14 0 3 MB
air-cooled screw liquid chiller
YGAS Series
Nomenclature YG A S XXX S A E 50 S A YORK chiller Design Level: A Air-cooled chiller Screw compressor Nominal Capacity (TR) Liquid Chiller Refrigerant: HFC-134a
S=Standard fan H=High pressure fan Power: 50=380V-3P-50HZ Power: 53=400V-3P-50HZ Power: 55=415V-3P-50HZ E: ARI design
Power: 50=380V-3P-50Hz 53=400V-3P-50Hz 55=415V-3P-50Hz
Specification General YORK YGAS series chillers are manufactured to the highest design and construction standards to ensure high performance, reliability and adaptability for all types of air conditioning installations. The units are designed for water cooling and to be located outside on the roof of a building or at ground level. The unit may contain one, two, or three refrigerant circuits. The units are completely factory-assembled with all interconnecting refrigerant piping and internal wiring, ready for field installation.
2
Prior to delivery, the unit is pressure tested, evacuated, and fully charged with refrigerant and lubrication oil. After assembly, an operational test is performed with water flowing through the cooler to ensure that each refrigerant circuit operates correctly. The unit structure is fabricated with heavy gauge, galvanized steel, which is coated with “Champagne” baked-on polyester powder paint.
Compressors The unit has accessible, direct drive semi-hermetic rotary twin-screw compressor(s). All rotating parts are statically and dynamically balanced to ensure high operational efficiencies and reliable performance. Stepless capacity control is achieved between 25% and 100% of full capacity for each compressor by regulating slide valve to fulfill the cooling load requirements. Motor - Motor cooling is provided by suction gas from the evaporator flowing across the motor. Redundant overload protection is provided using both internal thermistor and current overload protection on all three phases. Rotors -The rotors are housed in a cast iron compressor housing precision machined to provide optimal clearances for the rotors. Contact between the male and female rotor is primarily rolling on a contact band on each of the rotor’s pitch circle. This results in virtually no rotor wear and increased reliability, a trademark of the screw compressor. Housing - Cast iron compressor housing precisely machined for optimal clearances and superb efficiency. Entire compressor, from suction to discharge, has a Design Working Pressure (DWP) of 2.1MPa. Capacity Control - Microprocessor controls the load/ unload solenoid valve to drive the valve and achieve stepless and smooth capacity control from 100% to 25% of compressor capacity for each compressor. Isolation - Each compressor is mounted on isolator pads to reduce vibration transmission to the structure.
Evaporator The evaporator is a shell and tube, flooded type heat exchanger. A distributor trough provides uniform distribution of refrigerant over the entire shell length. A baffle plate is located above the tube bundle to prevent liquid refrigerant carryover into the compressor. The evaporator shell of each system contains a refrigerant relief valve. A 40mm diameter sight glass is installed at the appropriate position to allow visual inspection of refrigerant levels. The design working pressure is 2.3MPa for shell, 1.0MPa for tube side. The refrigerant side has a safety valve with trip pressure of 2.2MPa. The refrigerant side is manufactured and tested in accordance to China National Standard GB151. The removable compact water boxes are fabricated from steel. The design working pressure is 1MPa and the boxes are tested at 1.25MPa. Integral steel
water baffles provide the required pass arrangements. Stub-out water nozzle connections with flanges are welded to the water boxes. These nozzle connections are suitable for corresponding flanges, and are capped for shipment. Plugged 3/4”NPT drain and vent connections are provided in each water box. The evaporator shell is insulated with 19mm closed-cell material.
Condenser Coil -The fin and tube condenser coils are manufactured from seamless, internally enhanced, high-condensing coefficient, corrosion-resistant copper tubes arranged in staggered rows and mechanically expanded into corrosion resistant aluminum alloy fins with full height fin collars. The units also adopt Reversed “M” type Coil arrangement to achieve high efficiency heat transfer by optimizing the corner angle of the coils. A “silent night” mode can be provided by YGAS chiller. Customer can get the lower noise level by timing or manual driving the “silent night” on the control panel. The two speed fans equipped in chiller will switch to low speed automatically. Fans - The fans are dynamically and statically balanced, direct drive with corrosion resistant glass fiber reinforced composite blades molded into full airfoil cross section, providing vertical air discharge from extended orifices for efficiency and low sound. Motors - The motors are high-efficiency, direct drive, 6-pole, 3-phase, Class “F”, current overload protected with double sealed, permanently lubricated ball bearings.
