are closed. Also, check the [ALM REPORT]. 10.10.4.3 Tripping with Time Delay Energize binary input [En_Dly_MR], and certain binary input of [BI_MRn] (n = 1, 2 and 3) and then related LED labeled as [MECHn] (n=1,2 and 3) is lit at once. LED [TRIP 2] is also lit with time delay and relevant normal open contacts of signal relays and output relays are closed. Also, check the [TRP REPORT]. When Check MR1 protection, please check MR1 operates during two situations with logic setting [En_FixDly_MR1] is set as “1” and “0” respectively.
10.10.5 Pole Disagreement Protection Consider to release used start criteria. Refer to 3.3. If the PD is activated, LED labeled [TRIP1] is lit on and several relevant normal open contacts of signal relays and output relay are closed. 10.10.5.1 Pole Disagreement Protection Delay 1 Check the PD1 in the following ways: z
128
Set [En_PD1] as “1” and energize binary input [EBI_PD]. Then energize binary input [BI_PD_CB] without injecting any current. Check that whether the PD1 is activated after time delay [t_PD1].
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
z
Set [En_PD1] and [En_NegOC_PD] as “1”, and energize binary input [EBI_PD]. Then energize [BI_PD_CB] and inject current via terminals on No.2 AC board to make I2_CTn>[I_NegOC_PD_CTn], where n represents the CT group number. Check that whether the PD1 is activated after time delay [t_PD1].
z
Set [En_NegOC_PD] as “0”, [En_PD1] and [En_ROC_PD] as “1”, and energize binary input [EBI_PD]. Then energize [BI_PD_CB] and inject current via terminals on No.2 AC board to make 3I0_CTn>[I_ROC_PD_CTn], where n represents the CT group number. Check that whether the PD1 is activated after time delay [t_PD1].
z
Please ensure the time of keep injecting current should be longer than the time delay [t_PD1].
10.10.5.2 Pole Disagreement Protection Delay 2 Since PD2 can be blocked by an external binary input [BI_ExtCtrlPD2], firstly, set [En_ExtCtrlPD2] as “0” to make PD2 out of this external control. After the accomplishment of the following steps, set [En_ExtCtrlPD2] as “1”, choose one of the following three items of the follow ways and do it again. Check that whether the PD2 is activated after a time delay [t_PD2]. Check the PD2 in the following ways: z
Set [En_NegOC_PD], [En_ROC_PD] and [En_OC_PD2] as “0”, [En_PD2] as “1”, and energize binary input [EBI_PD]. Then energize [BI_PD_CB] without injecting any current. Check that whether the PD2 is activated after time delay [t_PD2].
z
Set [En_ROC_PD] and [En_OC_PD2] as “0”, [En_PD2] and [En_NegOC_PD] as “1”, and energize binary input [EBI_PD]. Then energize [BI_PD_CB] and inject current via terminals on No.2 AC board to make I2_CTn>[I_NegOC_PD_CTn], where n represents the CT group number. Check that whether the PD2 is activated after time delay [t_PD2].
z
Set [En_OC_PD2] and [En_NegOC_PD] as “0”, [En_PD2] and [En_ROC_PD] as “1”, and energize binary input [EBI_PD]. Then energize [BI_PD_CB] and inject current via terminals on No.2 AC board to make 3I0_CTn>[I_ROC_PD_CTn], where n represents the CT group number. Check that whether the PD2 is activated after time delay [t_PD2].
z
Set [En_ROC_PD] and [En_NegOC_PD] as “0”, [En_PD2] and [En_OC_PD2] as “1”, enable the hard switch link [EBI_PD], energize [BI_PD_CB] and inject current via terminals on No.2 AC board to make Imax_CT1>[I_OC_BFI_CT1] ( maximum value of three phase current greater than [I_OC_BFI_CT1]). Check that whether the PD2 is activated after time delay [t_PD2].
z
Please ensure the time of keep injecting current should be longer than the time delay [t_PD2].
Please note three current control elements mentioned above are “OR” relation to release blocking of pole disagreement protection delay 2. Binary input [BI_ExtCtrlPD2] is independent blocking criterion to block PD2.
NR ELECTRIC CO., LTD
129
Chapter 10 Commissioning and Installation
10.10.6 Breaker Failure Initiation Consider to release used start criteria. Refer to 3.4. The breaker failure initiation should be tested in cooperation with some other relays, and in particular with external CBF protection relay. Since BFI can be blocked by an external binary input [BI_PD_CB], [BI_52a] and [BI_ExTCtrlBFI], firstly, set [En_PD_Ctrl_BFI], [En_52aCtrlBFI] and [En_ExTCtrlBFI] as “0” to make BFI out of these external controls. After the accomplishment of the following steps, set [En_PD_Ctrl_BFI], [En_52aCtrlBFI] or [En_ExTCtrlBFI] as “1” respectively, corresponding energize and de-energize [BI_PD_CB], [BI_52a] or [BI_ExTCtrlBFI], choose one of the last three items of the follow ways and do it again. Check that whether the BFI is activated after time delay [t_BFI2]. Set [En_BFI] as “1”, check the BFI2 in the following ways: z
Set [En_ROC_BFI] and [En_NegOC_BFI] as “0”, and inject current via terminals on No.2 AC board to make Imax_CT1>[I_OC_BFI_CT1] ( maximum value of three phase current greater than [I_OC_BFI_CT1]). Check that whether the BFI is activated after time delay [t_BFI1] or [t_BFI2].
