Outdoor units for pair, twin, triple, double twin application The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners.
•
During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy.
•
Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
•
The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level
•
Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency
•
An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures.
•
A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions
1
1
Features
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS-DV1
2
Specifications
3
2-1 NOMINAL CAPACITY AND NOMINAL INPUT
RZQS71D7V1B
RZQS100D7V1B
RZQS125D7V1B
RZQS140D7V1B
FCQ71C7VEB
FCQ100C7VEB
FCQ125C7VEB
FCQ140C7VEB
For combination indoor units + outdoor units
Indoor Units
Cooling capacity
Standard
kW
7.1
10.0
12.5
14.0
Heating capacity
Standard
kW
8.0
11.2
14.0
16.0
Power Input For combination indoor units + outdoor units
1 Cooling
Standard
kW
2.28
3.22
4.02
5.36
Heating
Standard
kW
2.35
3.28
4.06
4.98
EER
Nominal
3.11
3.11
3.11
2.61
COP
Nominal
3.41
3.41
3.45
3.21
Energy Label
Cooling
B
B
B
D
Heating
B
B
B
C
1,141
1,608
2,010
2,682
Annual energy consumption kWh
FCQH71D7VEB
FCQH100D7VEB
FCQH125D7VEB
FCQH140D7VEB
Cooling capacity
Indoor Units Standard
kW
7.1
10.0
12.5
14.0
Heating capacity
Standard
kW
8.0
11.2
14.0
16.0
Power Input For combination indoor units + outdoor units
Cooling
Standard
kW
2.15
2.90
3.88
4.65
Heating
Standard
kW
2.16
2.95
3.79
4.69
EER
Nominal
3.30
3.45
3.22
3.01
COP
Nominal
3.70
3.80
3.69
3.41
Energy Label
Cooling
A
A
A
B
Heating
A
A
A
B
1,076
1,449
1,941
2,326
Annual energy consumption kWh
FBQ71C7VEB
FBQ100C7VEB
FBQ125C7VEB
FBQ140C7VEB
Cooling capacity
Indoor Units Standard
kW
7.1
10.0
12.5
13.4
Heating capacity
Standard
kW
8.0
11.2
14.0
15.0
Power Input For combination indoor units + outdoor units
Cooling
Standard
kW
2.18
3.03
3.98
4.77
Heating
Standard
kW
2.25
3.07
4.11
4.67
EER
Nominal
3.26
3.30
3.14
2.81
COP
Nominal
3.55
3.65
3.41
3.21
Energy Label
Cooling
A
A
B
C
Heating
B
A
B
C
1,089
1,515
1,990
2,384
Annual energy consumption kWh
FHQ71BVV1B
FHQ100BVV1B
FHQ125BVV1B
Cooling capacity
Indoor Units Standard
kW
7.1
10.0
12.5
Heating capacity
Standard
kW
8.0
11.2
14.0
Power Input For combination indoor units + outdoor units
Cooling
Standard
kW
2.51
3.56
4.55
Heating
Standard
kW
2.75
3.85
4.86
EER
Nominal
2.83
2.81
2.75
COP
Nominal
2.91
2.91
2.88
Energy Label
Cooling
C
C
D
Heating
D
D
D
1,254
1,779
2,273
Annual energy consumption kWh
FAQ71BVV1B
FAQ100BVV1B
FDQ125B8V3B9
Cooling capacity
Indoor Units Standard
kW
7.1
10.0
12.5
Heating capacity
Standard
kW
8.0
11.2
14
Cooling
Standard
kW
2.44
3.56
4.30
Heating
Standard
kW
2.49
3.49
3.97
Power Input
• Split Sky Air • Outdoor Units
2
2
• Outdoor Units • R-410A • RZQS-DV1
2
Specifications
2-1 NOMINAL CAPACITY AND NOMINAL INPUT
1
For combination indoor units + outdoor units
2
RZQS71D7V1B
RZQS100D7V1B
RZQS125D7V1B
Nominal
2.91
2.81
2.91
COP
Nominal
3.21
3.21
3.53
Energy Label
Cooling
C
C
C
Heating
C
C
B
1,220
1,779
2,148
EER
Annual energy consumption kWh
FVQ71BV1B
FVQ100BV1B
FVQ125BV1B
Cooling capacity
Indoor Units Standard
kW
7.1
10.0
12.5
Heating capacity
Standard
kW
8.0
11.2
14.0
Power Input For combination indoor units + outdoor units
Cooling
Standard
kW
2.53
3.56
4.45
Heating
Standard
kW
2.49
3.49
4.36
EER
Nominal
2.81
2.81
2.81
COP
Nominal
3.21
3.21
3.21
Energy Label
Cooling
C
C
C
Heating
C
C
C
1,265
1,779
2,225
RZQS71D7V1B
RZQS100D7V1B
Annual energy consumption kWh
2-2
TECHNICAL SPECIFICATIONS
Casing
Colour
Dimensions
Unit
Weight
Paintable galvanized steel plate Height
mm
770
1,170
1,170
1,170
Width
mm
900
900
900
900
Depth
mm
320
320
320
320
Height
mm
900
1,349
1,349
1,349
Width
mm
980
980
980
980
Depth
mm
420
420
420
420
kg
68
103
103
103
Unit Packed Unit
Heat Exchanger
Dimensions
Length
kg
72
119
119
119
mm
857
857
857
857
2
2
2
2
mm
1.4
1.4
1.4
1.4
Nr of Rows Fin Pitch
Nr of Passes Face Area
m²
Nr of Stages
8
10
10
10
0.641
0.98
0.98
0.98
34
52
52
52
Tube type Fin
Hi-XSS(8) Type
WF fin
Treatment Fan
Anti-corrosion treatment (PE)
Type
Propeller
Discharge direction
Horizontal
Quantity
1
2
2
2
Air Flow Rate (nominal at 230V)
Cooling
m³/min
52
96
100
97
Heating
m³/min
48
90
90
90
Motor
Quantity Model
Motor
Fan
Speed (nominal)
Motor
Steps
1
2
2
2
KFD-325-70-8A
Brushless DC Motor
Brushless DC Motor