Electronic Expansion Valve YGAS series chillers are equipped with advanced electronic expansion valve to ensure accurate control at various load conditions. The electronic expansion valve is able to inject precise amounts of liquid into the evaporators for the system. The electronic expansion valve modulation is electronically controlled by activation of the AST stepper motor. The motor is a 2-phase bi-polar type, which stays in position unless power pulses from a driver to initiate the two discrete sets of motor stator windings for rotation in either direction. The direction depends on the phase relationship of the power pulses, whose value again is decisive for the travel. The motor operates the spindle, where rotating movements are transformed into linear motion by the transmission in the cage assembly.
3
Refrigerant Circuits
Power and Control Panels
Unit piping is TP2 copper with brazed joints. The liquid line includes: electronic expansion valve, angle valve, ball valve, sight glass with moisture-indicator, drier filter, etc. The refrigeration system is pressure-tested, leak-tested, and evacuated then charged with refrigerant. The entire suction line and the liquid line between the expansion valve and the cooler, are insulated with flexible, UV stable color coordinated closed-cell, foam insulation.
All controls and motor starting equipment necessary for unit operation are factory wired and function tested. 1 and 2 circuit units have one control panel respectively, and 3 circuit unit has two control panels (main and auxiliary). The panel enclosures are designed to IP55 and manufactured from powder coated galvanized steel. The surface is painted YORK Champagne.
There are two high pressure sensors, which are equipped to test discharge pressure and oil pressure, and a low pressure sensor, to test the evaporator pressure. High pressure switch and low pressure switch are also installed in the system pipe to protect the compressor.
Oil Separator Besides the high efficiency internal oil separation in each compressor, there is an external centrifugal oil separator used to avoid lubrication oil mixing with the refrigerant in the system ensuring maximum heat exchange and compressor lubrication. The external oil separators, with no moving parts and designed for minimum oil carry-over, are mounted in the discharge line of the compressor. DWP of the oil separator can reach 2.26MPa.
The control panel is divided into a power and a control compartment. Power and control sections have separate hinge, latch and gasket sealed doors for ease of maintenance and safety of the operators. Each power compartment comprises of compressor starting contactors, control circuit serving compressor capacity control, compressor contactor coils. The compressor motor protection can relay the compressor current to the microprocessor, and it can also protect from phase reversal and lack of phase for compressor power supply. The control section contains microcomputer keypad, HMI and I/O board.
Microprocessor All the control logic and devices which are factory wired will be fully tested in the factory. A LCD display screen and user-friendly keypad is mounted in front of the HMI.
The oil flows from the oil separator into the compressor through an oil filter and a solenoid valve at high pressure. This high pressure “oil injection” forces the oil into the compressor, where it is fed to the bearings and rotors for lubrication. After lubricating the bearings, differential pressure causes the oil to be automatically injected through orifices on a closed thread near the suction end of the rotors. It lubricates the rotors as well as provides an oil seal against leakage around the rotors to ensure refrigerant compression efficiency.
Oil Eductor Oil eductor circuit is provided to properly manage the amount of oil in the evaporator and transfer oil from the evaporator to compressor with the “jet pump” principle. Returning oil to the compressor prolongs its life and also improves the performance of the evaporator.
Oil Cooling Oil cooling is provided by routing oil from the compressor through several of the bottom rows of the condenser coils, where it is cooled, then sent back to the compressor.
4
The microprocessor-based control center includes the following functions: LCD Display The display consists of a liquid crystal 240*128 dot display, with light emitting diode backlighting for outdoor viewing of operating parameters and program points.