z
Set [En_ROC_BFI] as “0”, [En_NegOC_BFI] as “1”, and inject current via terminals on No.2 AC board to make I2_CTn>[I_NegOC_BFI_CTn], where n represents the CT group number. Check that whether the BFI is activated after time delay [t_BFI1] or [t_BF2].
z
Set [En_NegOC_BFI] as “0”, [En_ROC_BFI] as “1”, inject current via terminals on No.2 AC board to make 3I0_CTn>[I_ROC_BFI_CTn], where n represents the CT group number. Check that whether the BFI is activated after time delay [t_BFI1] or [t_BFI2].
z
Please ensure the time of keep injecting current should be longer than the time delay [t_BFP1] or [t_BFP2].
Please note three current elements mentioned above are “OR” relation to pick up breaker failure initiation. Binary inputs [BI_PD_CB], [BI_52a] and [BI_ExTCtrlBFI] are “AND” relation to release blocking of breaker failure protection.
10.10.7 Secondary Circuit Abnormality and Failure 10.10.7.1 CT Circuit Failure Slowly inject a three unbalanced current to make the negative current of CT1 or CT 2 greater than 0.06In (In is rated secondary current), 10s later the equipment will generate a CT exception alarm. The LED “ALARM” will be extinguished automatically 20s later after the three-phase current returns to normal state. 10.10.7.2 Contact of Pole Disagreement Position Abnormality When binary input [BI_PD_CB] keeps being energized for 10s, LED “ALARM” is lit on with report [Alm_BI_ExTrp] is issued on LCD. The LED “ALARM” will be extinguished automatically 20s later after the binary input is de-energized.
130
NR ELECTRIC CO., LTD
Chapter 10 Commissioning and Installation
10.10.7.3 Contact of External Tripping Abnormality When any one of binary inputs [BI_ExTCtrlBFI] and [BI_ExTCtrlPD2] keeps being energized for 10s, LED “ALARM” is lit on with report [Alm_BI_ExTrp] is issued on LCD. The LED “ALARM” will be extinguished automatically 20s later after binary input [BI_ExTCtrlBFI] or [BI_ExtCtrlPD2] is de-energized.
10.10.8 Print Fault Report In order to acquire the details of protection operation, it is convenient to print the fault report of protection device. The printing work can be easily finished when operator presses the print button on panel of protection device to energize binary input [BI_Print] or operate control menu. What should be noticed is that only the latest fault report can be printed if operator presses the print button. A complete fault report includes the content shown as follows. 1) Trip event report 2) Binary input when protection devices start 3) Self-check and the transition of binary input in the process of devices start 4) Fault wave forms compatible with COMTRADE 5) The setting value when the protection device trips
10.10.9 Final Check After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the external wiring from the protection in order to perform the wiring verification tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram. Ensure that the protection has been restored to service. If the protection is in a new installation or the circuit breaker has just been maintained, the circuit breaker maintenance and current counters should be zero. If a test block is installed, remove the test plug and replace the cover so that the protection is put into service. Ensure that all event records, fault records, disturbance records and alarms have been cleared and LED’s has been reset before leaving the protection.
NR ELECTRIC CO., LTD
131
Chapter 10 Commissioning and Installation
132
NR ELECTRIC CO., LTD
Chapter 11 Maintenance
Chapter 11 Maintenance NR numerical relay RCS-974 is designed to require no special maintenance. All measurement and signal processing circuit are fully solid state. All input modules are also fully solid state. The output relays are hermetically sealed. Since the device is almost completely self-monitored, from the measuring inputs to the output relays, hardware and software defects are automatically detected and reported. The self-monitoring ensures the high availability of the device and generally allows for a corrective rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are not required. Operation of the device is automatically blocked when a hardware failure is detected. If a problem is detected in the external measuring circuits, the device normally only provides alarm messages.
11.1 Appearance Check The relay case should be clean without any dust stratification. Case cover should be sealed well. No component has any mechanical damage and distortion, and they should be firmly fixed in the case. Relay terminals should be in good condition. The keys on the front panel with very good feeling can be operated flexibly. It is only allowed to plug or withdraw relay board when the supply is reliably switched off. Never allow the CT secondary circuit connected to this equipment to be opened while the primary system is live when withdrawing an AC module. Never try to insert or withdraw the relay board when it is unnecessary. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual inline components must be well plugged.
