Daikin Sky Air (RZQS-DV1) Outdoor Technical Data Book [PDF]

  • 0 0 0
  • Suka dengan makalah ini dan mengunduhnya? Anda bisa menerbitkan file PDF Anda sendiri secara online secara gratis dalam beberapa menit saja! Sign Up
File loading please wait...
Citation preview

• Outdoor Units • R-410A • RZQS-DV1



1 t A i n y U k 1S r V o AD t o0- i d1S lt4Q puZ- SR•O •



1



Outdoor units for pair, twin, triple, double twin application The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners.







During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy.







Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.







The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level







Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency







An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures.







A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions



1



1



Features



• Split Sky Air • Outdoor Units



• Outdoor Units • R-410A • RZQS-DV1



2



Specifications



3



2-1 NOMINAL CAPACITY AND NOMINAL INPUT



RZQS71D7V1B



RZQS100D7V1B



RZQS125D7V1B



RZQS140D7V1B



FCQ71C7VEB



FCQ100C7VEB



FCQ125C7VEB



FCQ140C7VEB



For combination indoor units + outdoor units



Indoor Units



Cooling capacity



Standard



kW



7.1



10.0



12.5



14.0



Heating capacity



Standard



kW



8.0



11.2



14.0



16.0



Power Input For combination indoor units + outdoor units



1 Cooling



Standard



kW



2.28



3.22



4.02



5.36



Heating



Standard



kW



2.35



3.28



4.06



4.98



EER



Nominal



3.11



3.11



3.11



2.61



COP



Nominal



3.41



3.41



3.45



3.21



Energy Label



Cooling



B



B



B



D



Heating



B



B



B



C



1,141



1,608



2,010



2,682



Annual energy consumption kWh



FCQH71D7VEB



FCQH100D7VEB



FCQH125D7VEB



FCQH140D7VEB



Cooling capacity



Indoor Units Standard



kW



7.1



10.0



12.5



14.0



Heating capacity



Standard



kW



8.0



11.2



14.0



16.0



Power Input For combination indoor units + outdoor units



Cooling



Standard



kW



2.15



2.90



3.88



4.65



Heating



Standard



kW



2.16



2.95



3.79



4.69



EER



Nominal



3.30



3.45



3.22



3.01



COP



Nominal



3.70



3.80



3.69



3.41



Energy Label



Cooling



A



A



A



B



Heating



A



A



A



B



1,076



1,449



1,941



2,326



Annual energy consumption kWh



FBQ71C7VEB



FBQ100C7VEB



FBQ125C7VEB



FBQ140C7VEB



Cooling capacity



Indoor Units Standard



kW



7.1



10.0



12.5



13.4



Heating capacity



Standard



kW



8.0



11.2



14.0



15.0



Power Input For combination indoor units + outdoor units



Cooling



Standard



kW



2.18



3.03



3.98



4.77



Heating



Standard



kW



2.25



3.07



4.11



4.67



EER



Nominal



3.26



3.30



3.14



2.81



COP



Nominal



3.55



3.65



3.41



3.21



Energy Label



Cooling



A



A



B



C



Heating



B



A



B



C



1,089



1,515



1,990



2,384



Annual energy consumption kWh



FHQ71BVV1B



FHQ100BVV1B



FHQ125BVV1B



Cooling capacity



Indoor Units Standard



kW



7.1



10.0



12.5



Heating capacity



Standard



kW



8.0



11.2



14.0



Power Input For combination indoor units + outdoor units



Cooling



Standard



kW



2.51



3.56



4.55



Heating



Standard



kW



2.75



3.85



4.86



EER



Nominal



2.83



2.81



2.75



COP



Nominal



2.91



2.91



2.88



Energy Label



Cooling



C



C



D



Heating



D



D



D



1,254



1,779



2,273



Annual energy consumption kWh



FAQ71BVV1B



FAQ100BVV1B



FDQ125B8V3B9



Cooling capacity



Indoor Units Standard



kW



7.1



10.0



12.5



Heating capacity



Standard



kW



8.0



11.2



14



Cooling



Standard



kW



2.44



3.56



4.30



Heating



Standard



kW



2.49



3.49



3.97



Power Input



• Split Sky Air • Outdoor Units



2



2



• Outdoor Units • R-410A • RZQS-DV1



2



Specifications



2-1 NOMINAL CAPACITY AND NOMINAL INPUT



1



For combination indoor units + outdoor units



2



RZQS71D7V1B



RZQS100D7V1B



RZQS125D7V1B



Nominal



2.91



2.81



2.91



COP



Nominal



3.21



3.21



3.53



Energy Label



Cooling



C



C



C



Heating



C



C



B



1,220



1,779



2,148



EER



Annual energy consumption kWh



FVQ71BV1B



FVQ100BV1B



FVQ125BV1B



Cooling capacity



Indoor Units Standard



kW



7.1



10.0



12.5



Heating capacity



Standard



kW



8.0



11.2



14.0



Power Input For combination indoor units + outdoor units



Cooling



Standard



kW



2.53



3.56



4.45



Heating



Standard



kW



2.49



3.49



4.36



EER



Nominal



2.81



2.81



2.81



COP



Nominal



3.21



3.21



3.21



Energy Label



Cooling



C



C



C



Heating



C



C



C



1,265



1,779



2,225



RZQS71D7V1B



RZQS100D7V1B



Annual energy consumption kWh



2-2



TECHNICAL SPECIFICATIONS



Casing



Colour



Dimensions



Unit



Weight



Paintable galvanized steel plate Height



mm



770



1,170



1,170



1,170



Width



mm



900



900



900



900



Depth



mm



320



320



320



320



Height



mm



900



1,349



1,349



1,349



Width



mm



980



980



980



980



Depth



mm



420



420



420



420



kg



68



103



103



103



Unit Packed Unit



Heat Exchanger



Dimensions



Length



kg



72



119



119



119



mm



857



857



857



857



2



2



2



2



mm



1.4



1.4



1.4



1.4



Nr of Rows Fin Pitch



Nr of Passes Face Area







Nr of Stages



8



10



10



10



0.641



0.98



0.98



0.98



34



52



52



52



Tube type Fin



Hi-XSS(8) Type



WF fin



Treatment Fan



Anti-corrosion treatment (PE)