Brushless DC Motor
8
8
8
8
rpm Cooling (Standard )
800
800
850
830
rpm Heating (Standard )
745
760
760
760
Output
70
70
70
70
W
Drive
3
RZQS140D7V1B
Ivory White
Material
Packing
RZQS125D7V1B
RZQS140D7V1B
Direct drive
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS-DV1
2 2-2
Specifications TECHNICAL SPECIFICATIONS
Compressor
Quantity Motor
RZQS71D7V1B
RZQS100D7V1B
RZQS125D7V1B
RZQS140D7V1B
1
1
1
1
Model
2YC63DXD
JT100G-VD
JT100G-VD
JT100G-VD
Type
Hermetically sealed swing compressor
Hermetically sealed scroll compressor
Hermetically sealed scroll compressor
Hermetically sealed scroll compressor
1,700
2,200
2,200
2,200
33
33
33
-5.0
Motor Output
W
Crankcas W e Heater Starting Method Operation Range
Sound Level (nominal)
Cooling
°CDB
-5.0
-5.0
-5.0
Max
°CDB
46
46
46
46
Heating
Min
°CWB
-15
-15
-15
-15
Max
°CWB
15.5
15.5
15.5
15.5
Cooling
Sound Power
dBA
65
67
67
68
Sound dBA Pressure (Standard )
49
51
51
52
Sound dBA Pressure (Standard )
51
55
53
54
dBA
47
49
49
50
2.75
3.7
3.7
3.7
Sound Level (Night quiet)
Sound Pressure
Refrigerant
Type kg
Control
Expansion valve (electronic type)
Nr of Circuits Type Charged Volume Piping connections
Liquid (OD)
l Quantity
1
1
1
1
FVC50K
Daphne FVC68D
Daphne FVC68D
Daphne FVC68D
0.75
1.0
1.0
1.0
1
1
1
1
9.52
9.52
1
1
15.9
15.9
3
3
26
26
Type
Flare connection
Diameter (OD) Gas
mm
Quantity
9.52
9.52
1
1
Type
Flare connection
Diameter (OD) Drain
mm
Quantity
15.9
15.9
3
3
Type
Piping Length
Hole
Diameter (OD)
mm
Minimum
26
26
m
5
5
5
5
Maximum m
30
50
50
50
Equivalen m t
40
70
70
70
Chargele ss
30
30
30
30
Additional Refrigerant Charge Installation height difference
2
R-410A
Charge
Refrigerant Oil
1
Inverter driven
Min
Heating
3
m kg/m
Maximum m
Max. internunit level difference
m
see installation manual 4PW49302-1 15
30
30
30
0.5
0.5
0.5
0.5
Heat Insulation
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Temperature
Capacity Control Method
Inverter controlled
• Split Sky Air • Outdoor Units
4
• Outdoor Units • R-410A • RZQS-DV1
2 2-2
Specifications TECHNICAL SPECIFICATIONS
RZQS71D7V1B
RZQS100D7V1B
Safety Devices
RZQS125D7V1B
RZQS140D7V1B
High pressure switch Fan motor thermal protector
1 2
Fuse Standard Accessories
Item
Tie-wraps
Quantity
2
2
Item
2
2
1
1
Installation manual
Quantity
1
Notes
1
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 5m, level difference : 0m. Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 5m, level difference : 0m
2-3
ELECTRICAL SPECIFICATIONS
Power Supply
RZQS71D7V1B
RZQS100D7V1B
Name Phase
Current Wiring connections
Hz
Voltage
V Minimum
50
50
50
50 220-240
V
198
198
198
198
Maximum V
264
264
264
264
32
32
Minimum Ssc (²) value
kVa
Recomended fuses
A
For Power Supply
RZQS140D7V1B
1~
Frequency Voltage range
RZQS125D7V1B
V1
Dummy 20
32
Remark
see installation manual 4PW49302-1
For connection Remark with indoor
see installation manual 4PW49302-1
Power Supply Intake
Outdoor unit only
Notes
See separate drawings for electrical data (1) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase. (2) Short-circuit power Power supply to the FDQ indoor unit is separate
5
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS-DV1
3
Electrical data
3
RZQS71-140DV1 Unit combination Indoor unit Outdoor unit
Hz-volts
Power supply Comp. Voltage range MCA TOCA MFA MSC RLA
OFM kW
IFM FLA
kW
FLA
1 3
NOTES 1
2 3
4 5
6 7
RLA is based on the following conditions: Power supply: 50Hz - 230V Cooling Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Heating Indoor temperature 20.0°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
SYMBOLS MCA TOCA MFA MSC RLA OFM IFM FLA kW
: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (A) (See note 7) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)
3D063321
• Split Sky Air • Outdoor Units
6
• Outdoor Units • R-410A • RZQS-DV1
4
Options
RZQ(S)71-140DV1 Kit name
1 4
Name of option
RZQ71D7V1B
RZQ100D7V1B
RZQ125D7V1B
RZQ140D7V1B
RZQS71D7V1B
RZQS100D7V1B
RZQS125D7V1B
RZQS140D7V1B
-
RZQ100B8W1B
RZQ125B8W1B
RZQ140B8W1B
Central drain plug
EKDK04 Twin
Refrigerant branch piping
KHRQ22M20TA (KHRQ58T): see note
Triple
-
Double-twin
-
-
Demand adapter kit
KHRQ127H (KHRQ58H): see note KHRQ22M20TA (KHRQ58T): see note (3x) KRP58M51
NOTE 1
For RZQ100-140B8W1B in combination with FCQ35-71C, FCQH71C or FCQH71D use the refrigerant branch piping mentioned between brackets.