11.2 Failure Tracing and Repair Failures will be detected by automatic supervision or regular testing. When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on the front panel with LED indicators and LCD display. It is also recorded in the event record. Failures detected by supervision are traced by checking the “ALM REPORT” screen on the LCD. When a failure is detected during regular testing, confirm the following:
Test circuit connections are correct
Modules are securely inserted in position
Correct DC power voltage is applied
Correct AC inputs are applied
Test procedures comply with those stated in the manual
NR ELECTRIC CO., LTD
133
Chapter 11 Maintenance
11.3 Replace Failed Modules If the failure is identified to be in the relay module and the user has spare modules, the user can recover the protection by replacing the failed modules. Repair at the site should be limited to module replacement. Maintenance at the component level is not recommended. Check that the replacement module has an identical module name (AI, PWR, CPU, SIG, BI, BO, etc.) and hardware type-form as the removed module. Furthermore, the CPU module replaced should have the same software version. In addition, the AI module, PWR module, BI module, IO module and RLY module replaced should have the same ratings. The module name is indicated on the top front of the module. The software version is indicated in LCD menu “VERSION”. CAUTION: When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. After replacing the CPU module, check the settings. 1)
Replacing a module
Switch off the DC power supply
Disconnect the trip outputs
Short circuit all AC current inputs and disconnect all AC voltage inputs
Unscrew the module. WARNING: Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It takes approximately 30 seconds for the voltage to discharge.
2)
Replacing the Human Machine Interface Module (front panel)
Open the relay front panel
Unplug the ribbon cable on the front panel by pushing the catch outside.
Detach the HMI module from the relay
Attach the replacement module in the reverse procedure.
3)
Replacing the AI, PWR, CPU, BI, IO, BO module
Unscrew the module connector
Unplug the connector from the target module.
Unscrew the module.
Pull out the module
134
NR ELECTRIC CO., LTD
Chapter 11 Maintenance
Inset the replacement module in the reverser procedure.
After replacing the CPU module, input the application-specific setting values again. WARNING: Units and modules may only be replaced while the supply is switched off and only by appropriately trained and qualified personnel. Strictly observe the basic precautions to guard against electrostatic discharge. WARNING: When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. After replacing the CPU module, check the settings. DANGER: After replacing modules, be sure to check that the same configuration is set as before the replacement. If this is not the case, there is a danger of the unintended operation of switchgear taking place or of protections not functioning correctly. Persons may also be put in danger.
11.4 Replace Button Battery When the voltage of button Battery on CPU board is below 2.5 volts (nominal voltage is 3 volts), please replace the button battery to ensure internal clock of CPU board running correctly.
11.5 Cleaning Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean the front panel. Do not use abrasive material or detergent chemicals.
11.6 Storage The spare relay or module should be stored in a dry and clean room. Based on IEC standard 60255-6 the storage temperature should be from-40°C to 70°C, but the temperature of from -10°C to 40°C is recommended for long-term storage.
NR ELECTRIC CO., LTD
135
Chapter 11 Maintenance
136
NR ELECTRIC CO., LTD
Chapter 12 Decommissioning and Disposal
Chapter 12 Decommissioning and Disposal 12.1 Decommissioning 12.1.1 Switching off To switch off the RCS-974, switch off the external miniature circuit breaker of the power supply.
12.1.2 Disconnecting Cables Disconnect the cables in accordance with the rules and recommendations made by relational department. DANGER: Before disconnecting the power supply cables that connected with the PWR module of the RCS-974 make sure that the external miniature circuit breaker of the power supply is switched off. DANGER: Before disconnecting the cables that are used to connect analog input module with the primary CTs, make sure that the primary CTs aren’t in service.
12.1.3 Dismantling The RCS-974 rack may now be removed from the system cubicle, after which the cubicles may also be removed. DANGER: When the station is in operation, make sure that there is an adequate safety distance to live parts, especially as dismantling is often performed by unskilled personnel.
12.2 Disposal In every country there are companies specialized in the proper disposal of electronic waste. NOTE: Strictly observe all local and national regulations when disposing of the device.
NR ELECTRIC CO., LTD
137
Chapter 12 Decommissioning and Disposal
138
NR ELECTRIC CO., LTD
Chapter 13 Manual Version History
Chapter 13 Manual Version History In the latest version of the instruction manual, several descriptions on existing features have been modified. Manual version and modification history records Manual Version Source
New 1.00
1.00
1.01
Software Version
Date
V1.11
2009-06-22
Form the original manual.
2010-12-02
1. Add a setting item “Language” for selecting default displaying language for equipment.. 2. Add menu item “Language” for selecting default displaying language for equipment.
V1.11ECKF101212
NR ELECTRIC CO., LTD
Description of change
139