Type



Propeller



Discharge direction



Horizontal



Quantity



1



2



2



2



Air Flow Rate (nominal at 230V)



Cooling



m³/min



52



96



100



97



Heating



m³/min



48



90



90



90



Motor



Quantity Model



Motor



Fan



Speed (nominal)



Motor



Steps



1



2



2



2



KFD-325-70-8A



Brushless DC Motor



Brushless DC Motor



Brushless DC Motor



8



8



8



8



rpm Cooling (Standard )



800



800



850



830



rpm Heating (Standard )



745



760



760



760



Output



70



70



70



70



W



Drive



3



RZQS140D7V1B



Ivory White



Material



Packing



RZQS125D7V1B



RZQS140D7V1B



Direct drive



• Split Sky Air • Outdoor Units



• Outdoor Units • R-410A • RZQS-DV1



2 2-2



Specifications TECHNICAL SPECIFICATIONS



Compressor



Quantity Motor



RZQS71D7V1B



RZQS100D7V1B



RZQS125D7V1B



RZQS140D7V1B



1



1



1



1



Model



2YC63DXD



JT100G-VD



JT100G-VD



JT100G-VD



Type



Hermetically sealed swing compressor



Hermetically sealed scroll compressor



Hermetically sealed scroll compressor



Hermetically sealed scroll compressor



1,700



2,200



2,200



2,200



33



33



33



-5.0



Motor Output



W



Crankcas W e Heater Starting Method Operation Range



Sound Level (nominal)



Cooling



°CDB



-5.0



-5.0



-5.0



Max



°CDB



46



46



46



46



Heating



Min



°CWB



-15



-15



-15



-15



Max



°CWB



15.5



15.5



15.5



15.5



Cooling



Sound Power



dBA



65



67



67



68



Sound dBA Pressure (Standard )



49



51



51



52



Sound dBA Pressure (Standard )



51



55



53



54



dBA



47



49



49



50



2.75



3.7



3.7



3.7



Sound Level (Night quiet)



Sound Pressure



Refrigerant



Type kg



Control



Expansion valve (electronic type)



Nr of Circuits Type Charged Volume Piping connections



Liquid (OD)



l Quantity



1



1



1



1



FVC50K



Daphne FVC68D



Daphne FVC68D



Daphne FVC68D



0.75



1.0



1.0



1.0



1



1



1



1



9.52



9.52



1



1



15.9



15.9



3



3



26



26



Type



Flare connection



Diameter (OD) Gas



mm



Quantity



9.52



9.52



1



1



Type



Flare connection



Diameter (OD) Drain



mm



Quantity



15.9



15.9



3



3



Type



Piping Length



Hole



Diameter (OD)



mm



Minimum



26



26



m



5



5



5



5



Maximum m



30



50



50



50



Equivalen m t



40



70



70



70



Chargele ss



30



30



30



30



Additional Refrigerant Charge Installation height difference



2



R-410A



Charge



Refrigerant Oil



1



Inverter driven



Min



Heating



3



m kg/m



Maximum m



Max. internunit level difference



m



see installation manual 4PW49302-1 15



30



30



30



0.5



0.5



0.5



0.5



Heat Insulation



Both liquid and gas pipes



Defrost Method



Pressure equalising



Defrost Control



Temperature



Capacity Control Method



Inverter controlled



• Split Sky Air • Outdoor Units



4



• Outdoor Units • R-410A • RZQS-DV1



2 2-2



Specifications TECHNICAL SPECIFICATIONS



RZQS71D7V1B



RZQS100D7V1B



Safety Devices



RZQS125D7V1B



RZQS140D7V1B



High pressure switch Fan motor thermal protector



1 2



Fuse Standard Accessories



Item



Tie-wraps



Quantity



2



2



Item



2



2



1



1



Installation manual



Quantity



1



Notes



1



Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 5m, level difference : 0m. Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 5m, level difference : 0m



2-3



ELECTRICAL SPECIFICATIONS



Power Supply



RZQS71D7V1B



RZQS100D7V1B



Name Phase



Current Wiring connections



Hz



Voltage



V Minimum



50



50



50



50 220-240



V



198



198



198



198



Maximum V



264



264



264



264



32



32



Minimum Ssc (²) value



kVa



Recomended fuses



A



For Power Supply



RZQS140D7V1B



1~



Frequency Voltage range



RZQS125D7V1B



V1



Dummy 20



32



Remark



see installation manual 4PW49302-1



For connection Remark with indoor



see installation manual 4PW49302-1



Power Supply Intake



Outdoor unit only



Notes



See separate drawings for electrical data (1) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase. (2) Short-circuit power Power supply to the FDQ indoor unit is separate