Operation Status Display Operating data - Includes outlet temperature of chilled water/liquid, ambient temperature, evaporator pressure, discharge pressure, discharge temperature, oil pressure, oil temperature and compressor current etc of system. Operating fault - When a fault occurs, the unit can self diagnose, display the cause, and send an alarm. The failure alarm history is logged for field troubleshooting. DI and DO status - Displays the DI (Data Input) and DO (Data Output) status. System Protection
● No water flow ● Anti-frozen protection ● High/low oil temperature protection ● Oil level switch protection ● High discharge temperature protection ● Low suction pressure protection ● High discharge pressure protection
● Power supply phase reversal, phase imbalance and phase loss protection
● High compressor motor’s current protection ● Low water/liquid temperature protection ● Compressor motor overload protection ● Compressor anti-recycle protection ● Fan motor overload protection The unit also has other control functions such as:
● External interlock with other auxiliary equipment ● Silent mode ● Program start/stop time ● Stepless capacity control ● Pre heating for unit ● Remote ON/OFF ● Smart fan control ● Integration with open MODBUS protocol provides easy connection to BAS system
● RS-485 standard serial communication ports
Options Flow Switch
Compressor Suction Service Valve Option
The design working pressure of target type flow switch is 10.3bar. It is suitable for chilled liquid applications.
This option includes a suction service valve in the suction line used to close off the connection between the cooler/ evaporator and compressor when required.
Power Supply Option ● 380V-3P-50Hz ● 400V-3P-50Hz ● 415V-3P-50Hz Coil Fin Option ● Epoxy Coated Aluminum-Ripple Fin Vibration Isolation Option ● Neoprene isolation to provide great performance in most applications (field mounted) for the Standard Chiller. ● Adjustable spring Isolators. Spring and cage type isolators for mounting under the unit base rails. Deflection may vary slightly by application (field mounted).
Disconnect Switch with Single Power Connection Option Disconnect switch with single power connection option is available for 2 Circuit Units.
Compressor Acoustic Enclosure The silencers cotton can be installed outside the compressor and it is made of flexibility acoustic material and can reduce the operation noise effectively.
High Static Fans The unit is capable of choosing a high static pressure fan to be used for some applications that need the duct connection.
Single Water connection For 3 Circuit Units The option provides one water connection for 3 Circuit Units and saves the installation space.
5
Cooler water pressure drop Pressure Drop Calculation:
B D EC F
A
120
Pressure Drop [kPa] = a x (Flow Rate [l/s]b), Where parameters a, b can be showed from following list,
G
Chiller Model
100
Pressure drop / kPa
H 80
60
40
20
0
10
20
30
40
50
Line
a
b
YGAS090
A
0.5183
1.763
YGAS120
B
0.1530
1.7714
YGAS150
C
0.0993
1.7812
YGAS180
D
0.1501
1.7733
YGAS210
E
0.1189
1.778
YGAS240
F
0.0937
1.7896
YGAS270
G
0.0729
1.799
YGAS300
H
0.0563
1.8057
YGAS450
H
0.0563
1.8057
C
0.0995
1.7812
60
Note: Cooler Water Pressure drop of 3 Circuit Units, YGAS450, is formed respectively by two branches, Coolers of YGAS300/YGAS150. And it’s necessary to balance the pressure of their two branches.
Water flow / L/s
Operating limitations YGAS Series Chillers
Min.
Max.
Leaving Chilled Liquid Temperature
°C
4
10
Chilled Liquid
Chilled Liquid Temperature Difference
°C
3.5
8
Maximum Water Side Pressure
bar
Ambient Air
Air Entering Temperature
°C
5
46
380V,3P,50Hz
V
342
418
400V,3P,50Hz
V
360
440
415V,3P,50Hz
V
374
457
YGAS150
YGAS180
YGAS210
YGAS240
YGAS270
YGAS300
YGAS450
10
YGAS120
YGAS090
Power Supply Voltage
Minimum Cooler1 Flow Rate l/s
7.8
10.0
12.5
14.5
17.1
19.4
21.6
25.2
25.2
Maximum Cooler1 Flow Rate l/s
23.3
30.1
37.4
43.4
51.2
58.3
64.9
75.7
75.7
Minimum Cooler2 Flow Rate l/s
-
-
-
-
-
-
-
-
12.5
Maximum Cooler2 Flow Rate l/s
-
-
-
-
