4 0 91 KB
Sr. No. 1
Formula Used:
2 3 4
Interpolation: Y2 = Y3 -[{(Y3-Y1)*(X3-X2)}/(X3-X1)]
5
T(°F) = 1.8*T(°C)+32
Units Converter Temperature Tc = Tf =
573 1063.4
Tf = Tc =
1100 593.333333333333 Length 24 0.94488188976378 0.237 6.0198
mm Inch Inch mm
Pressure Bar Mpa 1Ksi
34 3.4 6.89 Mpa
N/mm2 Legend
Input Field Output field
Client Project Item Number Item
Company Logo
Date: Issued: Revision: Page:
Pipe wall thickness calculation according to ASME B31.1 only for straight Pipes Design Pressure (P) = Design Temperature (T) = Material designation =
15.70 Mpa 584.0 °C A335 P91
Max Possible Reduction 1083.2 °F Seamless Pipe
Outside Diameter (Do) =
323.9 mm
12.751968503937 Inch
Inside Diameter (Di) =
mm 33.3 mm 0.0
Wall Thickness Ordered = Weld Joint Factor (z) = Corrosion Allowance (c0) =
Not Evaluated Pipe class, SCH
160
0.0 mm
Manufacturing Allowance (c1) =
4.01 mm
14.3% of t(min)
Allowable Stress to ASME B 31.1 Appendix A Material values (for Interpolation) T T °F
SE
Unit Conversion
°C
N/mm2
KSI
N/mm2
1050 565.5556 1100 593.3333
96.5 71.0
14.0 10.3
96.5 71.0
Material values at 584 °C SE =
### MPa
SE =
### MPa
Value of y Coefficient* °C Sigma 592 0.4 584.0 0.7 592.01 0.4
T Design 584 Minimum Wall Thickness to ASME B 31.1,2007 paragraph 104.1
tm = =
P * Do 2(SE+Py)
+A
28.07 mm 28.07 mm
tr = tm + c0 + c1 = 32.09 mm tr
D0/tm