5



• Split Sky Air • Outdoor Units



• Outdoor Units • R-410A • RZQS-DV1



3



Electrical data



3



RZQS71-140DV1 Unit combination Indoor unit Outdoor unit



Hz-volts



Power supply Comp. Voltage range MCA TOCA MFA MSC RLA



OFM kW



IFM FLA



kW



FLA



1 3



NOTES 1



2 3



4 5



6 7



RLA is based on the following conditions: Power supply: 50Hz - 230V Cooling Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Heating Indoor temperature 20.0°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)



SYMBOLS MCA TOCA MFA MSC RLA OFM IFM FLA kW



: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (A) (See note 7) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)



3D063321



• Split Sky Air • Outdoor Units



6



• Outdoor Units • R-410A • RZQS-DV1



4



Options



RZQ(S)71-140DV1 Kit name



1 4



Name of option



RZQ71D7V1B



RZQ100D7V1B



RZQ125D7V1B



RZQ140D7V1B



RZQS71D7V1B



RZQS100D7V1B



RZQS125D7V1B



RZQS140D7V1B



-



RZQ100B8W1B



RZQ125B8W1B



RZQ140B8W1B



Central drain plug



EKDK04 Twin



Refrigerant branch piping



KHRQ22M20TA (KHRQ58T): see note



Triple



-



Double-twin



-



-



Demand adapter kit



KHRQ127H (KHRQ58H): see note KHRQ22M20TA (KHRQ58T): see note (3x) KRP58M51



NOTE 1



For RZQ100-140B8W1B in combination with FCQ35-71C, FCQH71C or FCQH71D use the refrigerant branch piping mentioned between brackets.



3TW26739-1F



7



• Split Sky Air • Outdoor Units



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-1



Combination table



3



RZQ(S)71-140DV1 Multi Combination Possibilities:



P = Pair



71



100



125



140



2 = Twin



35+35



50+50



60+60



71+71



3 = Triple



35+35+35



4 = Double Twin



50+50+50 (*)



50+50+50 (*)



35+35+35+35 (*)



35+35+35+35



1 5



(*) Max capacity depend on outdoor unit



RZQ71D7V1B



P 2



P



2



4



3



4



3



2



4



3



4



3



2



2



4



3



4



3



P 2



P



2



4



3



4



3



P



FVQ125BV1B



FVQ71BV1B



FVQ125BV1B



FVQ71BV1B



FVQ100BV1B



FDQ125B8V3B



Floor standing



P P



2



FVQ100BV1B



FDQ125B8V3B



FAQ71BVV1B



FAQ100BVV1B



FUQ125BVV1B



FUQ71BVV1B



P P



2



FAQ100BVV1B



Wall mounted High ESP Duct FAQ71BVV1B



FUQ125BVV1B



FHQ125BVV1B



P 2



4way ceiling



P



3



FUQ100BVV1B



FHQ125BVV1B



FHQ71BVV1B



FHQ60BVV1B



FHQ100BVV1B



2



FHQ100BVV1B



FHQ35BVV1B



FBQ140C7VEB



2 P



2



2



P P



FUQ100BVV1B



3



Floor standing



P



P



FUQ71BVV1B



4



2



Wall mounted High ESP Duct



P



Ceiling suspended



P



3



FHQ50BVV1B



FHQ35BVV1B



FBQ140C7VEB



FBQ125C7VEB



FBQ71C7VEB



FBQ100C7VEB



FBQ60C7VEB



2



3



P



3



New Duct (medium ESP) FBQ35C7VEB



FFQ60B8V1B



FFQ50B8V1B



2



4



P P



FHQ71BVV1B



3



P



2



FHQ60BVV1B



4



2



4way ceiling



P



3



FHQ50BVV1B



3



FBQ125C7VEB



3



4



2 P



FBQ100C7VEB



4



2



2



FBQ71C7VEB



3



Ceiling suspended



P



3



FBQ60C7VEB



4



FFQ35B8V1B



FCQ140C7VEB P



FBQ50C7VEB



FFQ60B8V1B



FBQ35C7VEB



FFQ50B8V1B 2



2 P



2



2



3



2x2 cassette



P 2



New Duct (medium ESP)



FBQ50C7VEB



P



P



3



FFQ35B8V1B



FCQ140C7VEB



FCQ125C7VEB



FCQ71C7VEB



FCQ100C7VEB



2



2 P



RZQ125D7V1B



FCQ60C7VEB



FCQ50C7VEB



FCQH140D7VEB



FCQ35C7VEB



3



P



Thin cassette



P



RZQ100D7V1B RZQ140D7V1B



4



2



FCQ125C7VEB



Model name



3



HH Cassette FCQH71D7VEB



Sky-air



P



4



2 P



FCQ100C7VEB



2



2



FCQ71C7VEB



RZQ140B8W1B



P



2x2 cassette



P



3



FCQ60C7VEB



RZQ140D7V1B



2 P



FCQ50C7VEB



RZQ125B8W1B



P



FCQ35C7VEB



RZQ125D7V1B



Thin cassette



FCQH140D7VEB



RZQ100B8W1B



FCQH125D7VEB



RZQ71D7V1B RZQ100D7V1B



FCQH100D7VEB



Model name



FCQH125D7VEB



FCQH71D7VEB



HH Cassette FCQH100D7VEB



Sky-air



P P



P



2



NOTES



1 2



Individual indoor capacities are not given because the combinations are for simultaneous operation (= indoor units installed in the same room) When different indoor models are used in combination, designate the remote control that is equipped with the most function as the main unit.