-
-
-
-
37.4
Chiller Model
6
Unit
Physical data 1 circuit units Chiller Model for Standard Mode YGAS090 Unit Capacity Ton 90.0 Qty PCS 1 Compressor Input Power kW 91.1 Capacity Control % 25~100 Fan Qty PCS 6 Fan Motor Power kW 2.45×6 Condenser Type — Air Flow Rate m3/h 19000×6 Type — Qty PCS 1 Evaporator Water flow rate l/s 15.1 Water Pressure Drop kPa 62.4 Water Pipe Connection - DN100 Refrigerant Charge System 1 - 125 Refrigerant Charge System 2 kg - Refrigerant Charge System 3 kg - L mm 3676 Dimension W mm 2240 H mm 2456 Shipping Weight kg 4000 Weight Operating Weight kg 4150
1 Circuit Units YGAS120 118.8 1 111.8 25~100 8 2.45×8 Reversed “M” type 19000×8 Flooded Cooler 1 20.0 30.8 DN125 140 - - 4676 2240 2456 4700 4850
YGAS150 150.0 1 151.4 25~100 8 2.45×8 19000×8 1 25.2 31.2 DN125 150 5076 2240 2456 5200 5400
2 circuit units 2 Circuit Units Chiller Model for Standard Mode YGAS180 YGAS210 YGAS240 YGAS270 Unit Capacity Ton 172.0 203.0 231.0 257.0 Qty PCS 2 2 2 2 Compressor Input Power kW 184.0 196.6 218.1 252.7 Capacity Control % 12.5~100 12.5~100 12.5~100 12.5~100 Fan Qty PCS 10 14 16 16 Fan Motor Power kW 2.45×10 2.45×14 2.45×16 2.45×16 Condenser Type — Reversed “M” type 19000×10 19000×14 19000×16 19000×16 Air Flow Rate m3/h Type — Flooded Cooler Qty PCS 1 1 1 1 Evaporator Water flow rate l/s 28.9 34.2 38.9 43.2 Water Pressure Drop kPa 58.6 63.3 65.5 63.9 Water Pipe Connection - DN150 DN150 DN150 DN150 Refrigerant Charge System 1 kg 100 110 130 140 Refrigerant Charge System 2 kg 100 130 130 130 Refrigerant Charge System 3 kg - - - - L mm 5938 8176 9200 9600 Dimension W mm 2240 2240 2240 2240 H mm 2456 2456 2456 2456 Shipping Weight kg 7000 8250 9050 9500 Weight Operating Weight kg 7150 8400 9300 9750
YGAS300 300.0 2 302.8 12.5~100 16 2.45×16 19000×16 1 50.5 67.0 DN150 160 160 10000 2240 2456 9950 10250
7
3 circuit units Chiller Model for Standard Mode Unit Capacity Ton Qty PCS Compressor Input Power kW Capacity Control % Fan Qty PCS Fan Motor Power kW Condenser Type — Air Flow Rate m3/h Type — Qty PCS Evaporator Water flow rate l/s Water Pressure Drop kPa Water Pipe Connection — Refrigerant Charge System 1 kg Refrigerant Charge System 2 kg Refrigerant Charge System 3 kg L mm Dimension W mm H mm Shipping Weight kg Weight Operating Weight kg
3 Circuit Units YGAS450 450.0 3 454.2 8.3~100 24 2.45×24 Reversed “M” type 19000×24 Flooded Cooler 2 75.7 67.0 DN150/DN125 160 160 160 15276 2240 2456 15150 15650
Note: Cooling capacities in kW at 7°C leaving liquid temperature and 35°C ambient temperature.
Electrical data Multi Point Input (to each system) System Nominal / Amps
System Maximum / Amps System Max Start / Amps
System(s)
380 V
400 V
415 V
380 V
400 V
415 V
380 V
400 V
415 V
YGAS090
1
182
173
168
239
232
224
438
456
475
YGAS120
1
233
222
215
305
294
284
553
574
596
YGAS150
1
304
289
280
370
355
341
710
718
727
YGAS180
1&2
185
176
171
234
227
219
438
456
475
1
182
173
168
239
232
224
438
456
475
2
233
222
215
305
294
284
553
574
596
1 & 2
233
222
215
305
294
284
553
574
596
1
304
289
280
370
355
341
710
718
727
2
233
222
215
305
294
284
553
574
596
YGAS300
1 & 2
304
289
280
370
355
341
710
718
727
YGAS450
1 & 2 & 3
304
289
280
370
355
341
710
718
727
YGAS Model
YGAS210
YGAS240 YGAS270
8
Power supply connection 1 Circuit Units: YGAS090, YGAS120, YGAS150, Control Section
Control Section
Power Section
Power Section
YORK-003
KM3
EOEVD
T2 KM1
KM2
1QF 1MP
PE
CT
PE
N
Protective Earth
Circuit Breaker Protective Earth
Field Connection YGAS090SAE \ YGAS120SAE \ YGAS150SAE Control Section 13 13 13 13 13 13 13 1
2 3
8 14 11
KA7
KA8
Power Centre
N1 N1 N1 N1 N1 N1 N1 N1 32 33 34 35 36 85 86 87 88 89
Breaker
1QF
PE PE WIRE # 16AWG COPPER Chiller water flow switch
L1
L2
L3
1. Terminal 86 and 87 are used for PUMP(dry contact output, contact impedance is less than 0.5 Ohm) ; WIRE # 16AWG COPPER
2. Terminal 88 and 89 are used for ALARM(dry contact output,contact impedance is less than 0.5 Ohm) ;
Customer supply
WIRE # 16AWG COPPER Remote stop/start
Field wiring must also comply with local codes.
