TRANSFORMER
INSPECTION TEST PLAN
Prepared by:
PT Bambang Djaja
(Nur Aswan Darwis)
PT.BAMBANG DJAJA Jl. RUNGKUT INDUSTRI III/56 SURABAYA, INDONESIA, Fax. No. : (031) 8438350 - Telex 33295 BD SB IA Phone : (031) 8438703 (Hunting), 8438470, 8439688, 8414058
TRANSFORMER INSPECTION TEST PLAN Manufacturer : B & D No
Tests/Insp Item
Routine Test 1 Resistance measurement 2 Phase relation (vector group) test 3 Turn Ratio test
Standard/ Reference
IEC 60076
Activity/requirement
Performed on nominal tap
IEC 60076
IEC 60076
4
Insulation resistance
MFG STD
5
No load losses and excitation current ( magnetizing
IEC 60076
Performed on all position Performed between: HV - LV HV – G LV – G Performed on nominal tap position Under guaranteed value at rated KVA
Acceptance
Inspection Scope
B&D
PT Wasa Mitra Engineering
PT Rekadaya Elektrika
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
PT.BAMBANG DJAJA Jl. RUNGKUT INDUSTRI III/56 SURABAYA, INDONESIA, Fax. No. : (031) 8438350 - Telex 33295 BD SB IA Phone : (031) 8438703 (Hunting), 8438470, 8439688, 8414058
TRANSFORMER 6
7
8 9
10
current test) Impedance voltage and load losses ( Positive sequence impendance test) Applied voltage test
IEC 60076
P
F/W
F/W
Duration: 1 minutes Primary (BIL - kV ) : Secondary (BIL -) : Two time of rated Voltage 200 HZ, 30 seconds Rate of rise voltage 500V/sec Mushroom electrode 0,5 Bar positive pressure 24 hour
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W
IEC 60076
Induce voltage test Dielectric test for Oil
IEC 60076
Leak test
MFG STD
Site Test 1 Cek urutan Phasa 2 Insulation resistance
On nominal position Full Load Loss under guaranteed value at rated kVA Calculation based on 75 deg C
IEC 60156
MFG STD
Performed between: HV - LV HV – G LV – G
Type Test (between B&D and User) - >4000kVA Transformers Only
PT.BAMBANG DJAJA Jl. RUNGKUT INDUSTRI III/56 SURABAYA, INDONESIA, Fax. No. : (031) 8438350 - Telex 33295 BD SB IA Phone : (031) 8438703 (Hunting), 8438470, 8439688, 8414058
TRANSFORMER 1 2
3
Audible sound pressure level Temperature Test
IEC 60076
Peformed on Nominal Voltage
IEC 60076
Perform on Maximal Tap
Lightning Impulse Test
IEC 60076
Perform lightning impulse over voltage to each terminal base on it BIL
Legend: F = Inspect Within FAT SW = Spot Witness Inspection W = Witness inspection
P X S
Max 64 dB (0.3 m ONAN)
Oil Temperature Rise Winding Temperature Rise 20000V 125kV BIL 11000V 60kV BIL
= Perform = not applicable = Submit
R = Review M = Monitoring
P
F/W
F/W
P
F/W
F/W
P
F/W
F/W