3TW26739-2C



• Split Sky Air • Outdoor Units



8



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-2



Cooling capacity tables



RZQS71DV1



1 5



Coefficient of power input. (-)



Cooling



Capacity range



Rated point



Cooling capacity (kW) Cooling capacity



Indoor



Outdoor temp. (°CDB)



EWB



EDB



(°C)



(°C)



TC (kW)



25 SHC (kW)



CPI (-)



TC (kW)



30 SHC (kW)



CPI (-)



TC (kW)



35 SHC (kW)



CPI (-)



TC (kW)



40 SHC (kW)



CPI (-)



3DTW3172-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FCQH71D 21 (0.17)



FCQ71C 15.5 (0.19)



FBQ71 18 (0.08)



FHQ71 17 (0.10)



Model AFR (BF)



FCQ35Cx2 10.5x2 (0.28x2)



FFQ35x2 10x2 (0.25x2)



FBQ35Cx2 15x2 (0.15x2)



FHQ35x2 13x2 (0.2x2)



FAQ71 19 (0.08)



FVQ71 18 (0.16)



(Twin)



8. Rated power input of each model is tabulated below. (Pair)



Model Cooling



FCQH71D 2.15



FCQ71C 2.28



FBQ71C 2.18



FHQ71 2.51



FCQ35Cx2 2.59



FFQ35x2 2.61



FBQ35x2 2.25



FHQ35x2 2.66



FAQ71 2.44



FVQ71 2.53



(Twin)



Model Cooling



9



• Split Sky Air • Outdoor Units



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



Caution: TC and SHC are shown by kW



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-2



Cooling capacity tables



3



RZQS100DV1 Cooling



Coefficient of power input. (-)



1 5



Capacity range



Rated point



Cooling capacity (kW) Cooling capacity



Indoor



Outdoor temp. (°CDB)



EWB



EDB



(°C)



(°C)



TC (kW)



25 SHC (kW)



CPI (-)



TC (kW)



30 SHC (kW)



CPI (-)



TC (kW)



35 SHC (kW)



CPI (-)



TC (kW)



40 SHC (kW)



CPI (-)



3TW31722-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FCQH100D 34 (0.17)



FCQ100C 23.5 (0.16)



FBQ100C 32 (0.13)



FHQ100 24 (0.14)



Model AFR (BF)



FCQ50Cx2 12.5x2 (0.21x2)



FFQ50x2 12x2 (0.16x2)



FBQ50Cx2 16x2 (0.16x2)



FHQ50x2 13x2 (0.1x2)



Model AFR (BF)



FCQ35Cx3 10.5x3 (0.28x3)



FFQ35x3 10x3 (0.25x3)



FBQ35Cx3 16x3 (0.15x3)



FHQ35x3 13x3 (0.2x3)



FAQ100 23 (0.10)



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



Caution: TC and SHC are shown by kW



FVQ100 28 (0.19)



(Twin)



(Triple)



8. Rated power input of each model is tabulated below. (Pair)



Model Cooling



FCQH100D 2.90



FCQ100C 3.22



FBQ100C 3.03



FHQ100 3.56



FCQ35Cx2 3.58



FFQ35x2 3.58



FBQ35x2 3.16



FHQ35x2 3.90



FCQ35Cx3 3.58



FFQ35x3 3.58



FBQ35x3 3.16



FHQ35x3 3.90



FAQ100 3.56



FVQ100 3.56



(Twin)



Model Cooling (Triple)



Model Cooling



• Split Sky Air • Outdoor Units



10



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-2



Cooling capacity tables



RZQS125DV1



1 5



Coefficient of power input. (-)



Cooling



Capacity range



Rated point



Cooling capacity (kW) Cooling capacity



Indoor



Outdoor temp. (°CDB)



EWB



EDB



(°C)



(°C)



TC (kW)



25 SHC (kW)



CPI (-)



TC (kW)



30 SHC (kW)



CPI (-)



TC (kW)



35 SHC (kW)



CPI (-)



TC (kW)



40 SHC (kW)



CPI (-)



3TW31732-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FCQH125D 34 (0.19)



FCQ125C 27.5 (0.19)



FBQ125C 39 (0.16)



FHQ125 30 (0.13)



Model AFR (BF)



FCQ60Cx2 13.5x2 (0.21x2)



FFQ60x2 15x2 (0.11x2)



FBQ60Cx2 18x2 (0.15x2)



FHQ60x2 17x2 (0.2x2)



Model AFR (BF)



FCQ50Cx3 12.5x3 (0.21x3)



FFQ50x3 12x3 (0.16x3)



FBQ50Cx3 16x3 (0.16x3)



FHQ50x3 13x3 (0.1x3)



FDQ125 45 (0.25)



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



Caution: TC and SHC are shown by kW



FVQ125 32 (0.16)



(Twin)



(Triple)



(Double Twin)



Model AFR (BF)



FCQ35Cx4 10.5x4 (0.28x4)



FFQ35x4 10x4 (0.25x4)



FBQ35Cx4 16x4 (0.15x4)



FHQ35x4 13x4 (0.2x4)



8. Rated power input of each model is tabulated below. (Pair)



Model Cooling



FCQH125D 3.88



FCQ125C 4.02



FBQ125C 3.98



FHQ125 4.55



FCQ60Cx2 4.17



FFQ60x2 4.22



FBQ60x2 4.18



FHQ60x2 4.57



FCQ50Cx3 4.17



FFQ50x3 4.22



FBQ50x3 4.18



FHQ50x3 4.57



FAQ125 4.45



FUQ125 3.30



(Twin)



Model Cooling (Triple)



Model Cooling



11



(Double Twin)



Model Cooling



• Split Sky Air • Outdoor Units



FCQ35Cx4 4.17



FFQ35x4 4.22



FBQ35x4 4.18



FHQ35x4 4.57



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-2



Cooling capacity tables



3



RZQS140DV1 Cooling



Coefficient of power input. (-)