POWER (380/400/415V-3N-50HZ)
Extra inter lock If no EXT, please short-cut 14 an 13
9
2 Circuit Units: YGAS180, YGAS210, YGAS240, YGAS270, YGAS300
Power Section 1
Control Section
Power Section 2
YORK-003 EOEVD
Power Section 1
Control Section
Power Section 2
2KM3
1KM3 YORK-003 EOEVD
T2 1KM2
1KM1
2KM1 1QF
PE
CT1
PE
1MP
PE
2MP
N
Protective Earth
2KM2
2QF
CT2
Circuit Breaker Protective Earth
Circuit Breaker Protective Earth
Protective Earth
Field Connection YGAS180SAE \ YGAS210SAE \ YGAS240SAE \ YGAS270SAE \ YGAS300SAE \ YGAS450SAE Main Unit SYS1 Power Centre
Control Transformer is used in chiller.
Control Center 13 13 13 13 13 13 13 1
2 3
8 14 11
KA7
KA8
SYS2 Power Centre
N1 N1 N1 N1 N1 N1 N1 N1 32 33 34 35 36 85 86 87 88 89
Breaker
Breaker
1QF
2QF
PE
PE
PE
L1
L2
L3
1. Terminal 86 and 87 are used for PUMP(dry contact output, contact impedance is less than 0.5 Ohm) ;
WIRE # 16AWG COPPER
Chiller water flow switch
L1
L2
L3
Field wiring must also comply with local codes. Customer supply
WIRE # 16AWG COPPER
Customer supply
POWER (380V-3N-50HZ)
Remote stop/start Extra inter lock If no EXT, please short-cut 14 an 13
10
PE
2. Terminal 88 and 89 are used for ALARM(dry contact output,contact impedance is less than 0.5 Ohm) ;
WIRE # 16AWG COPPER
PE
N
POWER (380/400/415V-3N-50HZ)
3 Circuit Units: YGAS450 3 Circuit Units has two panels, a main control panel and an auxiliary control panel, and needs to connect a communication wire between them. Main control panel:
Power Section 1
Control Section 1
Power Section 2
YORK-003 EOEVD
Power Section 1
Control Section 1
Power Section 2
2KM3
1KM3 YORK-003 EOEVD
T2 1KM2
1KM1
2KM1 1QF
PE
CT1
PE
1MP
PE
2MP
N
Protective Earth
2KM2
2QF
CT2
PE
N
Circuit Breaker Protective Earth
Circuit Breaker Protective Earth
Protective Earth
Field Connection YGAS180SAE \ YGAS210SAE \ YGAS240SAE \ YGAS270SAE \ YGAS300SAE \ YGAS450SAE Main Unit SYS1 Power Centre
Control Transformer is used in chiller.
Control Center 13 13 13 13 13 13 13 1
2 3
8 14 11
KA7
KA8
SYS2 Power Centre
N1 N1 N1 N1 N1 N1 N1 N1 32 33 34 35 36 85 86 87 88 89
Breaker
Breaker
1QF
2QF
PE
PE
PE
L1
L2
L3
1. Terminal 86 and 87 are used for PUMP(dry contact output, contact impedance is less than 0.5 Ohm) ;
WIRE # 16AWG COPPER
Chiller water flow switch
PE
L1
L2
L3
2. Terminal 88 and 89 are used for ALARM(dry contact output,contact impedance is less than 0.5 Ohm) ;
WIRE # 16AWG COPPER
Field wiring must also comply with local codes. Customer supply
WIRE # 16AWG COPPER
Customer supply
POWER (380V-3N-50HZ)
Remote stop/start
POWER (380/400/415V-3N-50HZ)
Extra inter lock If no EXT, please short-cut 14 an 13
11
Auxiliary control panel:
Control Section 2
Control Section 2
Power Section 3
Power Section 3
YORK-003
KM3
EOEVD
T2 KM1
KM2
1QF 1MP CT
PE
PE
N
Protective Earth
Circuit Breaker Protective Earth
Field Connection Control Transformer is used in chiller.