3TW26739-1F
7
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-1
Combination table
3
RZQ(S)71-140DV1 Multi Combination Possibilities:
P = Pair
71
100
125
140
2 = Twin
35+35
50+50
60+60
71+71
3 = Triple
35+35+35
4 = Double Twin
50+50+50 (*)
50+50+50 (*)
35+35+35+35 (*)
35+35+35+35
1 5
(*) Max capacity depend on outdoor unit
RZQ71D7V1B
P 2
P
2
4
3
4
3
2
4
3
4
3
2
2
4
3
4
3
P 2
P
2
4
3
4
3
P
FVQ125BV1B
FVQ71BV1B
FVQ125BV1B
FVQ71BV1B
FVQ100BV1B
FDQ125B8V3B
Floor standing
P P
2
FVQ100BV1B
FDQ125B8V3B
FAQ71BVV1B
FAQ100BVV1B
FUQ125BVV1B
FUQ71BVV1B
P P
2
FAQ100BVV1B
Wall mounted High ESP Duct FAQ71BVV1B
FUQ125BVV1B
FHQ125BVV1B
P 2
4way ceiling
P
3
FUQ100BVV1B
FHQ125BVV1B
FHQ71BVV1B
FHQ60BVV1B
FHQ100BVV1B
2
FHQ100BVV1B
FHQ35BVV1B
FBQ140C7VEB
2 P
2
2
P P
FUQ100BVV1B
3
Floor standing
P
P
FUQ71BVV1B
4
2
Wall mounted High ESP Duct
P
Ceiling suspended
P
3
FHQ50BVV1B
FHQ35BVV1B
FBQ140C7VEB
FBQ125C7VEB
FBQ71C7VEB
FBQ100C7VEB
FBQ60C7VEB
2
3
P
3
New Duct (medium ESP) FBQ35C7VEB
FFQ60B8V1B
FFQ50B8V1B
2
4
P P
FHQ71BVV1B
3
P
2
FHQ60BVV1B
4
2
4way ceiling
P
3
FHQ50BVV1B
3
FBQ125C7VEB
3
4
2 P
FBQ100C7VEB
4
2
2
FBQ71C7VEB
3
Ceiling suspended
P
3
FBQ60C7VEB
4
FFQ35B8V1B
FCQ140C7VEB P
FBQ50C7VEB
FFQ60B8V1B
FBQ35C7VEB
FFQ50B8V1B 2
2 P
2
2
3
2x2 cassette
P 2
New Duct (medium ESP)
FBQ50C7VEB
P
P
3
FFQ35B8V1B
FCQ140C7VEB
FCQ125C7VEB
FCQ71C7VEB
FCQ100C7VEB
2
2 P
RZQ125D7V1B
FCQ60C7VEB
FCQ50C7VEB
FCQH140D7VEB
FCQ35C7VEB
3
P
Thin cassette
P
RZQ100D7V1B RZQ140D7V1B
4
2
FCQ125C7VEB
Model name
3
HH Cassette FCQH71D7VEB
Sky-air
P
4
2 P
FCQ100C7VEB
2
2
FCQ71C7VEB
RZQ140B8W1B
P
2x2 cassette
P
3
FCQ60C7VEB
RZQ140D7V1B
2 P
FCQ50C7VEB
RZQ125B8W1B
P
FCQ35C7VEB
RZQ125D7V1B
Thin cassette
FCQH140D7VEB
RZQ100B8W1B
FCQH125D7VEB
RZQ71D7V1B RZQ100D7V1B
FCQH100D7VEB
Model name
FCQH125D7VEB
FCQH71D7VEB
HH Cassette FCQH100D7VEB
Sky-air
P P
P
2
NOTES
1 2
Individual indoor capacities are not given because the combinations are for simultaneous operation (= indoor units installed in the same room) When different indoor models are used in combination, designate the remote control that is equipped with the most function as the main unit.