1 5



Capacity range



Rated point



Cooling capacity (kW) Cooling capacity



Indoor



Outdoor temp. (°CDB)



EWB



EDB



(°C)



(°C)



TC (kW)



25 SHC (kW)



CPI (-)



TC (kW)



30 SHC (kW)



CPI (-)



TC (kW)



35 SHC (kW)



CPI (-)



TC (kW)



40 SHC (kW)



CPI (-)



3TW31742-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FCQH140D 34 (0.20)



Model AFR (BF)



FCQH71Dx2 FCQ71Cx2 21x2 15.5x2 (0.17x2) (0.19x2)



FBQ71Cx2 18x2 (0.08x2)



FHQ71x2 17x2 (0.1x2)



Model AFR (BF)



FCQ50Cx3 12.5x3 (0.21x3)



FBQ50Cx3 16x3 (0.15x3)



FHQ50x3 13x3 (0.1x3)



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



Caution: TC and SHC are shown by kW



FCQ140C 27.5 (0.22)



(Twin)



(Triple)



FAQ71x2 19x2 (0.08x2) (Double Twin)



FFQ50x3 12x3 (0.16x3)



Model AFR (BF)



FCQ35Cx4 10.5x4 (0.28x4)



FFQ35x4 10x4 (0.25x4)



FBQ35Cx4 16x4 (0.15x4)



FHQ35x4 13x4 (0.2x4)



8. Rated power input of each model is tabulated below. (Pair)



Model Cooling



FCQH140D 4.65



FCQ140C 5.36



(Twin)



Model Cooling



FCQH71Dx2 FCQ71Cx2 4.99 5.12



FBQ71Cx2 4.95



FHQ71x2 5.10



FCQ50Cx3 5.12



FBQ50x3 4.95



FHQ50x3 5.10



(Triple)



Model Cooling



FAQ71x2 5.01 (Double Twin)



FFQ50x3 4.89



Model Cooling



• Split Sky Air • Outdoor Units



FCQ35Cx4 5.12



FFQ35x4 4.89



FBQ35x4 4.95



FHQ35x4 5.10



12



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-2



Cooling capacity tables



RZQS140DV1



1 5



Coefficient of power input. (-)



Cooling



Capacity range



Rated point



Cooling capacity (kW) Cooling capacity



Indoor



Outdoor temp. (°CDB)



EWB



EDB



(°C)



(°C)



TC (kW)



25 SHC (kW)



CPI (-)



TC (kW)



30 SHC (kW)



CPI (-)



TC (kW)



35 SHC (kW)



CPI (-)



TC (kW)



40 SHC (kW)



CPI (-)



3TW31742-3



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FBQ140C 39 (0.14)



8. Rated power input of each model is tabulated below. (Pair)



Model Cooling



13



FBQ140C 4.77



• Split Sky Air • Outdoor Units



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



Caution: TC and SHC are shown by kW



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-2



Cooling capacity tables



3



RZQS71-140DV1 Capacity in function of field piping length for non-inverter



1 5



Capacity (%)



Field piping length (m) Cooling Heating



• Split Sky Air • Outdoor Units



3TW31712-1



14



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-3



Heating capacity tables



RZQS71DV1



1 5



Coefficient of power input. (-)



Heating



Rated point



Capacity range



Heating capacity (kW) Heating capacity



Indoor EDB



-15 TC (kW)



(°C)



-10 CPI (-)



TC (kW)



CPI (-)



Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)



6 TC (kW)



10 CPI (-)



TC (-)



CPI (-)



3TW31712-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FCQH71C 21 (0.17)



FCQ71C 15.5 (0.19)



FBQ71 18 (0.08)



FHQ71 17 (0.10)



Model AFR (BF)



FCQ35Cx2 10.5x2 (0.28x2)



FFQ35x2 10x2 (0.25x2)



FBQ35Cx2 16x2 (0.15x2)



FHQ35x2 13x2 (0.2x2)



FAQ71 19 (0.08)



FVQ71 18 (0.16)



(Twin)



10. Rated power input of each model is tabulated below. (Pair)



Model Heating



FCQH71D 2.16



FCQ71C 2.35



FBQ71 2.25



FHQ71 2.75



FCQ35Cx2 2.75



FFQ35x2 2.70



FBQ35Cx2 2.20



FHQ35x2 2.85



FAQ71 2.49



FVQ71 2.49



(Twin)



Model Heating



15



• Split Sky Air • Outdoor Units



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



Caution: TC and SHC are shown by kW



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-3



Heating capacity tables



3



RZQS100DV1 Heating



Coefficient of power input. (-)



1 5



Rated point



Capacity range



Heating capacity (kW) Heating capacity



Indoor EDB



-15 TC (kW)



(°C)



-10 CPI (-)



TC (kW)



CPI (-)



Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)



6 TC (kW)



10 CPI (-)



TC (-)



CPI (-)



3TW31722-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below.