Control Section 2 XT1 13 13 13 13 13 13 13 1
2
3
8
Power Section 3 Circuit Breaker
1QF
N N
PE PE
L1
L2
L3
WIRE # 16AWG COPPER
Copper conductors only. Do not use Aluminum conductors.
2#FLS Chiller water flow switch Customer supply
POWER (380/400/415V-3N-50HZ) Field wiring must also comply with local codes.
12
Dimensions 1 Circuit Units: YGAS090, YGAS120, YGAS150
1300
Control Panel
2456
Control Panel
815
Water Outlet
Q R
Water Inlet 48
A
D B
2240
P
C E F
G
Dimensions / mm A B C D E F G H P Q R 1060 1134 2770 150 3495 3676 760 1000 618 315 615 1060 1228 3410 150 4493 4676 760 1000 700 304 620 1260 1628 3810 150 4895 5076 810 1100 700 304 620
6-Ø14 Isolator Mounting Holes
8-Ø14 Isolator Mounting Holes
1
2152
YGAS090 Vibration Isolators Distribution
6 735
5 963
4
4
3
8 663
1240
2
1
YGAS120 Vibration Isolators Distribution
2152
2
CONTROL PANNEL
3
Qty m 2 3 3
7 1040
6 710
5
CONTROL PANNEL
Chiller Model YGAS090 YGAS120 YGAS150
HXm
1306.5
4
3
2
1
2152
YGAS150 Vibration Isolators Distribution
8 760
7 980
6 1518.5
5
CONTROL PANNEL
8-Ø14 Isolator Mounting Holes
1065
13
2 Circuit Units: YGAS180, YGAS210, YGAS240, YGAS270, YGAS300
2456
1300
Control Panel
815
Water Outlet
Q
R
Water Inlet 48
P
E
A
2240
B C D F G K
JXm
H
LXn
Dimensions / mm A B C D E F G H J K L P Q R 914 1015 2960 4764 184 5747 5938 760 1020 - - 1120 315 669 1370 2372 4230 7020 184 8015 8176 760 1000 1380 1000 1100 321 675 1405 2232 4625 7511 184 9015 9200 760 1000 1380 1000 1120 337 657 1450 2424 4714 7911 184 9415 9600 810 1000 1430 1100 1120 321 675 1450 2591 5030 8355 184 9815 10000 810 1100 1480 1100 1120 352 748
10-Ø14 Isolator Mounting Holes
3
2
1
9
7
8
880.5
1150
1544
6
14
1080
713
2152
15 1050
4
3
2
1
14 1250
13 955
12 876.5
11 955
10 1230
9 1455
6
5
3
2
1
2152
YGAS300 Vibration Isolators Distribution
16 767
14
4
15 1080
14 900
13 1550
12 1014.5
11 1600
10 800
9 1350
CONTROL PANNEL
7
8
3
2
1
12
11
1500
10
900
1398.5
9 1200
8 720
7
6
5
4
3
2
1
YGAS270 Vibration Isolators Distribution
16 767
16-Ø14 Isolator Mounting Holes
8
13 890
2152
5
CONTROL PANNEL
6
YGAS240 Vibration Isolators Distribution
16
4
16-Ø14 Isolator Mounting Holes
7
710
5
YGAS210 Vibration Isolators Distribution
16-Ø14 Isolator Mounting Holes
8
6
15 1080
14 900
13 1523.6
12 970
11 958
10 1230
9 1455
CONTROL PANNEL
2152
10
7 2152
4
YGAS180 Vibration Isolators Distribution
535
n 2 3 3 3
14-Ø14 Isolator Mounting Holes
CONTROL PANNEL
5
Qty m 4 3 3 3 3
CONTROL PANNEL
Chiller Model YGAS180 YGAS210 YGAS240 YGAS270 YGAS300
3 Circuit Units: YGAS450 Auxiliary Control Panel
A-A
A
B
A
B
Main Control Panel
C
B-B
The structure of the unit near the main control panel of YGAS450 Chillers refers to YGAS300 Chiller, and the structure of the unit near the auxiliary control panel of YGAS450 Chiller refers to YGAS150. The total length of YGAS450 is 15,276.