3TW26739-2C
• Split Sky Air • Outdoor Units
8
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-2
Cooling capacity tables
RZQS71DV1
1 5
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity (kW) Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
(°C)
(°C)
TC (kW)
25 SHC (kW)
CPI (-)
TC (kW)
30 SHC (kW)
CPI (-)
TC (kW)
35 SHC (kW)
CPI (-)
TC (kW)
40 SHC (kW)
CPI (-)
3DTW3172-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FCQH71D 21 (0.17)
FCQ71C 15.5 (0.19)
FBQ71 18 (0.08)
FHQ71 17 (0.10)
Model AFR (BF)
FCQ35Cx2 10.5x2 (0.28x2)
FFQ35x2 10x2 (0.25x2)
FBQ35Cx2 15x2 (0.15x2)
FHQ35x2 13x2 (0.2x2)
FAQ71 19 (0.08)
FVQ71 18 (0.16)
(Twin)
8. Rated power input of each model is tabulated below. (Pair)
Model Cooling
FCQH71D 2.15
FCQ71C 2.28
FBQ71C 2.18
FHQ71 2.51
FCQ35Cx2 2.59
FFQ35x2 2.61
FBQ35x2 2.25
FHQ35x2 2.66
FAQ71 2.44
FVQ71 2.53
(Twin)
Model Cooling
9
• Split Sky Air • Outdoor Units
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-2
Cooling capacity tables
3
RZQS100DV1 Cooling
Coefficient of power input. (-)
1 5
Capacity range
Rated point
Cooling capacity (kW) Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
(°C)
(°C)
TC (kW)
25 SHC (kW)
CPI (-)
TC (kW)
30 SHC (kW)
CPI (-)
TC (kW)
35 SHC (kW)
CPI (-)
TC (kW)
40 SHC (kW)
CPI (-)
3TW31722-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FCQH100D 34 (0.17)
FCQ100C 23.5 (0.16)
FBQ100C 32 (0.13)
FHQ100 24 (0.14)
Model AFR (BF)
FCQ50Cx2 12.5x2 (0.21x2)
FFQ50x2 12x2 (0.16x2)
FBQ50Cx2 16x2 (0.16x2)
FHQ50x2 13x2 (0.1x2)
Model AFR (BF)
FCQ35Cx3 10.5x3 (0.28x3)
FFQ35x3 10x3 (0.25x3)
FBQ35Cx3 16x3 (0.15x3)
FHQ35x3 13x3 (0.2x3)
FAQ100 23 (0.10)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
FVQ100 28 (0.19)
(Twin)
(Triple)
8. Rated power input of each model is tabulated below. (Pair)
Model Cooling
FCQH100D 2.90
FCQ100C 3.22
FBQ100C 3.03
FHQ100 3.56
FCQ35Cx2 3.58
FFQ35x2 3.58
FBQ35x2 3.16
FHQ35x2 3.90
FCQ35Cx3 3.58
FFQ35x3 3.58
FBQ35x3 3.16
FHQ35x3 3.90
FAQ100 3.56
FVQ100 3.56
(Twin)
Model Cooling (Triple)
Model Cooling
• Split Sky Air • Outdoor Units
10
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-2
Cooling capacity tables
RZQS125DV1
1 5
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity (kW) Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
(°C)
(°C)
TC (kW)
25 SHC (kW)
CPI (-)
TC (kW)
30 SHC (kW)
CPI (-)
TC (kW)
35 SHC (kW)
CPI (-)
TC (kW)
40 SHC (kW)
CPI (-)
3TW31732-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FCQH125D 34 (0.19)
FCQ125C 27.5 (0.19)
FBQ125C 39 (0.16)
FHQ125 30 (0.13)
Model AFR (BF)
FCQ60Cx2 13.5x2 (0.21x2)
FFQ60x2 15x2 (0.11x2)
FBQ60Cx2 18x2 (0.15x2)
FHQ60x2 17x2 (0.2x2)
Model AFR (BF)
FCQ50Cx3 12.5x3 (0.21x3)
FFQ50x3 12x3 (0.16x3)
FBQ50Cx3 16x3 (0.16x3)
FHQ50x3 13x3 (0.1x3)
FDQ125 45 (0.25)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
FVQ125 32 (0.16)
(Twin)
(Triple)
(Double Twin)
Model AFR (BF)
FCQ35Cx4 10.5x4 (0.28x4)
FFQ35x4 10x4 (0.25x4)
FBQ35Cx4 16x4 (0.15x4)
FHQ35x4 13x4 (0.2x4)
8. Rated power input of each model is tabulated below. (Pair)
Model Cooling
FCQH125D 3.88
FCQ125C 4.02
FBQ125C 3.98
FHQ125 4.55
FCQ60Cx2 4.17
FFQ60x2 4.22
FBQ60x2 4.18
FHQ60x2 4.57
FCQ50Cx3 4.17
FFQ50x3 4.22
FBQ50x3 4.18
FHQ50x3 4.57
FAQ125 4.45
FUQ125 3.30
(Twin)
Model Cooling (Triple)
Model Cooling
11
(Double Twin)
Model Cooling
• Split Sky Air • Outdoor Units
FCQ35Cx4 4.17
FFQ35x4 4.22
FBQ35x4 4.18
FHQ35x4 4.57
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-2
Cooling capacity tables
3
RZQS140DV1 Cooling
Coefficient of power input. (-)
1 5
Capacity range
Rated point
Cooling capacity (kW) Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
(°C)
(°C)
TC (kW)
25 SHC (kW)
CPI (-)
TC (kW)
30 SHC (kW)
CPI (-)
TC (kW)
35 SHC (kW)
CPI (-)
TC (kW)
40 SHC (kW)
CPI (-)