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



Caution: TC and SHC are shown by kW



(Pair)



Model AFR (BF)



FCQH100D 34 (0.17)



FCQ100C 23.5 (0.16)



FBQ100C 32 (0.13)



FHQ100 24 (0.14)



Model AFR (BF)



FCQ35Cx2 12.5x2 (0.21x2)



FFQ35x2 12x2 (0.16x2)



FBQ35Cx2 16x2 (0.16x2)



FHQ35x2 13x2 (0.1x2)



Model AFR (BF)



FCQ35Cx3 10.5x3 (0.28x3)



FFQ35x3 10x3 (0.25x3)



FBQ35Cx3 16x3 (0.15x3)



FHQ35x3 13x3 (0.2x3)



FAQ100 23 (0.10)



FVQ100 28 (0.19)



(Twin)



(Triple)



10. Rated power input of each model is tabulated below. (Pair)



Model Heating



FCQH100D 2.95



FCQ100C 3.28



FBQ100C 3.07



FHQ100 3.85



FCQ35Cx2 3.55



FFQ35x2 3.44



FBQ35x2 3.15



FHQ35x2 3.89



FCQ35Cx3 3.55



FFQ35x3 3.44



FBQ35x3 3.15



FHQ35x3 3.89



FAQ100 3.49



FUQ100 3.49



(Twin)



Model Heating (Triple)



Model Heating



• Split Sky Air • Outdoor Units



16



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-3



Heating capacity tables



RZQS125DV1



1 5



Coefficient of power input. (-)



Heating



Capacity range



Rated point



Heating capacity (kW) Heating capacity



Indoor EDB



-15 TC (kW)



(°C)



-10 CPI (-)



TC (kW)



CPI (-)



Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)



6 TC (kW)



10 CPI (-)



TC (-)



CPI (-)



3TW31732-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 4. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 5. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 6. The value contains less than 5% error acording to indoor unit type. 7. Heating capacity include the drop of frost formation. 8. Air flow rate and BF are tabulated below.



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



Caution: TC and SHC are shown by kW



(Pair)



Model AFR (BF)



FCQH125D 34 (0.19)



FCQ125C 27.5 (0.19)



FBQ125C 39 (0.16)



FHQ125 30 (0.13)



Model AFR (BF)



FCQ60Cx2 13.5x2 (0.21x2)



FFQ60x2 15x2 (0.11x2)



FBQ60Cx2 18x2 (0.15x2)



FHQ60x2 17x2 (0.2x2)



Model AFR (BF)



FCQ50Cx3 12.5x3 (0.21x3)



FFQ50x3 12x3 (0.16x3)



FBQ50Cx3 16x3 (0.16x3)



FHQ50x3 13x3 (0.1x3)



FDQ125 45 (0.25)



FVQ125 32 (0.16)



(Twin)



(Triple) (Double Twin)



Model AFR (BF)



FCQ35Cx4 10.5x4 (0.28x4)



FFQ35x4 10x4 (0.25x4)



FBQ35Cx4 16x4 (0.15x4)



FHQ35x4 13x4 (0.2x4)



9. Rated power input of each model is tabulated below. (Pair)



Model Heating



FCQH125D 3.79



FCQ125C 4.06



FBQ125C 4.11



FHQ125 4.86



FCQ60Cx2 4.68



FFQ60x2 4.34



FBQ60x2 4.19



FHQ60x2 4.84



FCQ50Cx3 4.68



FFQ50x3 4.34



FBQ50x3 4.19



FHQ50x3 4.84



FAQ125 4.36



FUQ125 3.97



(Twin)



Model Heating (Triple)



Model Heating



17



(Double Twin)



Model Heating



• Split Sky Air • Outdoor Units



FCQ35Cx4 4.68



FFQ35x4 4.34



FBQ35x4 4.19



FHQ35x4 4.84



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-3



Heating capacity tables



3



RZQS140DV1 Heating



Coefficient of power input. (-)



1 5



Rated point



Capacity range



Heating capacity (kW) Heating capacity



Indoor EDB



-15 TC (kW)



(°C)



-10 CPI (-)



TC (kW)



CPI (-)



Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)



6 TC (kW)



10 CPI (-)



TC (-)



CPI (-)



3TW31742-2



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below.



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



Caution: TC and SHC are shown by kW



(Pair)



Model AFR (BF)



FCQH140D 34 (0.20)



FCQ140C 27.5 (0.22)



Model AFR (BF)



FCQH71Dx2 FCQ71Cx2 21x2 15.5x2 (0.17x2) (0.19x2)



FBQ71Cx2 18x2 (0.08x2)



FHQ71x2 17x2 (0.1x2)



Model AFR (BF)



FCQ50Cx3 12.5x3 (0.21x3)



FBQ50Cx3 16x3 (0.16x3)



FHQ50x3 13x3 (0.1x3)



(Twin)



FAQ71x2 19x2 (0.08x2)



(Triple)



(Double Twin)



FFQ50x3 12x3 (0.16x3)



Model AFR (BF)



FCQ35Cx4 10.5x4 (0.28x4)



FFQ35x4 10x4 (0.25x4)



FBQ35Cx4 16x4 (0.15x4)



FHQ35x4 13x4 (0.2x4)



10. Rated power input of each model is tabulated below. (Pair)



Model Heating



FCQH125D 4.69



FCQ125C 4.98



(Twin)



Model Heating



FCQH71Dx2 FCQ71Cx2 5.26 5.46



FBQ71Cx2 5.06



FHQ71x2 5.70



FCQ50Cx3 5.46



FBQ50x3 5.06



FHQ50x3 5.70



(Double Twin)



(Triple)



Model Heating



FAQ71x2 5.54



FFQ50x3 5.61



• Split Sky Air • Outdoor Units



Model Heating



FCQ35Cx4 5.46



FFQ35x4 5.61



FBQ35x4 5.06



FHQ35x4 5.70



18



• Outdoor Units • R-410A • RZQS-DV1



5



Capacity tables



5-3



Heating capacity tables



RZQS140DV1



1 5



Coefficient of power input. (-)



Heating



Capacity range



Rated point



Heating capacity (kW) Heating capacity



Indoor EDB



-15 TC (kW)



(°C)



-10 CPI (-)



TC (kW)



CPI (-)



Outdoor temp. (°CDB) -5 0 TC CPI TC CPI (kW) (-) (kW) (-)



6 TC (kW)



10 CPI (-)



TC (-)



CPI (-)



3TW31742-3



NOTES



SYMBOLS



1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 5.0 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair)



Model AFR (BF)



FBQ140C 41 (0.14)



10. Rated power input of each model is tabulated below. (Pair)



Model Heating



19



FBQ140C 4.67



• Split Sky Air • Outdoor Units



AFR: BF: EWB: EDB: TC: SHC: PI: CPI:



Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.