Note: For 3 Circuit Units, YGAS450, there are 16 vibration isolators installed at the base frame of main control panel side (referred to that of YGAS300) and 8 vibration isolators installed in bottom rail of unit frame of auxiliary control panel side (referred to that of YGAS150).
15
Johnson Controls is the global leader that creates smart environments – bringing ingenuity to the places where people live, work and travel. Johnson Controls' building efficiency business enables safe, comfortable, energy efficient and sustainable facilities. We are a single source of integrated heating/cooling, controls, lighting, fire, security and wireless infrastructure products for buildings and industrial plants. Our comprehensive life-cycle approach to in-building technology and operations includes planning and design, installation and integration optimization and maintenance as well as integrated real estate and facility management services. Sustainability matters at every level. Our triple bottom line – Economic Prosperity, Environmental Stewardship and Social Responsibility – and every facet of our operations and community involvement are geared to the efficient use of resources to benefit the planet and people all over the world. Johnson Controls inaugurated the Annual Energy Efficiency Forum in conjunction with the U.S. Energy Association. We are also a lead technology and energy-efficiency partner for the Clinton Climate Initiative and its ambitious C40 Large Buildings Retrofit Program, Johnson Controls helped the U.S. Green Building Council develop its Leadership in Energy Environmental Design (LEED) rating system and certification for green buildings. Our network of more than 150 sales and support centres with more than 10,000 dedicated professionals located in 15 countries and regions has made us the partner of choice for some of the most recognisable structures in Asia and the Pacific, including the 2008 Olympics. Johnson Controls is responsible for the region's LEED-certified buildings, including India's ITC Green Centre, China's Beijing Prosper Centre as well as the world's tallest buildings - Kuala Lumpur's Petronas Towers, Taipei 101 and the Shanghai World Finance Centre.
Asia headquarters 20/F, Tower 1, 2 & 3, Enterprise Square 1, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong Tel : +852 2590 0012 Fax : +852 2516 5648 Australia Tel : +61 (2) 9805 8300 Fax : +61 (2) 9247 7750
China (Shanghai) Tel : +86 (21) 6276 6509 Fax : +86 (21) 6277 3543
Hong Kong Tel : +852 2590 0012 Fax : +852 2516 5648
India Tel : +91 (22) 3082 0391 Fax : +91 (22) 3088 1592
Indonesia Tel : +61 (21) 626 3535 Fax : +61 (21) 659 8875
Japan Tel : +61 (3) 5738 6100 Fax : +61 (3) 5738 6298
Korea Tel : +82 (2) 554 5935 Fax : +82 (2) 554 5739
Macau Tel : +853 2875 1820 Fax : +853 2875 1821
Malaysia Tel : +60 (3) 7628 4300 Fax : +60 (3) 7848 1180
New Zealand Tel : +64 (9) 444 6434 Fax : +64 (9) 444 2092
Philippines Tel : +63 (2) 706 1420-22 Fax : +63 (2) 706 1486
Singapore Tel : +65 6748 0202 Fax : +65 6284 3473
Taiwan Tel : +886 (2) 2657 5568 Fax : +886 (2) 2657 6388
Thailand Tel : +66 (2) 717 0751 Fax : +66 (2) 717 0750
Vietnam Tel : +84 (8) 526 1205 Fax : +84 (8) 526 1206
Asia Factories: Guangzhou & Wuxi, China • Pune, India Asia Engineering Centre: Wuxi, China Asia Centre of Excellence in Engineering (CoEE): Beijing, China • Mumbai & Pune, India Asia Centre of Engineering & Technology (CET): Hong Kong Asia Parts & Product Hub: Shanghai, China China Refrigeration, Project Engineering Centre: Shanghai, China
© 2009 Johnson Controls, Inc.
www.johnsoncontrols.com Printed on recycled paper
PUBL-5353(0209)