3TW31742-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FCQH140D 34 (0.20)
Model AFR (BF)
FCQH71Dx2 FCQ71Cx2 21x2 15.5x2 (0.17x2) (0.19x2)
FBQ71Cx2 18x2 (0.08x2)
FHQ71x2 17x2 (0.1x2)
Model AFR (BF)
FCQ50Cx3 12.5x3 (0.21x3)
FBQ50Cx3 16x3 (0.15x3)
FHQ50x3 13x3 (0.1x3)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
FCQ140C 27.5 (0.22)
(Twin)
(Triple)
FAQ71x2 19x2 (0.08x2) (Double Twin)
FFQ50x3 12x3 (0.16x3)
Model AFR (BF)
FCQ35Cx4 10.5x4 (0.28x4)
FFQ35x4 10x4 (0.25x4)
FBQ35Cx4 16x4 (0.15x4)
FHQ35x4 13x4 (0.2x4)
8. Rated power input of each model is tabulated below. (Pair)
Model Cooling
FCQH140D 4.65
FCQ140C 5.36
(Twin)
Model Cooling
FCQH71Dx2 FCQ71Cx2 4.99 5.12
FBQ71Cx2 4.95
FHQ71x2 5.10
FCQ50Cx3 5.12
FBQ50x3 4.95
FHQ50x3 5.10
(Triple)
Model Cooling
FAQ71x2 5.01 (Double Twin)
FFQ50x3 4.89
Model Cooling
• Split Sky Air • Outdoor Units
FCQ35Cx4 5.12
FFQ35x4 4.89
FBQ35x4 4.95
FHQ35x4 5.10
12
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-2
Cooling capacity tables
RZQS140DV1
1 5
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity (kW) Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
(°C)
(°C)
TC (kW)
25 SHC (kW)
CPI (-)
TC (kW)
30 SHC (kW)
CPI (-)
TC (kW)
35 SHC (kW)
CPI (-)
TC (kW)
40 SHC (kW)
CPI (-)
3TW31742-3
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FBQ140C 39 (0.14)
8. Rated power input of each model is tabulated below. (Pair)
Model Cooling
13
FBQ140C 4.77
• Split Sky Air • Outdoor Units
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-2
Cooling capacity tables
3
RZQS71-140DV1 Capacity in function of field piping length for non-inverter
1 5
Capacity (%)
Field piping length (m) Cooling Heating
• Split Sky Air • Outdoor Units
3TW31712-1
14
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-3
Heating capacity tables
RZQS71DV1
1 5
Coefficient of power input. (-)
Heating
Rated point
Capacity range
Heating capacity (kW) Heating capacity
Indoor EDB
-15 TC (kW)
(°C)
-10 CPI (-)
TC (kW)
CPI (-)
Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)
6 TC (kW)
10 CPI (-)
TC (-)
CPI (-)
3TW31712-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FCQH71C 21 (0.17)
FCQ71C 15.5 (0.19)
FBQ71 18 (0.08)
FHQ71 17 (0.10)
Model AFR (BF)
FCQ35Cx2 10.5x2 (0.28x2)
FFQ35x2 10x2 (0.25x2)
FBQ35Cx2 16x2 (0.15x2)
FHQ35x2 13x2 (0.2x2)
FAQ71 19 (0.08)
FVQ71 18 (0.16)
(Twin)
10. Rated power input of each model is tabulated below. (Pair)
Model Heating
FCQH71D 2.16
FCQ71C 2.35
FBQ71 2.25
FHQ71 2.75
FCQ35Cx2 2.75
FFQ35x2 2.70
FBQ35Cx2 2.20
FHQ35x2 2.85
FAQ71 2.49
FVQ71 2.49
(Twin)
Model Heating
15
• Split Sky Air • Outdoor Units
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-3
Heating capacity tables
3
RZQS100DV1 Heating
Coefficient of power input. (-)
1 5
Rated point
Capacity range
Heating capacity (kW) Heating capacity
Indoor EDB
-15 TC (kW)
(°C)
-10 CPI (-)
TC (kW)
CPI (-)
Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)
6 TC (kW)
10 CPI (-)
TC (-)
CPI (-)
3TW31722-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
(Pair)
Model AFR (BF)
FCQH100D 34 (0.17)
FCQ100C 23.5 (0.16)
FBQ100C 32 (0.13)
FHQ100 24 (0.14)
Model AFR (BF)
FCQ35Cx2 12.5x2 (0.21x2)
FFQ35x2 12x2 (0.16x2)
FBQ35Cx2 16x2 (0.16x2)
FHQ35x2 13x2 (0.1x2)
Model AFR (BF)
FCQ35Cx3 10.5x3 (0.28x3)
FFQ35x3 10x3 (0.25x3)
FBQ35Cx3 16x3 (0.15x3)
FHQ35x3 13x3 (0.2x3)
FAQ100 23 (0.10)
FVQ100 28 (0.19)
(Twin)
(Triple)
10. Rated power input of each model is tabulated below. (Pair)
Model Heating
FCQH100D 2.95
FCQ100C 3.28
FBQ100C 3.07
FHQ100 3.85
FCQ35Cx2 3.55
FFQ35x2 3.44
FBQ35x2 3.15
FHQ35x2 3.89
FCQ35Cx3 3.55
FFQ35x3 3.44
FBQ35x3 3.15
FHQ35x3 3.89
FAQ100 3.49
FUQ100 3.49
(Twin)
Model Heating (Triple)
Model Heating
• Split Sky Air • Outdoor Units
16
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-3
Heating capacity tables
RZQS125DV1
1 5