Caution: TC and SHC are shown by kW



(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)



• Outdoor Units • R-410A • RZQS-DV1



6



Dimensional drawing & centre of gravity



6-1



Dimensional drawing unit (mm)



RZQS71DV1 Hole for anchor bolt 4-M12



1 2 3 4 5 6 7 8



Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet



3 1 6



3TW25144-1A



RZQS100-125-140DV1



Hole for anchor bolt 4-M12



1 2 3 4 5 6 7 8



Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet



3TW26364-1



• Split Sky Air • Outdoor Units



20



• Outdoor Units • R-410A • RZQS-DV1



6



Dimensional drawing & centre of gravity



6-2



Centre of gravity



RZQS71DV1



1 6



4TW30469-3



RZQS100,125,140DV1



4TW29169-4



21



• Split Sky Air • Outdoor Units



• Outdoor Units • R-410A • RZQS-DV1



7



Piping diagram



3



RZQS71-140DV1 (Pair)



1



Electronic expansion valve



7 Filter



Filter



Heat exchanger



4-way valve



Heat exchanger High pressure switch



Low pressure sensor



Field piping J9.5 C1220T-0



Service port 5/16″



Compressor Filter Field piping J15.9 C1220T-0 Accumulator



Indoor unit



Heating Cooling



Outdoor unit Stop valve (with service port 5/16’ flare)



O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe



3TW29165-1



RZQS71-140DV1 (Twin) Electronic expansion valve



Heat exchanger



Filter



Filter



Heat exchanger



Field piping Filter



4-way valve



Field piping



Indoor unit Low pressure sensor



High pressure switch



Heat exchanger



Branch duct connection



Service port 5/16″



Field piping J9.5



Compressor



Option Field piping J15.9



Accumulator



Outdoor unit



Field piping



Filter



Indoor unit



Heating Cooling



Field piping



Stop valve (with service port 5/16’ flare)



Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.



O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe



• Split Sky Air • Outdoor Units



3TW29165-2



22



• Outdoor Units • R-410A • RZQS-DV1



7



Piping diagram



RZQS100,125,140DV1 (Triple) Indoor unit Heat exchanger



1



Electronic expansion valve



7



Stop valve (with service port 5/16’ flare)



Heat exchanger Filter



Filter



Field piping



Filter



Field piping



Indoor unit Heat exchanger



4-way valve



Low pressure High pressure switch sensor



Field piping J9.5



Field piping Field piping



Filter



Field piping J15.9 Indoor unit Heat exchanger



Service port 5/16″



Compressor



Branch duct connection Option



Accumulator



Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. Heating Cooling



Field piping



Filter



Outdoor unit



Field piping



3TW29165-3



O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe



RZQS125-140DV1 (Double twin) Heat exchanger



Indoor unit



Electronic expansion valve Field piping



Filter



Filter



Field piping



Heat exchanger



Indoor unit



4-way valve



Field piping



Low pressure High pressure sensor switch



Field piping



Heat exchanger



Indoor unit



Heat exchanger



Field piping J9.5 Field piping J15.9



Filter



Filter



Branch duct connection Option



Field piping J9.5



Service port 5/16″



Compressor Field piping J15.9



Accumulator Field piping



Filter



Outdoor unit



Field piping



Heat exchanger



Stop valve (with service port 5/16’ flare)



Heating Cooling



Field piping J9.5 Field piping J15.9 Field piping



Filter



Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.



Field piping



O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe



23



• Split Sky Air • Outdoor Units



3TW29165-4



• Outdoor Units • R-410A • RZQS-DV1



8



Wiring diagram



8-1



Wiring diagram



3



RZQS71DV1



Indoor



Outdoor ON OFF



(Note 4)



El. comp. Assy Position of elements



: Printed circuit board (Main) : Printed circuit board (Inverter) : Push button switch : Capacitor : Dip switch : Fuse (T 6.3A / 250V) : Fuse (T 3.15A / 250V) : Light emitting diode (service monitor orange) : Light emitting diode (service monitor green) : Magnetic relay (Y1S) : Magnetic relay : Magnetic relay : Reactor : Motor (compressor) : Motor (fan) : Switching power supply : Field earth leakage breaker (30mA) : Resistor : Resistor : Thermistor (air) : Thermistor (discharge) : Thermistor (Suction) : Thermistor (Heat exchanger) : Thermistor (Thermistor (heat exchanger middle)) : Thermistor (liquid) : Thermistor (fin) : Signal receiver circuit : Pressure sensor : Pressure switch (High) : Signal transmission circuit : Power module : Diode module : IGBT : Terminal strip (Power supply) : Electronic expansion valve : Solenoid valve (4 way valve) : Noise filter (ferrite core) : Noise filter



1 8



Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. L: Live, N: Neutral, : Terminal strip : Connector : Connection 3. : Protective earth (screw) : Relay connector : Noiseless earth : Terminal 4. Refer to the option manual, for connecting wiring to x6A. 5. Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange BRN: Brown / GRN: Green / YLW: Yellow 8. Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.