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity (kW) Heating capacity
Indoor EDB
-15 TC (kW)
(°C)
-10 CPI (-)
TC (kW)
CPI (-)
Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)
6 TC (kW)
10 CPI (-)
TC (-)
CPI (-)
3TW31732-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Heating capacity include the drop of frost formation. 8. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(Pair)
Model AFR (BF)
FCQH125D 34 (0.19)
FCQ125C 27.5 (0.19)
FBQ125C 39 (0.16)
FHQ125 30 (0.13)
Model AFR (BF)
FCQ60Cx2 13.5x2 (0.21x2)
FFQ60x2 15x2 (0.11x2)
FBQ60Cx2 18x2 (0.15x2)
FHQ60x2 17x2 (0.2x2)
Model AFR (BF)
FCQ50Cx3 12.5x3 (0.21x3)
FFQ50x3 12x3 (0.16x3)
FBQ50Cx3 16x3 (0.16x3)
FHQ50x3 13x3 (0.1x3)
FDQ125 45 (0.25)
FVQ125 32 (0.16)
(Twin)
(Triple) (Double Twin)
Model AFR (BF)
FCQ35Cx4 10.5x4 (0.28x4)
FFQ35x4 10x4 (0.25x4)
FBQ35Cx4 16x4 (0.15x4)
FHQ35x4 13x4 (0.2x4)
9. Rated power input of each model is tabulated below. (Pair)
Model Heating
FCQH125D 3.79
FCQ125C 4.06
FBQ125C 4.11
FHQ125 4.86
FCQ60Cx2 4.68
FFQ60x2 4.34
FBQ60x2 4.19
FHQ60x2 4.84
FCQ50Cx3 4.68
FFQ50x3 4.34
FBQ50x3 4.19
FHQ50x3 4.84
FAQ125 4.36
FUQ125 3.97
(Twin)
Model Heating (Triple)
Model Heating
17
(Double Twin)
Model Heating
• Split Sky Air • Outdoor Units
FCQ35Cx4 4.68
FFQ35x4 4.34
FBQ35x4 4.19
FHQ35x4 4.84
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-3
Heating capacity tables
3
RZQS140DV1 Heating
Coefficient of power input. (-)
1 5
Rated point
Capacity range
Heating capacity (kW) Heating capacity
Indoor EDB
-15 TC (kW)
(°C)
-10 CPI (-)
TC (kW)
CPI (-)
Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)
6 TC (kW)
10 CPI (-)
TC (-)
CPI (-)
3TW31742-2
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
(Pair)
Model AFR (BF)
FCQH140D 34 (0.20)
FCQ140C 27.5 (0.22)
Model AFR (BF)
FCQH71Dx2 FCQ71Cx2 21x2 15.5x2 (0.17x2) (0.19x2)
FBQ71Cx2 18x2 (0.08x2)
FHQ71x2 17x2 (0.1x2)
Model AFR (BF)
FCQ50Cx3 12.5x3 (0.21x3)
FBQ50Cx3 16x3 (0.16x3)
FHQ50x3 13x3 (0.1x3)
(Twin)
FAQ71x2 19x2 (0.08x2)
(Triple)
(Double Twin)
FFQ50x3 12x3 (0.16x3)
Model AFR (BF)
FCQ35Cx4 10.5x4 (0.28x4)
FFQ35x4 10x4 (0.25x4)
FBQ35Cx4 16x4 (0.15x4)
FHQ35x4 13x4 (0.2x4)
10. Rated power input of each model is tabulated below. (Pair)
Model Heating
FCQH125D 4.69
FCQ125C 4.98
(Twin)
Model Heating
FCQH71Dx2 FCQ71Cx2 5.26 5.46
FBQ71Cx2 5.06
FHQ71x2 5.70
FCQ50Cx3 5.46
FBQ50x3 5.06
FHQ50x3 5.70
(Double Twin)
(Triple)
Model Heating
FAQ71x2 5.54
FFQ50x3 5.61
• Split Sky Air • Outdoor Units
Model Heating
FCQ35Cx4 5.46
FFQ35x4 5.61
FBQ35x4 5.06
FHQ35x4 5.70
18
• Outdoor Units • R-410A • RZQS-DV1
5
Capacity tables
5-3
Heating capacity tables
RZQS140DV1
1 5
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity (kW) Heating capacity
Indoor EDB
-15 TC (kW)
(°C)
-10 CPI (-)
TC (kW)
CPI (-)
Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)
6 TC (kW)
10 CPI (-)
TC (-)
CPI (-)
3TW31742-3
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair)
Model AFR (BF)
FBQ140C 41 (0.14)
10. Rated power input of each model is tabulated below. (Pair)
Model Heating
19
FBQ140C 4.67
• Split Sky Air • Outdoor Units
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R-410A • RZQS-DV1
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing unit (mm)
RZQS71DV1 Hole for anchor bolt 4-M12
1 2 3 4 5 6 7 8
Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet
3 1 6
3TW25144-1A
RZQS100-125-140DV1
Hole for anchor bolt 4-M12
1 2 3 4 5 6 7 8
Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet
3TW26364-1
• Split Sky Air • Outdoor Units
20
• Outdoor Units • R-410A • RZQS-DV1
6
Dimensional drawing & centre of gravity
6-2
Centre of gravity
RZQS71DV1
1 6
4TW30469-3
RZQS100,125,140DV1
4TW29169-4
21
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS-DV1
7
Piping diagram
3
RZQS71-140DV1 (Pair)
1
Electronic expansion valve
7 Filter
Filter
Heat exchanger
4-way valve
Heat exchanger High pressure switch
Low pressure sensor
Field piping J9.5 C1220T-0
Service port 5/16″
Compressor Filter Field piping J15.9 C1220T-0 Accumulator
Indoor unit
Heating Cooling
Outdoor unit Stop valve (with service port 5/16’ flare)
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
3TW29165-1
RZQS71-140DV1 (Twin) Electronic expansion valve
Heat exchanger
Filter
Filter
Heat exchanger
Field piping Filter
4-way valve
Field piping
Indoor unit Low pressure sensor
High pressure switch
Heat exchanger
Branch duct connection
Service port 5/16″
Field piping J9.5
Compressor
Option Field piping J15.9
Accumulator
Outdoor unit
Field piping
Filter
Indoor unit
Heating Cooling
Field piping
Stop valve (with service port 5/16’ flare)
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Outdoor Units
3TW29165-2
22
• Outdoor Units • R-410A • RZQS-DV1
7
Piping diagram
RZQS100,125,140DV1 (Triple) Indoor unit Heat exchanger
1
Electronic expansion valve
7
Stop valve (with service port 5/16’ flare)
Heat exchanger Filter
Filter
Field piping
Filter
Field piping
Indoor unit Heat exchanger
4-way valve
Low pressure High pressure switch sensor
Field piping J9.5
Field piping Field piping
Filter
Field piping J15.9 Indoor unit Heat exchanger
Service port 5/16″
Compressor
Branch duct connection Option
Accumulator
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. Heating Cooling
Field piping
Filter
Outdoor unit
Field piping
3TW29165-3
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQS125-140DV1 (Double twin) Heat exchanger
Indoor unit
Electronic expansion valve Field piping
Filter
Filter
Field piping
Heat exchanger
Indoor unit
4-way valve
Field piping
Low pressure High pressure sensor switch
Field piping
Heat exchanger
Indoor unit
Heat exchanger
Field piping J9.5 Field piping J15.9
Filter
Filter
Branch duct connection Option
Field piping J9.5
Service port 5/16″
Compressor Field piping J15.9
Accumulator Field piping
Filter
Outdoor unit
Field piping
Heat exchanger
Stop valve (with service port 5/16’ flare)
Heating Cooling
Field piping J9.5 Field piping J15.9 Field piping
Filter
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
Field piping
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
23
• Split Sky Air • Outdoor Units
3TW29165-4
• Outdoor Units • R-410A • RZQS-DV1
8
Wiring diagram
8-1
Wiring diagram
3
RZQS71DV1
Indoor
Outdoor ON OFF
(Note 4)
El. comp. Assy Position of elements
: Printed circuit board (Main) : Printed circuit board (Inverter) : Push button switch : Capacitor : Dip switch : Fuse (T 6.3A / 250V) : Fuse (T 3.15A / 250V) : Light emitting diode (service monitor orange) : Light emitting diode (service monitor green) : Magnetic relay (Y1S) : Magnetic relay : Magnetic relay : Reactor : Motor (compressor) : Motor (fan) : Switching power supply : Field earth leakage breaker (30mA) : Resistor : Resistor : Thermistor (air) : Thermistor (discharge) : Thermistor (Suction) : Thermistor (Heat exchanger) : Thermistor (Thermistor (heat exchanger middle)) : Thermistor (liquid) : Thermistor (fin) : Signal receiver circuit : Pressure sensor : Pressure switch (High) : Signal transmission circuit : Power module : Diode module : IGBT : Terminal strip (Power supply) : Electronic expansion valve : Solenoid valve (4 way valve) : Noise filter (ferrite core) : Noise filter
1 8
Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. L: Live, N: Neutral, : Terminal strip : Connector : Connection 3. : Protective earth (screw) : Relay connector : Noiseless earth : Terminal 4. Refer to the option manual, for connecting wiring to x6A. 5. Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange BRN: Brown / GRN: Green / YLW: Yellow 8. Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.