Position of compressor terminal



(Back)



A1P A2P BS1∼BS4 C1∼C3 DS1 F1U F6U H1P∼7P (A2P) HAP (A1P) K1R K10R K11R L1R M1C M1F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T R10T RC S1NPH S1PH TC V1R V2R,V3R V1T X1M Y1E Y1S Z1C Z1F∼Z4F



(Front)



2TW30466-1B RZQS100-140DV1



Indoor



Outdoor ON OFF



(Note 4)



El. comp. Assy Position of elements Position of compressor terminal Wire entrance (Back)



(Front)



A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1HC F1U, F3U, F4U F6U H1P∼7P (A2P) HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T R10T RC S1NPH S1PH TC V1R V2R,V3R V1T X1M Y1E Y1S Z1C Z1F∼Z4F



: Printed circuit board (Main) : Printed circuit board (Inverter) : Printed circuit board (Noise filter) : Printed circuit board : Push button switch : Capacitor : Dip switch : Crankcase heater : Fuse (T 6.3A / 250V) : Fuse (T 5,0A / 250V) : Light emitting diode (service monitor orange) (H2P) Prepare, Test --------- Flickering Malfunction Detection -- Light up : Light emitting diode (service monitor green) : Magnetic relay (Y1S) : Magnetic relay (E1HC) : Magnetic relay : Magnetic relay : Reactor : Motor (compressor) : Motor (fan) (upper) : Motor (fan) (lower) : Switching power supply : Field earth leakage breaker (30mA) : Resistor : Resistor : Thermistor (air) : Thermistor (discharge) : Thermistor (Suction) : Thermistor (Heat exchanger) : Thermistor (Thermistor (heat exchanger middle)) : Thermistor (liquid) : Thermistor (fin) : Signal receiver circuit : Pressure sensor : Pressure switch (High) : Signal transmission circuit : Power module : Diode module : IGBT : Terminal strip (Power supply) : Electronic expansion valve : Solenoid valve (4 way valve) : Noise filter (ferrite core) : Noise filter



Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. L: Live, N: Neutral, : Terminal strip : Connector : Connection 3. : Protective earth (screw) : Relay connector : Noiseless earth : Terminal 4. Refer to the option manual, for connecting wiring to x6A. 5. Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch. 6. Do not operate the unit by short-circuiting protection device S1PH 7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange BRN: Brown / GRN: Green / YLW: Yellow 8. Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.



2TW29166-2



• Split Sky Air • Outdoor Units



24



• Outdoor Units • R-410A • RZQS-DV1



9



Sound data



9-1



Sound pressure spectrum



RZQS71DV1 - Cooling Sound pressure level (dB)



9



Sound pressure level (dB)



1



RZQS71DV1 - Heating



3TW30467-2



3TW30467-1



Octave band center frequency (Hz)



Octave band center frequency (Hz)



NOTES 1 2 3 4



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



NOTES 1 2 3 Measuring location (discharge side)



4



RZQS100DV1 - Cooling



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



Sound pressure level (dB)



Sound pressure level (dB)



RZQS100DV1 - Heating



3TW31727-2



3TW31727-1



Octave band center frequency (Hz)



Octave band center frequency (Hz)



NOTES 1 2 3 4



25



Measuring location (discharge side)



NOTES



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



1 2 3 Measuring location (discharge side)



• Split Sky Air • Outdoor Units



4



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



Measuring location (discharge side)



• Outdoor Units • R-410A • RZQS-DV1



9



Sound data



9-1



Sound pressure spectrum



RZQS125DV1 - Cooling



3



Sound pressure level (dB)



Sound pressure level (dB)



RZQS125DV1 - Heating



1 9



3TW29167-2



3TW29167-1



Octave band center frequency (Hz)



Octave band center frequency (Hz)



NOTES 1 2 3 4



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



NOTES 1 2 3 Measuring location (discharge side)



4



RZQS140DV1 - Cooling



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



Measuring location (discharge side)



Sound pressure level (dB)



Sound pressure level (dB)



RZQS140DV1 - Heating



3TW29177-2



3TW29177-1



Octave band center frequency (Hz)



Octave band center frequency (Hz)



NOTES 1 2 3 4



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



NOTES 1 2 3 Measuring location (discharge side)



• Split Sky Air • Outdoor Units



4



Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa



Measuring location (discharge side)



26



• Outdoor Units • R-410A • RZQS-DV1



9



Sound data



9-2



Sound power spectrum



9



Sound power level (dB)



1



RZQS100DV1



Sound power level (dB)



RZQS71DV1



3TW30467-3



3TW0477-3



Octave band center frequency (Hz)



NOTES



NOTES



dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744



1 2 3



dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744



1 2 3



Sound power level (dB)



RZQS140DV1



Sound power level (dB)



RZQS125DV1



3TW29167-3



Octave band center frequency (Hz)



3TW29177-3



NOTES 1 2 3



27



Octave band center frequency (Hz)



Octave band center frequency (Hz)



NOTES



dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744



• Split Sky Air • Outdoor Units



1 2 3



dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744



• Outdoor Units • R-410A • RZQS-DV1



10



Installation



10 - 1 Installation method



3



RZQS71-140DV1 A. Non stacked installation



Legend Suction side obstacle



1



Discharge side obstacle



10



Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.



In these cases, only 2 units can be installed.



This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models.



B. Stacked installation 1. Obstacles exist in front of the outlet side



2. Obstacles exist in front of the air inlet



Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass.



C. Multiple-row installation 1. Installation of one unit per row



2. Installing multiple units (2 units or more) in lateral connection per row



Relation of dimensions of H, A, and L are shown in the table below. L≤H H