Position of compressor terminal
(Back)
A1P A2P BS1∼BS4 C1∼C3 DS1 F1U F6U H1P∼7P (A2P) HAP (A1P) K1R K10R K11R L1R M1C M1F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T R10T RC S1NPH S1PH TC V1R V2R,V3R V1T X1M Y1E Y1S Z1C Z1F∼Z4F
(Front)
2TW30466-1B RZQS100-140DV1
Indoor
Outdoor ON OFF
(Note 4)
El. comp. Assy Position of elements Position of compressor terminal Wire entrance (Back)
(Front)
A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1HC F1U, F3U, F4U F6U H1P∼7P (A2P) HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T R10T RC S1NPH S1PH TC V1R V2R,V3R V1T X1M Y1E Y1S Z1C Z1F∼Z4F
: Printed circuit board (Main) : Printed circuit board (Inverter) : Printed circuit board (Noise filter) : Printed circuit board : Push button switch : Capacitor : Dip switch : Crankcase heater : Fuse (T 6.3A / 250V) : Fuse (T 5,0A / 250V) : Light emitting diode (service monitor orange) (H2P) Prepare, Test --------- Flickering Malfunction Detection -- Light up : Light emitting diode (service monitor green) : Magnetic relay (Y1S) : Magnetic relay (E1HC) : Magnetic relay : Magnetic relay : Reactor : Motor (compressor) : Motor (fan) (upper) : Motor (fan) (lower) : Switching power supply : Field earth leakage breaker (30mA) : Resistor : Resistor : Thermistor (air) : Thermistor (discharge) : Thermistor (Suction) : Thermistor (Heat exchanger) : Thermistor (Thermistor (heat exchanger middle)) : Thermistor (liquid) : Thermistor (fin) : Signal receiver circuit : Pressure sensor : Pressure switch (High) : Signal transmission circuit : Power module : Diode module : IGBT : Terminal strip (Power supply) : Electronic expansion valve : Solenoid valve (4 way valve) : Noise filter (ferrite core) : Noise filter
Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. L: Live, N: Neutral, : Terminal strip : Connector : Connection 3. : Protective earth (screw) : Relay connector : Noiseless earth : Terminal 4. Refer to the option manual, for connecting wiring to x6A. 5. Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange BRN: Brown / GRN: Green / YLW: Yellow 8. Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.
2TW29166-2
• Split Sky Air • Outdoor Units
24
• Outdoor Units • R-410A • RZQS-DV1
9
Sound data
9-1
Sound pressure spectrum
RZQS71DV1 - Cooling Sound pressure level (dB)
9
Sound pressure level (dB)
1
RZQS71DV1 - Heating
3TW30467-2
3TW30467-1
Octave band center frequency (Hz)
Octave band center frequency (Hz)
NOTES 1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
NOTES 1 2 3 Measuring location (discharge side)
4
RZQS100DV1 - Cooling
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
Sound pressure level (dB)
Sound pressure level (dB)
RZQS100DV1 - Heating
3TW31727-2
3TW31727-1
Octave band center frequency (Hz)
Octave band center frequency (Hz)
NOTES 1 2 3 4
25
Measuring location (discharge side)
NOTES
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
1 2 3 Measuring location (discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
Measuring location (discharge side)
• Outdoor Units • R-410A • RZQS-DV1
9
Sound data
9-1
Sound pressure spectrum
RZQS125DV1 - Cooling
3
Sound pressure level (dB)
Sound pressure level (dB)
RZQS125DV1 - Heating
1 9
3TW29167-2
3TW29167-1
Octave band center frequency (Hz)
Octave band center frequency (Hz)
NOTES 1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
NOTES 1 2 3 Measuring location (discharge side)
4
RZQS140DV1 - Cooling
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
Measuring location (discharge side)
Sound pressure level (dB)
Sound pressure level (dB)
RZQS140DV1 - Heating
3TW29177-2
3TW29177-1
Octave band center frequency (Hz)
Octave band center frequency (Hz)
NOTES 1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
NOTES 1 2 3 Measuring location (discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa
Measuring location (discharge side)
26
• Outdoor Units • R-410A • RZQS-DV1
9
Sound data
9-2
Sound power spectrum
9
Sound power level (dB)
1
RZQS100DV1
Sound power level (dB)
RZQS71DV1
3TW30467-3
3TW0477-3
Octave band center frequency (Hz)
NOTES
NOTES
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744
1 2 3
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744
1 2 3
Sound power level (dB)
RZQS140DV1
Sound power level (dB)
RZQS125DV1
3TW29167-3
Octave band center frequency (Hz)
3TW29177-3
NOTES 1 2 3
27
Octave band center frequency (Hz)
Octave band center frequency (Hz)
NOTES
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744
• Split Sky Air • Outdoor Units
1 2 3
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744
• Outdoor Units • R-410A • RZQS-DV1
10
Installation
10 - 1 Installation method
3
RZQS71-140DV1 A. Non stacked installation
Legend Suction side obstacle
1
Discharge side obstacle
10
Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
In these cases, only 2 units can be installed.
This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models.
B. Stacked installation 1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation 1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral connection per row
Relation of dimensions of H, A, and L are shown in the table below. L≤H H